8
4.
Using four M6/M8 screws, securely attach the converter mounting brackets
to the mounting surface.
5.
Once the converter is securely tightened with screws to the wall, release it
from the lifting handles.
2.3 DC Connection
DANGER
Hazard of electric shock
•
Test using a meter to make sure all the circuits are de-energized. Follow
a lock-out tag-out procedure.
Ensure that the following requirement is met for installation:
•
All the components installed between the DC Source and the converter
shall be rated for at least 1000 VDC and as per the applicable installation
codes.
Table 1
PV input parameters
Parameter
ASGC 34.5TL-4P4W
Maximum input voltage
1000 VDC
Maximum input current
60 A
Maximum MPP voltage
950 V
Minimum MPP voltage
570 V
Assembling DC connector
Cable requirements:
•
Cable type: stranded, copper wire
•
Cross section: 10 mm
2
to 16 mm
2
•
Nominal voltage: UL/SCA/ICE 1000 V
•
M5 16mm
2
or M6 16mm
2
cable lugs (e.g. Klauke 3R5)