background image

 

 

 

 

25 

 

INITIAL CONFIGURATION EVALUATION 

Check the following aspects:  

 

Opening-closing of the valves: Turn on the system and generate demand in all the zones. Then, switch off and on all 
the zones to verify the associated valves are correct. 

 

ADVANCED SETTINGS 

To access the advanced configuration menu of the Blueface and Think thermostats follow the following steps: 

Blueface 

 

Think 

 Important:

 Use 

 to confirm and 

 to return.

 

SYSTEM PARAMETERS 

 

System address.

 The 

Supermaster 

option

 

allows you to impose the operation mode of the system to the rest of the 

systems connected to the CCP in a semi-forced way: 

 

 

Temperature range. 

Use this parameter to select the highest temperature in heating mode (19-30 ºC, by default 30ºC).  

 

Wireless valves.

  Allows you to associate/release a valve. Allows you to open/close the wireless channel of the 

AZX6CM1VALR module. Allows you to reset the AZX6CM1VALR module. 

 

Radio channel. 

It activates/deactivates the wireless association module of the system for thermostats. 

 

Reset system

 

(only available for master thermostat Blueface)

Resets the system and returns to factory settings. To 

reconfigure the thermostats, please check 

Initial configuration

). 

 

 

 

 

 

Press and hold

 

Operation mode: 

System 1

 

Available operation modes: 

Rest of the systems 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press once 

Press and hold 

Press and hold 

Содержание AZRA6CB1RAD

Страница 1: ...r e b m u N e g a P d r a o b p il C Installation Manual RADIANT365 AZRA6CB1RAD AZX6CM1VALR ...

Страница 2: ...1 8 ZONES AZRA6CB1RAD AZX6CM1VALR ...

Страница 3: ...irements 10 Introduction 11 System installation 11 Assembly and connection 12 AIRZONE RADIANT VALR SYSTEM FOR RADIATORS MAIN BOARD AZRA6CB1RAD 12 Assembly 12 Connection 12 AIRZONE CONTROL MODULE FOR WIRELESS VALVES VALR AZX6CM1VALR 14 Assembly 14 Connection 15 Reset 15 AIRZONE WIRELESS THERMOSTATIC VALVE ACTUATOR VALR FOR RADIATORS AZX6AC1VALR 15 Assembly 15 Connection 16 Airzone Wired thermostats...

Страница 4: ... Airzone Blueface and Think thermostats AZRA6BLUEFACEC AZRA6THINK C R 27 Blueface and Think Thermostats Warnings 27 Blueface and Think Thermostats Errors 27 Airzone Lite thermostat AZRA6LITE C R 32 LED Status 33 Navigation trees 34 Navigation Tree Blueface Thermostat 34 Navigation Tree Think Thermostat 35 ...

Страница 5: ...y are not handled appropriately The symbol of a crossed out waste bin indicates that electrical equipment should be collected separately from other urban waste For correct environmental management it must be taken to the collection centers provided for this purpose at the end of its useful life The equipment s components may be recycled Act in accordance with current regulations on environmental p...

Страница 6: ...ONE CONTROL MODULE FOR WIRELESS VALVES VALR AZX6CM1VALR Control module of radiant elements for heating stages by zone through the management of wireless valve actuators Communications with the main control board power supply through the VALR Module bus and wireless communication with the valves Mounted using DIN rail Functionalities Control of up to 10 wireless valve actuators AIRZONE WIRELESS THE...

Страница 7: ...controlling zones in Airzone systems Finished in steel and glass Wired wireless communications Powered from main control board wired or by CR2450 button battery wireless Available in white and black Functionalities Available in Spanish English French Italian German and Portuguese Control of temperature and Operation mode Master thermostat Room temperature and relative humidity reading Sleep functi...

Страница 8: ...atform Connected to router via Ethernet and communications through domotic bus Externally powered at 110 230 Vac Wall mounted Features Controls up to 32 systems 7 control relays for cooling heating modes cooling heating air demand cooling heating radiant demand Inputs for semi forced modes boiler probe and DHW control Configuration and control of zone parameters Room and set point temp operating m...

Страница 9: ...r cable formed by 4 wires 2x0 22 mm2 2x0 5mm2 AWG 20 4 wired Do not place the system bus close to high power lines fluorescent lights LED lamps motors etc It might cause interference on the communications Respect the connection polarity of each device A wrong connection may seriously damage the product For elements externally powered at 110 230 Vac for the communications it is only necessary to co...

Страница 10: ...alled Important For installations with radiant surfaces only it is recommended the installation of buffer tanks In order to install the Airzone system carefully follow these steps Connect all the necessary elements see sections Assembly and Connection Connect all the elements of the system thermostats modules etc Power the main board Check all the assembly and the connection are correct see sectio...

Страница 11: ...rzone connection bus connectors The Airzone connection bus allows you to connect all the internal components dependent on the main board to control up to 8 zones These are the elements that can be connected Blueface AZRA6BLUEFACEC Think AZRA6THINKC and Lite AZRA6LITEC thermostats If using a wired thermostat connect it in one of the 3 Airzone connection bus terminals The connection can be both a Bu...

Страница 12: ...connector The AC unit bus allows you to connect different Airzone air to water HP gateways AZX6GAWXXX To connect gateways disconnect the AC unit bus terminal and insert the connector and the fixing post of the gateway Boiler connector This output can be configured as boiler control See Blueface Advanced Configuration Menu system parameters Boiler configuration Status Stop Heating radiant Demand ON...

Страница 13: ...m will restart automatically if the supply is eventually turned off Use an independent circuit from the controlled system for the power supply Remember Once all the connections are made make sure you replace the cover properly AIRZONE CONTROL MODULE FOR WIRELESS VALVES VALR AZX6CM1VALR Assembly This module is mounted on DIN rail It should be placed and mounted in accordance with the current electr...

Страница 14: ...il LED change to searching status blue Wait for the LEDS to go back to their normal state before starting with the initial configuration process AIRZONE WIRELESS THERMOSTATIC VALVE ACTUATOR VALR FOR RADIATORS AZX6AC1VALR Assembly Airzone wireless thermostatic valve actuators are mounted on each of the valves of a heater Check that the thermostatic valve actuator is compatible with the valve body t...

Страница 15: ...om the main control board To fix it to the wall follow these steps Separate the back part of the thermostat from the wall support and make all the connections Fix the back part of the thermostat to the wall Place the display on the support once it is fixed Place the anti theft rods for additional support optional Connection The Airzone thermostats are connected to the Airzone connection bus of the...

Страница 16: ...ng batteries When a wireless Think thermostat is running out of battery it displays this icon on the screensaver In the case of wireless Lite thermostats a warning message will be displayed on the Blueface In order to know the zone of the Lite thermostat s running out of battery press on the warning icon To replace the battery separate the thermostat from its support and replace the battery CR2450...

Страница 17: ...through a 3 pin terminal Attach the wires with the terminal screws following the color code For added security secure the wires using the turret Important According to the current local and national regulations it is mandatory to add a switch or other element to disconnect the system to the external supply wiring so that a constant separation between poles is guaranteed The system will restart aut...

Страница 18: ...boiler protection Domotic bus connectors The indoor domotic bus allows you to connect the production control board with the main control board and aerothermal gateways AZX6GAWxxx The domotic bus has two terminals which are interconnected so that can be used interchangeably This system can only be connected by bus Attach the wires with the terminal screws following the color code Use the shield onl...

Страница 19: ...0 gateway AZX6GTCxxx in Flexa 3 0 Innobus Pro6 Acuazone and Innobus Pro32 main control boards Communication gateway for electromechanical units AZX6ELECTROMEC in Flexa 3 0 Innobus Pro6 Acuazone and Innobus Pro32 main control boards Infrared gateway module AZDI6MCIFR C R in Acuazone e Innobus Pro32 systems when configured as a zoning system or mixed system Gateway module AZDI6MCIFR C R in Acuazone ...

Страница 20: ... the Cloud Ethernet Production Control Board AZX6CCPWSCC It has a 4 pin terminal Disconnect the terminal to which you want to connect to the Webserver and fit the connector ASSEMBLY AND CONNECTION EVALUATION Check the following aspects The state of the LEDs of the main control board and the rest of control elements Check the self diagnose section of the data sheet of the elements If all the thermo...

Страница 21: ...y alter the process Start the radio channel search to do so press Airzone to start the search The controller will display the different wireless zone modules found with the signal level of each one of them Select the wanted module and press Check the selected module will begin to beep to be identified Verify the range is correct 30 minimum and confirm Zone address Select the zone associated to the...

Страница 22: ...10 is automatically assigned Associate each valve with its zone Other settings Access the advanced settings system address temperature range etc to change other settings or activate the basic function if you want to see Advanced Settings zone parameters Blueface ...

Страница 23: ...onalities of the LITE thermostat from the advanced configuration menu of a Blueface thermostat see section Advanced Settings Zone parameters If the association is correct the LED will flash green 5 times If it flashes red it means the zone is already occupied If it flashes red twice it means the thermostat is out of range Remember If you need to change the zone number reset the thermostat and star...

Страница 24: ...the systems connected to the CCP in a semi forced way Temperature range Use this parameter to select the highest temperature in heatingmode 19 30 ºC by default 30ºC Wireless valves Allows you to associate release a valve Allows you to open close the wireless channel of the AZX6CM1VALR module Allows you to reset the AZX6CM1VALR module Radio channel It activates deactivates the wireless association ...

Страница 25: ...resets the thermostat and returns it to factory values PRODUCTION PARAMETERS Operation logic It allows to configure the operation logic for the control relays of the AZX6CCPWSCC Aerothermal unit Default preset 2 pipes 4 pipes RadianT Recommended for RadianT365 systems Activation delay It allows to set a delay time in the power on of the production unit configurable in minutes from 0 to 7 Default p...

Страница 26: ...ed thermostat Main control board communication error This incident blocks the control of the zone Check this error is not common to all thermostats If so verify the proper operation of the main board To solve this incident check 1 Main control board status Correctly powered 2 Main control board status Airzone connection bus LEDs are operating properly 3 Connection Verify the polarity of the main c...

Страница 27: ...n 4 Restart the zone and re associate it with the system To do this press and hold on and restart the start up configuration process Note that if you need to associate wireless devices the wireless association module must be previously open from SW1 button or from any thermostat pressing Wireless module inside Advanced Settings zone settings 5 Restart system If the system is restarted this error m...

Страница 28: ...hange the zone number reset the thermostat and start association process Error 8 Wireless thermostat Lite not found The zone ceases to measure the room temperature of an associated wireless Lite thermostat therefore the zone cannot generate demand Check which Lite thermostat is not working properly To solve this incident check 1 Power supply Check the battery and replace it if necessary 2 Verify t...

Страница 29: ...control of the zone To solve this incident check 1 Status of the control module of the radiant elements Correctly powered Check the polarity of the connectors of the main control board and the module 2 Status of the control module of the radiant elements and the main control board Airzone connection bus LEDs are operating properly 3 Wiring Disconnect the terminal from the Airzone connection bus an...

Страница 30: ...lements Correctly powered 2 Status of the Main Control Board Airzone connection bus LEDs are operating properly 3 Connection Check the polarity of the connectors of the CCP and the Main Control Board of the system Error C 09 Aerothermal Gateway Production Control Board Communication Error The system loses communication with the Gateway and therefore with the aerothermal system The control of the s...

Страница 31: ...zone Check that Error 1 not appear in all thermostats If so verify the proper operation of the main board To solve this incident check 1 Main control board status Correctly powered 2 Main control board status Airzone connection bus LEDs are operating properly 3 Connection Verify the polarity of the main control board and thermostat connectors 4 Wiring Disconnect the terminal from the Airzone conne...

Страница 32: ...l the microswitchs reinsert the thermostat in its base and press on the thermostat The LED will flash green twice when the reset process is completed Note that if you need to associate wireless devices the wireless association module must be previously open from SW1 button or from any thermostat pressing Wireless module inside Advanced settings zone parameters 5 Restart system If the system is res...

Страница 33: ...34 NAVIGATION TREES NAVIGATION TREE BLUEFACE THERMOSTAT ...

Страница 34: ...35 NAVIGATION TREE THINK THERMOSTAT ...

Страница 35: ...02 400 446 http www myzone airzone es Parc Tertiaire Silic Inmeuble Panama 45 Rue Villeneuve 94573 Rungis France Téléphone 33 184 884 695 Fax 33 144 042 114 http www myzone airzonefrance fr Via Fabio Filzi 19 E 20032 Cormano Milano Italia Telefono 39 02 56814756 Fax 39 02 56816158 http www myzone airzoneitalia it ...