PROBLEM/SYMPTOM  

LIKELY 

CAUSE(S) 

 

CORRECTION 

Unit provides 

insufficient cooling. 

  1. Restriction in water 

system. 

 

2. Water pump. 

 

 

3. Air filter. 
4. Indoor coil. 

 

5. Ice on indoor coil. 

 

 

6. Unit is undersized 

 
 
7.Low refrigerant 

  1. Strainer or thru-hull fitting are clogged. Clean and 

check for water flow.  Make sure seacock (ball 

valve) is open. 

2. Check for electrical shorts, ground and open 

circuits.  Replace water pump if it is defective.  

Replace water pump if it is undersized. 

3. Clean or replace the air filter if it is dirty. 
4. The indoor coil may require cleaning if the unit 

was operated without a filter. 

5. Thermostat setting is too low.  Shut down unit until 

ice has melted and restart at a higher temperature 

setting. 

6. Check if the unit is undersized for the load. 

Replace with larger unit or add additional unit(s) if 
necessary. 

7.  Add refrigerant 

Noise operation. 

  1. Copper tubing is 

vibrating. 
 

2. Indoor blower assembly. 

 

 

3. Loose cabinet or 

components. 

4. Improper unit 

installation. 

  1. Adjust by bending slightly to a more stable 

position.  Separate any tubing that is making 
contact with other tubing or components. 

2. If blower wheel is hitting housing, adjust the wheel 

position in the housing.  Replace blower motor or 

assembly if the bearing(s) are defective. 

3. Check and tighten loose screws. 
 
4. Make sure unit is level and secure to deck. 

Water is leaking from 

unit. 

 1. 

Condensate 

pan. 

2. Condensate drain line 

or pump. 

 

3. Loose fittings or 

connections. 

  1. Check for leaks and repair as required. 

2. Check for leaks and repair as required. 

 

 
3. Tighten fittings and connections.  Check the 

condensate drain line for leaks. 

Electrical shock at unit.    1. Electrical component is 

shorted to ground. 

  1. Check control board, blower motor, compressor 

and pumps with an ohmmeter or high potential 

tester.  Determine what is grounded and replace 
or rewire. 

2. Line trip is too sensitive 

Содержание Marvair Marine SMB05ACP

Страница 1: ...Chapter 7 Wiring Diagram 10 Chapter 8 Spare Parts List 11 Chapter 8 Warranty 12 Manufactured By Marvair Division of AIRXCEL Inc P O Box 400 Cordele Georgia 31010 156 Seedling Drive Cordele Georgia 310...

Страница 2: ...point out helpful suggestions that will result in improved installation reliability or operation DANGER Self contained units or evaporators of split systems should never be installed in engine rooms...

Страница 3: ...URE FAULT shutdown Supply Air Grille s Some installations will have more than one supply air grille Standard main supply air grilles are generally made of aluminum or wood frames with two or four way...

Страница 4: ...me cases In such severe conditions seek the advice of your local factory service representative They will be most familiar with solutions to localized situations Marvair works closely with our servici...

Страница 5: ...air conditioner Electrical The SMB model is designed to operate of a nominal 12 volt DC power supply an inverter is not required The unit will operate on a DC voltage from 9 volts to 17 volts General...

Страница 6: ...dedicated breaker turn it on Verify that water is being discharged overboard Instructions for the Thermostat Cooling Cycle 1 Adjust the cooling temperature set point on the thermostat higher than the...

Страница 7: ...ct water line at ball valve 3 Insert line into a bucket of potable anti freeze 4 Run air conditioner until a solid stream of anti freeze is being discharged overboard 5 Reconnect water line at ball va...

Страница 8: ...ndoor coil The sensor and or thermostat should be replaced if defective 3 Check for water flow Check refrigerant charge Check switches for loose wire connection broken or burned contacts 4 Tug on wire...

Страница 9: ...tional unit s if necessary 7 Add refrigerant Noise operation 1 Copper tubing is vibrating 2 Indoor blower assembly 3 Loose cabinet or components 4 Improper unit installation 1 Adjust by bending slight...

Страница 10: ...SMB Air Conditioner 12 VDC Owner s Manual 9 09 Page 10 of 13 Chapter 7 Wiring Diagram...

Страница 11: ...pressor 10343 Control Module 01627 Evaporator Coil 60127 Blower Assembly 30067 Control Board 50196 Condenser water coil 60194 High Pressure Switch Manual Reset 400 psig 70339 Cap Tube Strainer Assembl...

Страница 12: ...heir designated Service Representative The responsibility of the Owner of the Equipment includes the following 1 To operate the equipment according to the manufacturer s instructions 2 To provide easy...

Страница 13: ...HIS WARRANTY AND SERVICE POLICY CONSTITUTE THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR REVERSE CYCLE AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING WITHOU...

Отзывы: