background image

SMB Air Conditioner 

 

12 VDC Owner’s Manual 9/09 

 

Page 4 of 13 

unchecked, equipment damage. Should the strainer become clogged or partially obstructed, adverse 
performance will be experienced. The first indication will be a reduction in the quantity of the discharge 
water. Eventually , the high pressure switch in the unit will activate and shut the unit down. (See 
Troubleshooting.) Turn the power off to the unit; check strainer and pump, restart. (See Pump and 
Troubleshooting.) 

To eliminate these potential problems, it is recommended that you check to make sure you have water 
flow each time you turn the system on and clean your strainer weekly. More often as conditions dictate. 
In some regions, it is common to experience a tremendous presence of jellyfish or sea nettles 
concentrated in back bay marinas for short periods of time. These can clog strainers and water pumps 
every hour to hour and a half in some cases. In such severe conditions, seek the advice of your local 
factory service representative. They will be most familiar with solutions to localized situations. Marvair 
works closely with our servicing dealers when custom solutions are required. During the warranty 
period, factory approval must be obtained for any modification to be done to alleviate the problem 
without voiding warranty coverage. 

Sea Water Pump 

Your seawater pump has been sized in accordance with specifications for system water flow and 
volume. A minimum of 1.5 GPM (5.69 LPM) measured at the inlet to the air conditioner of water flow 
is required for proper operation

.

 The pump is a self priming. 

Occasionally, sea grass, jellyfish and other items may pass through your strainer and get lodged in the 
pump impeller. Should cleaning your strainer fail to eliminate a water flow problem, you should next 
check the pump. First loosen the discharge line and gently remove it from the pump assembly. (Make 
sure the seacock is open.) Water should rise above the pump to a level equal to the waterline of your 
boat. If not, there is a blockage. 

 

Содержание Marvair Marine SMB05ACP

Страница 1: ...Chapter 7 Wiring Diagram 10 Chapter 8 Spare Parts List 11 Chapter 8 Warranty 12 Manufactured By Marvair Division of AIRXCEL Inc P O Box 400 Cordele Georgia 31010 156 Seedling Drive Cordele Georgia 310...

Страница 2: ...point out helpful suggestions that will result in improved installation reliability or operation DANGER Self contained units or evaporators of split systems should never be installed in engine rooms...

Страница 3: ...URE FAULT shutdown Supply Air Grille s Some installations will have more than one supply air grille Standard main supply air grilles are generally made of aluminum or wood frames with two or four way...

Страница 4: ...me cases In such severe conditions seek the advice of your local factory service representative They will be most familiar with solutions to localized situations Marvair works closely with our servici...

Страница 5: ...air conditioner Electrical The SMB model is designed to operate of a nominal 12 volt DC power supply an inverter is not required The unit will operate on a DC voltage from 9 volts to 17 volts General...

Страница 6: ...dedicated breaker turn it on Verify that water is being discharged overboard Instructions for the Thermostat Cooling Cycle 1 Adjust the cooling temperature set point on the thermostat higher than the...

Страница 7: ...ct water line at ball valve 3 Insert line into a bucket of potable anti freeze 4 Run air conditioner until a solid stream of anti freeze is being discharged overboard 5 Reconnect water line at ball va...

Страница 8: ...ndoor coil The sensor and or thermostat should be replaced if defective 3 Check for water flow Check refrigerant charge Check switches for loose wire connection broken or burned contacts 4 Tug on wire...

Страница 9: ...tional unit s if necessary 7 Add refrigerant Noise operation 1 Copper tubing is vibrating 2 Indoor blower assembly 3 Loose cabinet or components 4 Improper unit installation 1 Adjust by bending slight...

Страница 10: ...SMB Air Conditioner 12 VDC Owner s Manual 9 09 Page 10 of 13 Chapter 7 Wiring Diagram...

Страница 11: ...pressor 10343 Control Module 01627 Evaporator Coil 60127 Blower Assembly 30067 Control Board 50196 Condenser water coil 60194 High Pressure Switch Manual Reset 400 psig 70339 Cap Tube Strainer Assembl...

Страница 12: ...heir designated Service Representative The responsibility of the Owner of the Equipment includes the following 1 To operate the equipment according to the manufacturer s instructions 2 To provide easy...

Страница 13: ...HIS WARRANTY AND SERVICE POLICY CONSTITUTE THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR REVERSE CYCLE AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING WITHOU...

Отзывы: