LL357D4 PDS, 4.2011
6
Configuration Mode Settings (cont'd)
9. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed. Marvair recommends a max. heat
setpoint of 78ºF (25.6ºC)
Press the Up or Down button to select.
Press the Right button to advance to the next screen.
10. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed. Marvair recommends a minimum
cool setpoint of 68ºF (20ºC).
Press the Up or Down button to select.
Press the Right button to advance to the next screen.
11. Room Temperature Offset (+9°F to -9°F) (+4 .5°C to -4 .5°C)
Adjust to calibrate displayed room temperature to match actual room temperature. Note: When
not set to 0, º will display.
Press the Up or Down button to select.
Press the Right button to advance to the next screen.
12. Temperature Sensor (1-3)
1. Only on-board sensor determines room temperature.
2. Only remote sensor determines room temperature.
3. Average temperature of on-board and remote sensor.
Note: If there is no remote sensor, option 1 must be selected.
Press the Up or Down button to select.
Press the Right button to advance to the next screen.
13. Cooling Fan Delay Off Time (0, 30, 60, 90 seconds)
Select the fan purge time for cooling. Marvair recommends 0 seconds.
Press the Up or Down button to select.
Press the Right button to advance to the next screen.
14. Status Indicator Light (Led 0, 1, 2)
Marvair recommends 1.
0 = Status indicator never on
1 = Status indicator on with first stage
2 = Status indicator on with second stage
Press the Up or Down button to select.
Press the CONFIG button for 2 seconds to exit configuration.