Configuration Mode

To enter Configuration mode:
1.  Verify that the thermostat is in the OFF mode.
2.  Press the SYS (left) button until the off mode displays.
3.  Remove the thermostats cover by gently pulling on one corner at the top of the thermostat.
4.  Press the CONFIG button for 1 second.
5.  Press the up or down button to change the settings within each screen.
6.  Press the RIGHT button to advance to the next screen. Press the left button to return to previous

Screen 

Number

Description

Marvair Recommended 

Selection

Default

1

Temperature Scale °F or °C

As desired

F

2

1st Stage Temperature Differential 1°F to 3°F (0.5°C to 1.5°C)

2°F

3

2nd Stage Temperature Differential 1°F to 6°F (0.5°C to 3.0°C)

2°F

4

Staged Off Outputs 
1= outputs staged off independently
2= outputs staged off simultaneously

Select 11

1

5

Minimum Deadband
2°F to 9°F (1.0°C to 4.5°C)

3°F

6

System
Choose from heat pump, non-heat pump (air conditioner), reversing valve 
and number of compressors.

Select “non-heat pump” and 
“Electric”1

GAS

7

Auxiliary Delay On
Set the time delay (in minutes) for aux. heat to be locked out after a call for 
second stage

Set to 0 minutes.1

0:00

8

Lockout
Select the number of degrees that the set temperature can be changed 
during keypad lockout.

As desired

00

9

Maximum Heating Setpoint
55°F to 90°F (13°C to 232.0°C)

No higher than 78°F (25.6°C)

90°

10

Minimum Cooling Set point
45°F to 75°F (7.0°C to 24.0°C)

No lower than 68°F (20°C)

45°

11

Room Temperature Offset
+9°F to -9°F (+4.5°C to -4.5°C)

As desired

12

Temperature Sensor
1 = On board temperature sensor
2 = Only remote sensor
3 = Avg. temperature of on-board sensor and remote sensor

As desired

1

13

Cooling fan Delay Off Time
0, 30, 60, 90 seconds

0 seconds

0

14

Status indicator light 
0= status indicator never on
1= status indicator on with first stage
2= status indicator on with second stage

Select 1

1

To exit the Configuration Mode, press the CONFIG switch for 1 second.
Note: The red light indicates the unit(s) is in the heating cycle and the green light indicate that the unit(s) is in the cooling cycle.

1Settings and selections in italics are required settings/selections.

Содержание Marvair LL357D4

Страница 1: ...ng power outages no batteries required Programming not required Digital display shows temperature in F or C Room Temperature Offset Used to calibrate displayed room temperature with actual room temper...

Страница 2: ...box for control wiring to air conditioners Low Voltage Wiring 1 All wiring must comply with local codes and ordinances 2 Disconnect power to prevent electrical shock or equipment damage 3 On dual uni...

Страница 3: ...lectrical codes and ordinances Note Mount the thermostat about five feet above the floor Do not mount the thermostat on an outside wall in direct sunlight behind a door or in an area affected by a ven...

Страница 4: ...stem The LL357D4 functions with air conditioners with electric heat systems To configure the LL357D4 perform the following steps 1 Verify that the LL357D4 is in the OFF mode Press the SYS left button...

Страница 5: ...t up for Non Heat Pump and Type of Heat Electric Press the Up or Down button to select scale Press the Right button to advance to the next screen Press the Up or Down button to select Press the Right...

Страница 6: ...set to 0 will display Press the Up or Down button to select Press the Right button to advance to the next screen 12 Temperature Sensor 1 3 1 Only on board sensor determines room temperature 2 Only re...

Страница 7: ...n the lead lag control should be on One amber light will be on to identify the lead unit The other light should be off If the lag unit comes on with the lead unit the light for the lag unit will not c...

Страница 8: ...ode In this mode the thermostat controls the heating system When the heat is on the flame icon appears on the display Cool Mode In this mode the thermostat controls the cooling system When the the uni...

Страница 9: ...de steps 2 3 Status indicator light does not come on during call for Cooling or Heating Turn status indicator light function on See Config Mode Step 14 Room temperature is not correct Calibrate thermo...

Страница 10: ...of compressors Select non heat pump and Electric 1 GAS 7 Auxiliary Delay On Set the time delay in minutes for aux heat to be locked out after a call for second stage Set to 0 minutes 1 0 00 8 Lockout...

Страница 11: ...LL357D4 PDS 4 2011 11 Notes...

Страница 12: ...e at www marvair com for the latest product literature Detailed dimensional data is available upon request A complete warranty statement can be found in each product s Installation Operation Manual on...

Отзывы: