CAUTION
R-410A specified tools
Remarks
1 Gauge manifold
Range: HP
>
4.5MPa, LP
>
2MPa
2 Charge hose
Pressure: HP: 5.3MPa, LP: 3.5MPa
3 Electronic balance for charging R410A
Can not use the measurable charging tank
4 Torque spanner
5 Flare tool
6 Copper pipe gauge for adjusting projecting margin
7 Vacuum pump adapter
Must be with reverse stop valve
8 Leakage detector
Can not use freon leakage detector, but the He detector
• Execute earthing for the unit. But the earthing wire can not be connected to the gas pipe, water pipe, lightening
rod or the telephone earthing wire. Improper earthing will cause electric shock.
• Don't install the unit at the place where leaks the flammable gas. Or it will cause fire.
• Execute the water drainage pipe according to the manual, improper installation will cause water leakage to wet
the family things.
• The outdoor fan can not face to the flower or the other vegetable, or the blowing gas will make the flower dried
up.
•
Please ensure the maintenance room, if not, it will cause the maintenance person damaged.
•
When installing the unit on the roof or the other high place, to prevent the person falling down, please set the
fixed ladder and the railing at the passage.
• Use the two-end spanner, and fasten the nut at proper torque. Don't fasten the nut excessively against the flared
section broken. Or it will cause refrigerant leakage and lack of oxygen.
•
Take measures for heat insulation to the refrigerant pipe, or there will be water leakage or dew drop to wet the
family things.
• After finishing the refrigerant pipe, make leakage test by charging the nitrogen. In case the refrigerant leaks in a
small room and exceeds the limited concentration, it will cause lack of oxygen.
• Don't use the other refrigerant except for R410A. The R410A pressure is 1.6 times higher than R22 pressure. The
refrigerant R410A tank is marked with pink sign.
•
Against charging different refrigerant, we changed the stop valve diameter of the R410A unit. To enhance
the compression consistence, we also changed the flared pipe dimension. Prepare the R410A specially tools
according to the below table.
•
When charging refrigerant, the refrigerant must be taken out as liquid state from the tank.
•
For the liquid pipe and the gas pipe, take measures for heat insulation too. If there is no heat insulation, the dew
drop will wet the things.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
•
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety.
•
Children should be supervised to ensure that they do not play with the appliance.
•
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory
or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with
the appliance. Cleaning and user maintenance shall not be made by children without supervision.
• The appliances are not intended to be operated by means of an external timer or separate remote-control system.
•
Keep the appliance and its cord out of reach of children less than 8 years.
25
Содержание YEVFD Series
Страница 13: ...3 Dimension 11...
Страница 14: ...4 Function Parts layout 12...
Страница 15: ...5 Center of gravity 13...
Страница 16: ...6 Refrigerant Circuit 14...
Страница 24: ...10 Operation Range 22...
Страница 31: ...29...
Страница 32: ...Case 2 obstacles on the inlet and top side 30...
Страница 35: ...33...
Страница 48: ...13 PCB Photo PCB code 0151800421B LED7 LED2 LED8 LED9 BM1 LED10 LED4 LED3 LED6 LED5 SW1 SW2 SW3 46...