background image

Outdoor Unit 

Installation

Page 28

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 
an electrical wiring cover on the side of the unit. 
A comprehensive wiring diagram is printed on 
the inside of the wiring cover.

 WARNING

 

 

 

 

 

 

 

 

 

 

1. Prepare the cable for connection:

PAY

 ATTENTION TO LIVE WIRE

While crimping wires, make sure you clearly 
distinguish the Live (“L”) Wire from other wires.

 

7. Insulate unused wires with PVC electrical tape.

Arrange them so that they do not touch any
electrical or metal parts.

8. Replace the wire cover on the side of the unit,

and screw it in place.

2. Unscrew the electrical wiring cover and remove it.
3. Unscrew the cable clamp below the terminal

block and place it to the side.

4. Connect the wire according to the wiring

diagram, and firmly screw the u-lug of each
wire to its corresponding terminal.

5. After checking to make sure every connection is

secure, loop the wires around to prevent rain
water from flowing into the terminal.

6. Using the cable clamp, fasten the cable to the

unit. Screw the cable clamp down tightly.

1. Remove the wire cover from the unit by

loosening the 3 screws.

2. Dismount caps on the conduit panel.
3. Temperarily mount the conduit tubes(not
    included) on the conduit panel.
4. Properly connect both the power supply and

low voltage lines to the corresponding
terminals on the terminal block.

5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches

longer than the required length for wiring.

7. Use lock nuts to secure the conduit tubes.

BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE MAIN
POWER TO THE SYSTEM.

 WARNING

ALL WIRING WORK MUST BE PERFORMED 
STRICTLY IN ACCORDANCE WITH THE 
WIRING DIAGRAM LOCATED INSIDE OF 
WIRE COVER OF THE OUTDOOR UNIT .

 

 

 

 

 

 

 

 

 

 

 

 

 

In North America

Cover

Screw

G

Wire Cover 

Over 1

.57in.(4

0mm)

Terminal block

Conduit panel

Connecting cable 

Power supply cord 

Please select the appropriate through-hole according
to the diameter of the wire.

Three size hole: Small, Large, Medium

When the calbe is not fasten enough, use the
buckle to prop it up , so it can be clamped tightly. 

Buckle        

NOTE: 

If the cable clamp looks like the following,

please select the appropriate through-hole according 
to the diameter of the wire.

 

USE THE RIGHT CABLE

Please choose the right cable refer to
 “ 

Cable types

” in page 22.

a. Using wire strippers, strip the rubber

jacket from both ends of cable to reveal
about 40mm (1.57in) of the wires inside.

b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp u-lugs on the

ends of the wires.

CHOOSE THE RIGHT CABLE SIZE

The size of the power supply cable, signal cable, 
fuse, and switch needed is determined by the 
maximum current of the unit. The maximum 
current is indicated on the nameplate located 
on the side panel of the unit.  

NOTE:

 In North America, please choose the right 

cable size according to the Minimum Circuit 
Ampacity indicated on the nameplate of the unit. 

Содержание YDAA-025H-09M25

Страница 1: ...sure to save this manual for future reference 21 AW HDLA 09 24 R32 UM IM EN FR DE IT SP POR 07 21 English French German Italiano Português Español Split Type Room Air conditioner HDLA R32 Multilingual Manual HDLA 025N 09M25 YDAA 025H 09M25 HDLA 035N 09M25 YDAA 035H 09M25 HDLA 050N 09M25 YDAA 050H 09M25 HDLA 070N 09M25 YDAA 070H 09M25 ...

Страница 2: ...09M25 HDLA 035N 09M25 YDAA 035H 09M25 HDLA 050N 09M25 YDAA 050H 09M25 HDLA 070N 09M25 YDAA 070H 09M25 IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference 21 AW HDLA 09 24 R32 UM IM EN FR DE IT SP POR 07 21 ...

Страница 3: ... Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10 5 Manual operation without Remote 10 ...

Страница 4: ...8 Mount indoor unit 24 Outdoor Unit Installation 25 1 Select installation location 25 2 Install drain joint 26 3 Anchor outdoor unit 26 4 Connect signal and power cables 28 Refrigerant Piping Connection 30 A Note on Pipe Length 30 B Connection Instructions Refrigerant Piping 30 1 Cut pipe 30 2 Remove burrs 31 3 Flare pipe ends 31 4 Connect pipes 31 Air Evacuation 33 1 Evacuation Instructions 33 2 ...

Страница 5: ...ng smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit This may cause fire or combustion Do not oper...

Страница 6: ...ord to power the unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which has at least 3mm clearances in all poles and have a leakage current that may exceed 10mA the residual current device RCD having a rated residual operating current not exceed...

Страница 7: ... install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit i...

Страница 8: ...ical equipment should not be mixed with general household waste 2 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specifiec for operation For R32 frigerant models Appliance shall be installed operated and stored in a room with a floor area larger than 4m Appliance shall not be installed in an ...

Страница 9: ... Display window A Display window D Display window B fresh defrost run timer Display window C for 3 seconds when FRESH SWING TURBO or SILENCE feature is turned on when Fresh feature is activated some units for 3 seconds when TIMER OFF is set FRESH SWING TURBO or SILENCE feature is turned off when defrosting cooling heating units when anti cold air feature is turned on when unit is self cleaning som...

Страница 10: ... low temp cooling systems To further optimize the performance of your unit do the following Keep doors and windows closed Limit energy usage by using TIMER ON and TIMER OFF functions Do not block air inlets or outlets Regularly inspect and clean air filters FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER Inverter Split Type When outside temperature is below 0 C 32 F we strongly recommend keeping ...

Страница 11: ... settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep When in COOL mode the unit will increase the temperature by 1 C 2 F after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by...

Страница 12: ...e of air flow To operate your unit manually 1 Open the front panel of the indoor unit 2 Locate the MANUAL CONTROL button on the right hand side of the unit 3 Press the MANUAL CONTROL button one time to activate FORCED AUTO mode 4 Press the MANUAL CONTROL button again to activate FORCED COOLING mode 5 Press the MANUAL CONTROL button a third time to turn the unit off 6 Close the front panel CAUTION ...

Страница 13: ...ed cloths to clean the unit Do not use benzene paint thinner polishing powder or other solvents to clean the unit They can cause the plastic surface to crack or deform Do not use water hotter than 40 C 104 F to clean the front panel This can cause the panel to deform or become discolored Cleaning Your Air Filter CAUTION Do not touch air freshening Plasma filter for at least 10 minutes after turnin...

Страница 14: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the power Remove batteries from remote control Maintenance Pre Season Inspection After long periods of non use or before periods of frequent use do the following Check for damaged wires Clean all filter...

Страница 15: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is norm...

Страница 16: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solution Poor Cooling Performance Temperature setting may be higher than ambient room temperature Lower the temperature setting The hea...

Страница 17: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re seal if necessary and top off refrigerant Indicator lamps continue flashing The unit may stop operation or continue to run safely If th...

Страница 18: ...ape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote controller holder optional Remote controller holder optional Drain joint for cooling heating models Seal for cooling heating models Mounting plate Manual Parts you must purchase separately Consult the dea...

Страница 19: ...ng Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North America Connect Piping Prepare Drain Hose Connect Wiring not applicable for some locations in North America 4 5 6 7 8 9 ...

Страница 20: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller Drainage Pipe Louver Remote controller Holder Some Units Functional Filter On Back of Main Filter Some Units Front Panel Outdoor Unit Power Cable Some Units 1 2 3 4 5 6 7 8 9 10 11 1 2 1 2 3 4 6 7 8 ...

Страница 21: ...on subject to direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective piping step for the signal cable and refrigerant piping that connect the indoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the un...

Страница 22: ...illing the wall hole make sure to avoid wires plumbing and other sensitive components Φ16mm 5 8in or more the wall hole should be 90mm 3 54in NOTE When the gas side connective pipe is Type A Type B Left rear wall hole 65mm 2 5in Right rear wall hole 65mm 2 5in Indoor unit outline 39mm 1 5in 39mm 1 5in 285mm 11 2in 47mm 1 85in 47mm 1 85in HDLA 025N 09M25 HDLA 035N 09M25 Model A 148mm 5 8in 230mm 9 ...

Страница 23: ... extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By default the drain hose is attached to the left hand side of unit when you re facing the back of the unit However it can also be attached to the right hand side To ensure proper drainage attach the drain hose on the same si...

Страница 24: ... the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 10 minutes or more before you touch the electrical components 1...

Страница 25: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lead to fire or water damage DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES While bundling these items together do not intertwine or cross the signal cable with any other wiring 2 Using adhesive vinyl ...

Страница 26: ...t pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate 7 Again check that the unit is firmly mounted by applying slight pressure to the left and the right hand sides of the unit If refrigerant piping is alre...

Страница 27: ... wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build a shelter above the unit to protect it from the rain or snow Be careful not to obstruct air flow around the unit If the unit is frequently exposed to salty air seaside Use outdoor unit that ...

Страница 28: ...rubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode Seal Drain joint A B Base pan hole of outdoor unit Seal IN COLD CLIMATES In cold climates make sure that the drain hose is as vertical as pos...

Страница 29: ...bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO CONCRETE EYE PROTECTION IS RECOMMENDED AT ALL TIMES CAUTION Make sure that the wall is made of solid brick concrete or of similarly strong material The wall must be able to support at least four times the weight of the unit Outdoor ...

Страница 30: ...und the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK TURN OFF THE MAIN POWER TO THE SYSTEM WARNING ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOO...

Страница 31: ...ances or gases other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cause explosion and injury 2 Using a pipe cutter cut the pipe a little longer than the measured distance 3 Make sure that the pipe is cut at a perfect 90 angle Oblique Rough Warped 90 D...

Страница 32: ...alling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve an airtight seal 1 After removing burrs from cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends ...

Страница 33: ... 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm Ø 9 52 Ø 0 375 Ø 12 7 Ø 0 5 Ø 16 Ø 0 63 Ø 19 Ø 0 75 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Us...

Страница 34: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for leaks If there is no change in system pressur...

Страница 35: ...on the outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula CAUTION DO NOT mix refrigerant types ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Liquid Side Ø 6 35 ø 0 25 R32 Pipe length standard length x...

Страница 36: ...d Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using leak detector refer to the device s operation manual for proper usage instructions AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection points DO NOT leak replace th...

Страница 37: ...the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connection points do not have leaks Refer to Gas Leak Check section for instructions 5 After the Test Run is successfully completed and you confirm that all checks points in List of Checks to Perform...

Отзывы: