DC VOLTAGE IN THERMISTORS
Temp
Volts
All other
DUO De-icer
Volts
Temp
Volts
All other
DUO De-icer
Volts
-20 4.554
24 2.555
4.6
-19 4.529
25 2.500
4.5
-18 4.502
26 2.445
-17 4.475
27 2.391
-16 4.446
28 2.338
-15 4.417
29 2.284
-14 4.386
30 2.232 4.02
-13 4.354
31 2.180
-12 4.322
32 2.128
-11 4.287
33 2.077
-10 4.252
7.65
34 2.027
-9 4.216
7.59
35 1.978 3.56
-8 4.178
7.52
36 1.929
-7 4.140
7.45
37 1.881
-6 4.100
7.38
38 1.834
-5 4.059
7.31
39 1.798
-4 4.017
7.23
40 1.742 3.14
-3 3.974
7.15
41 1.698
-2 3.930
7.07
42 1.654
-1 3.885
6.99
43 1.611
0 3.839 6.91
44 1.569
1 3.792 6.83
45 1.527 2.75
2 3.744 6.74
46 1.487
3 3.695 6.65
47 1.447
4 3.646 6.56
48 1.409
5 3.595 6.47
49 1.371
6 3.544 6.38
50 1.334 2.4
7 3.492 6.29
51 1.298
8 3.443 6.19
52 1.263
9 3.388 6.09
53 1.228
10 3.333
6.00
54 1.195
11 3.278
5.9
55 1.162 2.09
12 3.223
5.8
56 1.130
13 3.168
5.7
57 1.009
14 3.113
5.6
58 1.069
15 3.257
5.5
59 1.040
16 3.002
5.4
60 1.011
17 2.946
5.3
61 0.983
18 2.890
5.4
62 0.956
19 2.833
5.1
63 0.929
20 2.777
5
64 0.904
21 2.722
4.9
65 0.879
22 2.666
4.8
66 0.854
23 2.610
4.7
67 0.831
All Three Thermistors on the unit have the same resistance values and therefore the same voltage readings, except
for the “Duo de-icer volts,” the voltage reading on the outdoor coil on the duo units fitted with a double de-icer or
typhoon PCB.
Page 19
Содержание XLM12RCA
Страница 1: ...Service Installation Manual XLM9RCA XLM12RCA XLM14RCA AIR CONDITIONING 20 06 03...
Страница 11: ...RC3 SILVER REMOTE CONTROL LOCK Button Page 9...
Страница 13: ...RC3 Silver MODES OF OPERATION FUNCTIONS AND FEATURES Continued Page 11...
Страница 14: ...CONTROL LIGHTS AND FUNCTIONS Page 12...
Страница 23: ...Page 21 Notes...