THERMISTOR RESISTANCE VS. TEMPERATURE 

 

Temp - c 

Rthern 

(

Rmin. 

(

Rmax. 

(

Temp - c 

Rthern 

(

Rmin. 

(

Rmax. 

(

-20 102062 

98850 

105061 26  9573 9359 9776 

-19  96064 93066 98866  27  9166  8963  9359 
-18  90462 87661 93080  28  8779  8586  8963 
-17  85226 82608 87674  29  8412  8228  8587 
-16  80331 77883 82621  30  8061  7886  8228 
-15  75751 73462 77894  31  7728  7561  7887 
-14  71465 69322 73472  32  7410  7251  7561 
-13  67452 65445 69332  33  7107  6956  7252 
-12  63692 91812 65454  34  6819  6675  6956 
-11  60168 58406 61821  35  6544  6407  6675 
-10  56864 55212 58414  36  6282  6151  6407 

-9  53764 52214 55219  37  6032  5907  6151 
-8  50855 49400 52221  38  5793  5674  5907 
-7  48123 46757 49406  39  5565  5451  5674 
-6  45557 44274 46763  40  5348  5239  5452 
-5  43145 41939 44279  41  5140  5036  5239 
-4  40878 39744 41944  42  4942  4843  5037 
-3  38745 37679 39748  43  4752  4658  4843 
-2  36738 35764 37683  44  4571  4481  4658 
-1  34848 33904 35738  45  4398  4312  4481 

33069 32179 33907  46  4233  4150  4312 

31392 30554 32183  47  4074  3995  4150 

29812 29022 30557  48  3923  3847  3995 

28322 27577 29025  49  3778  3705  3847 

26916 26213 27579  50  3639  3570  3705 

25590 24926 26216  51  3506  3440  3570 

24337 23711 24929  52  3379  3315  3440 

23154 22563 23713  53  5257  3196  3315 

22037 21478 22565  54  3140  3082  3196 

20981 20453 21480  55  3028  2972  3082 

10  19982 19483 20454  56  2921  2867  2973 
11  19037 18565 19484  57  2818  2767  2868 
12  18144 17697 18567  58  2720  2670  2767 
13  17298 16875 17698  59  2625  2578  2670 
14  16497 16096 16876  60  2534  2489  2578 
15  15738 15359 16097  61  2447  2404  2489 
16  15019 14659 15360  62  2363  2322  2404 
17  14337 13997 14661  63  2283  2243  2322 
18  13691 13368 19998  64  2206  2167  2243 
19  13078 12772 13369  65  2132  2095  2167 
20  12497 12206 12773  66  2061  2025  2095 
21  11945 11669 12207  67  1992  1958  2025 
22  11420 11158 11669  68  1926  1894  1958 
23  10923 10674 11159  69  1863  1832  1894 
24  10450 10213 10674  70  1802  1772  1832 
25  10000 9775 10214   

 

 

 

 

 

 

 

 

 

 

 

 

All Three Thermistors on the unit have the same resistance values. 

 

Page 18

Содержание XLM12RCA

Страница 1: ...Service Installation Manual XLM9RCA XLM12RCA XLM14RCA AIR CONDITIONING 20 06 03...

Страница 2: ...nance 8 6 Operation Remote Control 9 Dip Switch settings Resetting the Remote 11 7 Onboard LED display Onboard switches 12 8 Control Logic Description 14 Software and Hardware operation Points 14 PCB...

Страница 3: ...twork system including entering and leaving weatherproof louvres if fitted must be negligible pressure loss 3 8 In addition to the service clearances noted on the dimension sheet it is essential that...

Страница 4: ...unit avoiding hot surfaces such as hot water pipes boiler flues etc 8 2 The refrigerant piping should be as short and straight as possible to obtain the most efficient performance 8 3 All vertical ga...

Страница 5: ...chboard using HRC fuses or circuit breakers Low Voltage wiring including sensor wire must be wired using shielded cable and must not be run in conduits with power wiring 240 415 volt as any induced vo...

Страница 6: ...diagram Procedure 1 Select minimum acceptable wire size to handle starting current Graph 1 2 Check that wire size from step 1 is adequate for full load current increase size as necessary Graph 2 3 Che...

Страница 7: ...Active 240 v A 240 v A 240 v A 240 v N 5 volt 5 volt Outdoor coil defrost sensor 240 Volt supply Power Supply to Indoor Unit E Earth 4 Cores Earth two core sensor wires indoor to outdoor Keep Low Vol...

Страница 8: ...ive RV Active Fan Active Power Supply to Outdoor Unit N L E 240 Volt supply 1 E 3 4 5 6 1 E 3 4 5 6 8 9 8 9 Earth Active 1 E 3 4 5 6 No need to wire the outdoor sensor wires Remove 3 Pin Power plugs f...

Страница 9: ...is pumping it is operating correctly If it is noisy and not pumping it is running the wrong direction and will fail within minutes Reverse two of the phases to correct the running direction of the com...

Страница 10: ...ves or papers over a period of time The surface should be inspected periodically and cleaned down by hosing or steam cleaning as required 5 ELECTRICAL The contact surfaces of relays and contactors sho...

Страница 11: ...RC3 SILVER REMOTE CONTROL LOCK Button Page 9...

Страница 12: ...F OPERATION FUNCTIONS AND FEATURES Automatically selects heating or cooling mode according to the requirement then controls the temperature in that mode It does not change from cooling to heating or v...

Страница 13: ...RC3 Silver MODES OF OPERATION FUNCTIONS AND FEATURES Continued Page 11...

Страница 14: ...CONTROL LIGHTS AND FUNCTIONS Page 12...

Страница 15: ...r all other units 2 RIGHT DIP SWITCH When looking at the back UP Cooling only units DOWN Heat pump operation RESETTING REMOTE CONTROL The remote control must be reset after changing DIP switches repla...

Страница 16: ...p button for 3 secs 5 beeps will sound and the unit will run in cooling with high speed indoor fan for 30 minutes 8 AUTO Mode The Auto mode on these units selects either heating or cooling mode accord...

Страница 17: ...ins 5 Fan Speed Change Delay There is a 3 min delay when increasing the indoor fan speed but no delay on decreasing fan speed to avoid the fan speeds changing frequently 6 Relay Delay If all function...

Страница 18: ...off Filter LED on Filter LED off Louver motor A and B run to MAX angle IFAN in Mid speed Comp on Comp off OFAN on OFAN off RV on RV off Electrostatic Filter on Electrostatic Filter off Fresh Air on F...

Страница 19: ...5 mins and compressor run time in total is 45 mins and compressor runs for 20mins a defrost will be initiated Note 1 If OCT is in default value OCT Fault ignore ICT and compressor run time in total is...

Страница 20: ...0 33069 32179 33907 46 4233 4150 4312 1 31392 30554 32183 47 4074 3995 4150 2 29812 29022 30557 48 3923 3847 3995 3 28322 27577 29025 49 3778 3705 3847 4 26916 26213 27579 50 3639 3570 3705 5 25590 24...

Страница 21: ...6 83 45 1 527 2 75 2 3 744 6 74 46 1 487 3 3 695 6 65 47 1 447 4 3 646 6 56 48 1 409 5 3 595 6 47 49 1 371 6 3 544 6 38 50 1 334 2 4 7 3 492 6 29 51 1 298 8 3 443 6 19 52 1 263 9 3 388 6 09 53 1 228 1...

Страница 22: ...charged or under normal cooling operation on a very high ambient day 40o C Cooling Outdoor Coil Temp Heating Indoor Coil Temp Process of Operation High outdoor coil temperature protection mode and ind...

Страница 23: ...Page 21 Notes...

Страница 24: ...02 9793 3644 Fax 02 9793 3688 Bankstown Airport 2200 NSW Newcastle Suite 3 19 Darby St Tel 02 4940 4652 Fax 02 4940 4653 Newcastle 2300 NSW QUEENSLAND Unit 9 123 Muriel Ave Tel 07 3392 8113 Fax 07 339...

Отзывы: