PIPES TO BE MADE ON SITE

REFRIGERANT LINES

 

²

Supplied precharged in factory:

 

 

MAXIMUM LENGTH 25M.

 

²

Realized on the site by the installer:

 

 

MAXIMUM LENGTH 45M.

REFRIGERANT

linking pipes up to 45m:

 

²

GAS line:   
gas precharge

 

²

LIqUID line (above to 2m):   
 

4650

   110g/m  

6450

   183g/m

For refrigerant lines with a length between 25 and 45m (to be mounted on the site) the diameters, the refrigerant 
charge and the installation safety measures must be determined professionally.

minimum slope 

1cm/m downwards

Condenseur higher than the 

indoor unit

Condenseur at the same level as the 

indoor unit

Condenseur lower than the 

indoor unit

L

L

H

L

H

L. max = 45m

H. max = 20m

(L+H) max = 45m

H. max = 9m

(L+H) max = 45m

REFRIGERANT CONNECTIONS (AIR COOLED UNIT)

The outdoor unit are factory charged and equipped with refrigerant connections. Follow 
the connection instructions for the valves with non-removable membranes.

The couplings are situated behind the lower front panel of the unit, 
to the rear.

 

²

valve A: GAS line   
 

4650

   Ø 5/8"  

6450

   Ø 3/4

 

²

valve B: LIqUID line  
 

4650

   Ø 1/2"  

6450

   Ø 5/8"

valve LIqUID line

Cable passage

valve GAS line

BACK SIGHT

Discharge

Liquid

"Discharge" line

"Liquid" line

Discharge

Liquid

OUTDOOR UNIT

INDOOR UNIT

12

Содержание UC 104

Страница 1: ...iento IOM X 03 N 3 Part number Code Teil Nummer Codice C digo 3990529 Supersedes Annule et remplace Annulliert und ersetzt Annulla e sostituisce Anula y sustituye IOM X 03 N 2 Packaged Air Conditioner...

Страница 2: ......

Страница 3: ...INSTALLATION INSTRUCTION NOTICE D INSTALLATION INSTALLATIONSHANDBUCH ISTRUZIONI INSTALLAZIONE instRUCCIONES DE INSTALACI N...

Страница 4: ...scharge and intake 10 Access to the filters 10 installation of the outdoor unit 11 Clearances 11 Installation 11 attachment to the ground 11 refrigerant connections AIR COOLED UNIT 12 Refrigerant line...

Страница 5: ...ecific conditions of the location and the current required for any other appliance connected to the same circuit The unit must be EARTHED to avoid any risks caused by insulation defects It is forbidde...

Страница 6: ...elow the occupational limits or equal to them Occupational exposure limits R407C Recommended limits 1 000 ppm v v 8 hours TWA Stability R407C Not specified Conditions to avoid Use in the presence of e...

Страница 7: ...essively high temperatures above 60 C can harm certain plastic materials and cause permanent damage Moreover the performance of certain electrical or electronic components can be impaired WARRANTY The...

Страница 8: ...t 1 wiring diagram 1 diagram key 1 set of grommets UC 74 UC 104 1 outdoor unit UC 74 kg 93 104 kg 130 A B C D 4650 mm 1970 400 1715 790 6450 mm 1970 400 1980 790 X ARV X AO 4650 kg 525 565 6450 kg 600...

Страница 9: ...X ARV X AO X ARV X AO X ARV X ARV Cooling Ventilation VS FV Nominal power input kW 17 19 13 9 16 17 19 13 9 16 24 6 26 2 24 6 26 2 Maximum intensity A 76 85 67 76 45 50 39 44 109 117 64 69 Starting i...

Страница 10: ...e 50x60 2 Recycled water outlet nut F 26x34 1 3 Condensate water evacuation souple tube 26x32 4 Electric connection with Faults report 5 Electric connection with Remote control 6 General electric supp...

Страница 11: ...damage to property in the event of the unit being incorrectly supported The unit must be installed on a firm level foundation of adequate strength to support its full operating weight 1 It must be hig...

Страница 12: ...ke through the removable front panel A and the filter D factory mounted 2 Total rear air intake with duct Duct E to be mounted on the rear of the unit connection elements remove the panel J 3 Direct a...

Страница 13: ...charge Installation Install and attach the AIR COOLED condenser on a masonry surface concrete slab X Access panel electrical section 4 oblong holes 9x16 mm 229 229 11 900 1085 11 104 104 4 oblong hole...

Страница 14: ...ds Condenseur higher than the indoor unit Condenseur at the same level as the indoor unit Condenseur lower than the indoor unit L L H L H L max 45m H max 20m L H max 45m H max 9m L H max 45m refrigera...

Страница 15: ...ings Remove the protective plugs on each coupling Check if the valves are greased on the inside if not lubricate them slightly with oil fit refrigeration use Give a few clockwise turns by hand to make...

Страница 16: ...he power terminals situated on the left in the electric box behind the plastic protection cover caution In the case of a casing heater it must be started according to the compressor is located 2 hours...

Страница 17: ...TE Motors 74 and 104 are coupled of single phase 400 230 V coupling They are supplied ex factory coupled for 400 V between two phases To are to be coupled on site at the power supply voltage of the ca...

Страница 18: ...stages F1 F2 2 HEATING stages C1 C2 3 1 Automatic basic thermostat 2 Equipment with automatic cooling heating thermostat four stages and electrical heater accessories to order 3 The entire electrical...

Страница 19: ...TEGORIA I UC 74 UC 104 SOTTOMODULO A1 CATEGORIA II X 4650 ARV X 4650 AO X 6450 ARV CON SUPERVISION POR EL TUV RHEINLAND 62 bis avenue Henri Ginoux 92120 Montrouge France i prodotti sono forniti con la...

Страница 20: ...rherige Ank ndigung ge ndert werden Fotos nicht vertraglich bindend A causa della politica di continua miglioria posta in atto dal costruttore questi prodotti sono soggetti a modifiche senza alcun obb...

Отзывы: