41
Operation
(3) Rated operation including USA rated operation and
European rated operation can be inquired/adjusted through
function code 07 in the advanced setting. “00” means the
European rated operation, and “01” means the USA rated
operation.
(4) If the content of 07 is “00”, then press the Up/Down key to
switch to 08(Europe rated operation) directly, “09” will not in
the function code cycle, use the Up/Down key to adjust and
press the SET key to confirm .
(5) If the content of 07 is “01”, press the Up/Down key to
switch to 09(USA rated operation) directly. “08” will not in the
function code cycle. use the Up/Down key to adjust, and press
the SET key to confirm.
(6) When in the Europe rated operation situation, only rated
cooling condition(00-05) can be set in cooling mode; only rated
heating condition(00-04,06,07) can be set in heating mode. In
other modes, rated condition can’t be set.
(7) When in the USA rated operation situation, only rated
cooling condition(00-05)can be set in cooling mode; only rated
heating condition(00,06-11) can be set in heating mode. In
other modes, rated condition can’t be set.
(8) If the wired controller sets the rated operation function,
only wired controller can cancel it. If the remote controller sets
the rated operation function, the wired controller and remote
controller can both cancel it.