General Characteristics

Introduction

This new range of PAC HT air/water high temperature heat pumps offers the 
special feature of producing hot water at 65 °C at outdoor temperatures down 
to -20 °C, while guaranteeing a high COP.

For outdoor temperatures above +7° C, the PAC HT supplies water at 55 °C 
with a single compressor.

Consequently, this PAC HT unit is ideally suited to replace a traditional hot 
water boiler in producing Domestic Hot Water (DHW).

The patented technology

 uses two-stage compressors that provide : 

 

Higher COP :

  In  fact,  in  a  two-stage  system,  each  compressor  operates  at  a  low 

compression  ratio,  i.e.  3:1  compared  with  12:1  for  single-stage 
compressor systems.

  This  improves  the  compressors'  service  life  and  reduces  electricity 

consumption.

 

Same heating capacity maintained even with low outdoor temperatures :

  As compressor efficiency is maintained, PAC HT performance is hardly 

affected, even at low outdoor temperatures. 

 

Remarkable  adaptability  in  terms  of  matching  supplied  capacity 
to  heating  requirements  thanks  to  the  possibility  of  using  each 
compressor stage separately :

  The  PAC  HT  controller  chooses  the  optimum  compressor  staging 

configuration according to the demand for heating and the heat emitters' 
operating temperatures.

 

Optimised Domestic Hot Water production :

  Both  for  producing  DHW  and  Heating,  the  controller  determines  the 

compressor  staging  best  suited  to  the  DHW  tank  coil's  heat  exchange 
capacity, while taking account of the outdoor temperature. At the end of 
the heating phase, the DHW temperature is very close to the condensing 
temperature without an unnecessary energy consumption. 

Scope of application

The PAC HT is mainly designed as a replacement for the boiler without altering 
the rest of the installation. 

Bodywork and structure

Steel bodywork coated with oven-baked epoxy paint coating.

The unit base is equipped with large openings under the coil for condensate 
or de-icing water drainage.

Removable panels on all sides allow access to the electrical box and to the 
refrigeration and hydraulic circuits. Closed bodywork protection index : IP 24.

Compressors

Maintenance-free Scroll type compressors produce a high efficiency with low 
sound levels.

The  two-stage  circuit  equipped  with  2  compressors  with  an  unrivalled 
capacity ensures the best possible matching of supplied capacity to heating 
requirements.

Anti-vibration  pads  under  the  compressor  prevent  the  transmission  of  any 
vibrations to the bodywork.

Water side exchangers

Brazed plate construction operating on a counter flow configuration in Winter 
mode to ensure excellent heating performance.

Air exchanger

Treated with a hydrophilic coating to assist condensed water drainage.

The exchanger is sized to avoid clogging, maintain its performance in sub-
zero temperatures and cut the time and frequency of de-icing operations.

Fans

Reinforced polypropylene, low-speed helicoidal fans with optimised fan blade 
profiles to ensure efficient air flow at an extremely low sound level.

Fully-enclosed motor, maintenance-free bearings, automatic reset overheating 
protection device. The fan blades are shielded by plastic grilles for personal 
protection in accordance with health & safety standards.

Refrigerating circuit

The  patented  refrigerating

  circuit  enables  each  compressor  to  be  used 

independently or in two-stage mode.

The circuit, factory-filled and tested, includes a filter-dryer, two thermostatic 
expansion valves, high and low pressure safety devices and all the equipment 
specific to two-stage technology.

Electrical box

The  electrical  box  contains  all  the  components  for  PAC  HT  operation  and 
notably  the  system's  protection  devices  :  compressor  protection  circuit 
breaker or fuse, protection fuse, standard start-up current limiter for single-
phase units, phase sequence controller for three-phase units.

The  microprocessor  based  controller  integrated  in  the  box  controls  all  the 
PAC HT's functions with the help of a room terminal and temperature sensors.

Safety functions controlled by the controller :

  High  and  low  pressure  safety,  lack  of  water  flow,  lack  of  refrigerant 

charge, low evaporation pressure, high and low outlet water temperature 
limits, winter frost protection, compressor short cycling protection.

  Diagnosis of failures with history of 150 latest alarms (code, description, 

occurrence time and sensor values at the time of alarm). 

Other functions managed by the controller :

 

  Water  temperature  control  (inlet  and  outlet)  depending  on  outdoor 

temperature and ambient temperature (water law).

  Choice of compressors for optimised efficiency.

  De-icing the outdoor exchanger in winter.

  DHW production management.

  2-stage extra electric heating management. 

  Management  of  boiler  relief  without  additional  kit  (not  compatible  with 

extra electric heating).

Содержание PAC HT 12-6

Страница 1: ...Engineering Data Manual PAC HT High Temperature Air to Water Heat Pumps Models 12 6 14 7 18 9 AN AIRWELL GROUP COMPANY 12 0 to 17 9 kW...

Страница 2: ...system installation radiators PAC HT PAC HT Domestic hot water DHW tank Domestic hot water DHW tank Radiator system ambience thermostat Radiator system room thermostat Low temperature zone room thermo...

Страница 3: ...ures the best possible matching of supplied capacity to heating requirements Anti vibration pads under the compressor prevent the transmission of any vibrations to the bodywork Water side exchangers B...

Страница 4: ...r new installations or boiler replacement only Filter sludge trap Buffer Mixing tank 140 litres The water law parameters are programmed in the controller at the factory It is possible to adapt them mo...

Страница 5: ...ing cooled gas to cool the HP compressor suction side When the LP or the HP compressor operates on its own its cycle is identical to that of a traditional single compressor cycle Compressor operation...

Страница 6: ...radiator thermostatic valves The buffer tank 2 provides extra circulating water volume to maintain the minimum volume 1 Stop valve 12 Expansion tank 2 Buffer tank optional 13 In line heater 3 Filter...

Страница 7: ...n the minimum volume when the maximum number of thermostatic valves are closed The flow adjustment valve 11 is used to balance the flow in heating mode and domestic hot water mode to always ensure opt...

Страница 8: ...nt of 50 of the mixing tank s volume Example For a useful volume of 100 litres the actual mixing tank volume will be 200 litres The flow adjustment valve 11 is used to balance the flow in heating mode...

Страница 9: ...Depth mm 401 401 401 Height mm 1309 1309 1309 Weight kg 195 201 208 PAC HT MODELS 12 6 14 7 18 9 supply voltage 1 230 V Electrical supply cable mm2 3 x 6 3 x 6 General protection fuse rating A 32 32 s...

Страница 10: ...C WB Water condition 65 C Heating capacity dual compressor kW 10 0 12 0 14 8 Power input kW 5 1 6 0 7 3 COP with defrost 1 96 2 00 2 03 Outdoor air condition 7 C 8 C WB Water condition 65 C Heating c...

Страница 11: ...t 55 C T out 50 C T out 45 C T out 35 C 2 stage operating mode Small compressor operating mode T out 65 C T out 60 C T out 55 C T out 50 C 20 18 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 0 0 5 1...

Страница 12: ...ut 65 C T out 60 C T out 55 C T out 50 C T out 50 C T out 55 C T out 60 C T out 65 C 2 stage operating mode Small compressor operating mode 20 18 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 0 0 5...

Страница 13: ...T out 65 C T out 60 C T out 55 C T out 50 C T out 50 C T out 55 C T out 60 C T out 65 C 2 stage operating mode Small compressor operating mode 20 18 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 0 0...

Страница 14: ...1400 1500 1600 1700 1800 0 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 Domestic hot water tank optional Domestic hot water tank 3 way valve optio...

Страница 15: ...000 1100 1200 1300 1400 1500 1600 1700 20 30 40 50 60 70 Water flow l h Available pressure kPa Max flow Min flow Nominal flow HS 3 MS 2 LS 1 0 10 20 30 40 50 60 70 Water flow l h Available pressure kP...

Страница 16: ...700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 PAC HT 18 9 PAC HT All sizes 50 60 70 80 90 100 110 120 130 140 150 Water flow l h Power input W HS 3 MS 2 LS 1 700 800 900 1000 1100 1200 1300 140...

Страница 17: ...C B J A K 349 1150 400 50 1192 60 1236 60 A Electrical power supply B Inlet water 1 gas female C Outlet water 1 gas female E Display F Main switch G Water pressure gauge H High pressure tap I Low pre...

Страница 18: ...18 Minimum Clearances 800 500 400 500 100 800 Unit Domestic hot water tank optional 140 litre buffer tank optional Water inlet 150 150 200 Water inlet 200 500 200 200 700...