CONTROL SYSTEM
Service Manual-CN Fixed RPM series
12-11
12.5 HEATING MODE
12.5.1 Heating Mode – General
1. In heating Mode, temp. compensation schedule will be activated for wall mounted,
ducted models, and ceiling mounted (i.e. NKN, CN, and NFC) according to the following
table:
Add to SPT
SPT [
o
c]
I-FEEL ON
I-FEEL OFF
18
d
SPT
d
27
0
o
c
+2
o
c
27 < SPT
d
30
0
o
c
+3
o
c
Notes :
1) compensation will be activated in Forced operation modes
2. RV is OFF in RH group.
3. IF operating rules
(a)
As a general rule for
RC and SH groups
, when
COMP is ON
, excluding protection
modes, IFAN will be switched ON if
x
ICT > 35
o
c or
x
at the 30 second
(4)
after the COMP is switched ON. In this
case, the IFAN will be started at low speed
(5)
.
IFAN Speed
Any
Low
Stop
30
35
40
ICT [
o
c]
Notes :
.
1) In
SH or RC group
, if HE is set to OFF due to low ICT, IFAN will be switched
to LOW and will be turned OFF after 30 sec.
2) An exception to this rule is the Back-up mode for SH group. 3)
3) If the IFAN is turned ON by the 30 seconds operation, its minimum operation
time before stopping due to low ICT temperature is 60 sec.
Содержание ONG3-17 R410A
Страница 1: ...CN Fixed RPM Series REFRIGERANT R410A HEATPUMP REV 01 Oct 2008...
Страница 21: ...Pressure Curves Service Manual CN Fixed RPM series 6 2 6 1 2 Heating...
Страница 22: ...Pressure Curves Service Manual CN Fixed RPM series 6 3 6 2 Model CN12 GCN 12 R410A 6 2 1 Cooling...
Страница 23: ...Pressure Curves Service Manual CN Fixed RPM series 6 4 6 2 2 Heating...
Страница 24: ...Pressure Curves Service Manual CN Fixed RPM series 6 5 6 3 Model CN18 ONG3 17 R410A 6 3 1 Cooling...
Страница 25: ...Pressure Curves Service Manual CN Fixed RPM series 6 6 6 3 2 Heating...
Страница 27: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 2...
Страница 29: ...Sound Level Characteristices Service Manual CN Fixed RPM series 7 4...
Страница 31: ...Wiring Diagrams Service Manual CN Fixed RPM series 9 1 9 WIRING DIAGRAMS 9 1 Indoor Unit CN 9 12 18...
Страница 32: ...Wiring Diagrams Service Manual CN Fixed RPM series 9 2 9 2 Outdoor Unit GCN 9 R410A GCN 12 R410A ONG3 17 R410A...
Страница 33: ...Wiring Diagrams Service Manual CN Fixed RPM series 9 3 9 3 Connections between indoor unit and outdoor unit...
Страница 86: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 2 17...
Страница 87: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 3 14 2 EXPLODED VIEWS GCN 9 12...
Страница 88: ...EXPLODED VIEWS AND SPARE PARTS LISTS Service Manual CN Fixed RPM series 14 4 14 3 EXPLODED VIEWS ONG3 17...
Страница 94: ...APPENDIX A Service Manual CN Fixed RPM series 15 1 APPENDIX A INSTALLATION AND OPERATION MANUAL...
Страница 95: ...English Installation manual Indoor unit cassette type Part Number 468050324 01 AIR CONDITIONER CASSETTE...
Страница 119: ...PROTECTION 468100326...
Страница 121: ......
Страница 122: ...3...
Страница 124: ......
Страница 125: ......
Страница 127: ......