12b-11
CONTROL SYSTEM
Revision
0
12B.3.14 Deicing
Deicing starts, if OCT <= -6ºC and meets with one of the following conditions:
•
ICT < 39ºC, and IFAN is on for 20 minutes, and COMP is on for 5 minutes, and that
ICT decrease 1ºC per 6 minutes, occur 3 times;
•
ICT < 39ºC, and (sum of COMP on >= 3 Hours), and COMP is on for 20 minutes;
•
ICT – RT < 19ºC ( for F/S :ICT-RT<16ºC )keep for 5 minutes, and (sum of COMP
on) > 45 minutes ,And COMP is on for 20 minutes;
•
(4) ICT =< 35 ºC, and IFAN is on for 20 minutes, COMP is on for 5minutes,and sum
of COMP on > 45 minutes.
Note:
•
If OCT is invalid, and (ICT < 39ºC), and COMP keeps on for 30 minutes, and
ICT is decreasing 1ºC per 6 minutes occur 3 times;
•
If OCT and ICT are invalid; and if (sum of COMP on) >= 3 Hours;
•
If ICT is invalid, and (OCT <-6ºC) keeps for 4 min, (sum of COMP on) > 45min.
12B.3.14.1 Deicing
process
:
•
At the beginning of Deicing, COMP, IFAN, OFAN stop, RV stops after 55 seconds,
and then COMP will turn on after 5 seconds.
•
Deicing ends if (OCT >= 12ºC) or Deicing time is more than 9 minutes.
•
Once deicing ends, IFAN operates according to anti-cool fan mode;
•
Once deicing ends, COMP stops for 20 seconds, OFAN will turn on. After 35
seconds, RV will turn on, 5 seconds later COMP resumes its operation;
•
If AHEAT is operating when deicing conditions met, AHEAT will be turned off, and o
deicing starts 1 minute later.
•
After Deicing ends, if the conditions of AHEAT opening are met, AHEAT will turn on.
Note:
1. Deicing can’t end at the first 60 seconds once it was activated.
2. If OCT is invalid, Deicing ends after 5 minutes.
According to anti-cool wind
IFAN Any
Off
OFAN Any
Off
RV Any
Off
COMP Any
Off
AHEAT Any
Off
1min 55s 5s 9 min or OCT >= 12 ºC 55s 20s 5s
Содержание ONG 12
Страница 4: ......
Страница 19: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 FLO N 7 9 12 14 4 2 FLO N 18 24...
Страница 20: ...4 2 OUTLINE DIMENSIONS Revision 0 4 3 FLO N 30 4 4 ONG 7 9 12 14 RC 150m m...
Страница 21: ...4 3 OUTLINE DIMENSIONS Revision 0 4 5 GCN 7 9 12 14 RC 4 6 GC 18 24 RC AI R O U TLET AI R I N TAKE...
Страница 22: ...4 4 OUTLINE DIMENSIONS Revision 0 4 7 OU7 24 RC 4 8 GC 30 N RC...
Страница 23: ...4 5 OUTLINE DIMENSIONS Revision 0 4 9 OU8 30 RC...
Страница 60: ...8 2 WIRING DIAGRAMS Revision 0 8 2 Indoor Unit FLO 18 24 N LCD...
Страница 61: ...8 3 WIRING DIAGRAMS Revision 0 8 3 Indoor Unit FLO 30 N...
Страница 62: ...8 4 WIRING DIAGRAMS Revision 0 8 4 Outdoor Unit GC18 1PH R410A 8 5 Outdoor Unit GC 24 1PH R410A VT VT...
Страница 63: ...8 5 WIRING DIAGRAMS Revision 0 8 6 Outdoor Unit ONG7 1PH R410A...
Страница 64: ...8 6 WIRING DIAGRAMS Revision 0 8 7 Outdoor Unit OU7 24 OU8 30 1PH R410A...
Страница 65: ...8 7 WIRING DIAGRAMS Revision 0 8 8 Outdoor Unit OU7 24 OU8 30 3PH R410A 8 9 Outdoor Unit OU8 33 1PH R410A...
Страница 66: ...8 8 WIRING DIAGRAMS Revision 0 8 10 Outdoor Unit OU8 33 3PH R410A...
Страница 68: ...9 2 ELECTRICAL CONNECTIONS Revision 0 9 3 FLO 30 N 3PH...
Страница 69: ...10 1 REFRIGERATION DIAGRAMS Revision 0 10 REFRIGERATION DIAGRAMS 10 1 Heat Pump Models 10 1 1 FLO 7 N...
Страница 70: ...10 2 REFRIGERATION DIAGRAMS Revision 0 10 1 2 FLO 9 12 14 N R410A...
Страница 72: ...10 4 REFRIGERATION DIAGRAMS Revision 0 10 1 4 FLO 24 N R410A...
Страница 135: ...14 3 OPTIONAL ACCESSORIES Revision 0 14 3 RCW RCW2 Wiring Connections as Shown on Kit...
Страница 137: ...15 5 OPTIONAL ACCESSORIES Revision 0...
Страница 138: ...15 6 OPTIONAL ACCESSORIES Revision 0...
Страница 139: ...15 7 OPTIONAL ACCESSORIES Revision 0...
Страница 140: ...15 8 OPTIONAL ACCESSORIES Revision 0...
Страница 141: ......