12b-10
CONTROL SYSTEM
Revision
0
12B.3.12
High Pressure Protection
•
If ICT >= 61ºC, OFAN turn off. If ICT <= 55ºC, OFAN turn on.
•
If (ICT >= 66ºC) for duration of 10 seconds, COMP turn off. If ICT <= 52ºC, COMP turn on.
Note:
If ICT is invalid, High Pressure protection cannot be activated.
12B.3.13 Auxiliary Electric Heating
AHEAT will turn on, if all the following conditions are met:
•
COMP is on for 60 seconds;
•
RT <= 20ºC;
•
IFAN run at least at LOW speed;
•
RT <= SPT – 2ºC;
•
ICT <= 50ºC.
AHEAT will turn off, if one of the following conditions is filled:
•
RT > 21ºC;
•
COMP or IFAN stop;
•
RT >= SPT - 1ºC;
•
ICT >= 55ºC.
Note:
1. If ICT or RT is invalids, AHEAT will not be activated.
2. When the system turns off, if the AHEAT does not operate before, IFAN operates
according to the hot keep condition, otherwise, IFAN should turn off after 30 seconds’ at
supper low fan speed (Note: F/S type in low speed) to blow off the remaining heat.
ICT (ºC)
66
61
55
52
>= 10s >= 3 Min
COMP Any
Off
OFAN Any
Off
Содержание ONG 12
Страница 4: ......
Страница 19: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 FLO N 7 9 12 14 4 2 FLO N 18 24...
Страница 20: ...4 2 OUTLINE DIMENSIONS Revision 0 4 3 FLO N 30 4 4 ONG 7 9 12 14 RC 150m m...
Страница 21: ...4 3 OUTLINE DIMENSIONS Revision 0 4 5 GCN 7 9 12 14 RC 4 6 GC 18 24 RC AI R O U TLET AI R I N TAKE...
Страница 22: ...4 4 OUTLINE DIMENSIONS Revision 0 4 7 OU7 24 RC 4 8 GC 30 N RC...
Страница 23: ...4 5 OUTLINE DIMENSIONS Revision 0 4 9 OU8 30 RC...
Страница 60: ...8 2 WIRING DIAGRAMS Revision 0 8 2 Indoor Unit FLO 18 24 N LCD...
Страница 61: ...8 3 WIRING DIAGRAMS Revision 0 8 3 Indoor Unit FLO 30 N...
Страница 62: ...8 4 WIRING DIAGRAMS Revision 0 8 4 Outdoor Unit GC18 1PH R410A 8 5 Outdoor Unit GC 24 1PH R410A VT VT...
Страница 63: ...8 5 WIRING DIAGRAMS Revision 0 8 6 Outdoor Unit ONG7 1PH R410A...
Страница 64: ...8 6 WIRING DIAGRAMS Revision 0 8 7 Outdoor Unit OU7 24 OU8 30 1PH R410A...
Страница 65: ...8 7 WIRING DIAGRAMS Revision 0 8 8 Outdoor Unit OU7 24 OU8 30 3PH R410A 8 9 Outdoor Unit OU8 33 1PH R410A...
Страница 66: ...8 8 WIRING DIAGRAMS Revision 0 8 10 Outdoor Unit OU8 33 3PH R410A...
Страница 68: ...9 2 ELECTRICAL CONNECTIONS Revision 0 9 3 FLO 30 N 3PH...
Страница 69: ...10 1 REFRIGERATION DIAGRAMS Revision 0 10 REFRIGERATION DIAGRAMS 10 1 Heat Pump Models 10 1 1 FLO 7 N...
Страница 70: ...10 2 REFRIGERATION DIAGRAMS Revision 0 10 1 2 FLO 9 12 14 N R410A...
Страница 72: ...10 4 REFRIGERATION DIAGRAMS Revision 0 10 1 4 FLO 24 N R410A...
Страница 135: ...14 3 OPTIONAL ACCESSORIES Revision 0 14 3 RCW RCW2 Wiring Connections as Shown on Kit...
Страница 137: ...15 5 OPTIONAL ACCESSORIES Revision 0...
Страница 138: ...15 6 OPTIONAL ACCESSORIES Revision 0...
Страница 139: ...15 7 OPTIONAL ACCESSORIES Revision 0...
Страница 140: ...15 8 OPTIONAL ACCESSORIES Revision 0...
Страница 141: ......