CONTROL SYSTEM
Revision 0
11-7
11.3.7 RV
Fault
This test is applied only in compressor units where 4.7k
Ω
resistor is not connected to
the OCT.
The test is performed every time the unit is switched from OFF/STBY to OPER in Heat
mode or changes operation mode from COOL/DRY to HEAT or (this applies also in
AUTO COOL/HEAT mode).
If ICT is lower than 35
º
C at the time of mode change, then at the first occurrence of 15
min continuous COMP operation, ICT is compared with ICT reading when the COMP
was switched from OFF to ON 15 min before. RV fault is defined when ICT decreases
more than 5
º
C.
In this case, the COMP will stop and the SB LED will blink. The fault is reset after
switching to SB or after mode change.
11.3.8 General
Features
a. Allowed (control target) range for RAT is SPT +/-1ºC.
b. Whenever the unit is changed from COOL/DRY/STBY mode to HEAT mode or
vice versa, the procedures below are followed:
Stop COMP for 3 min
→
Change RV state
→
Start COMP if necessary.
Содержание K XLN24 RC 3PH
Страница 12: ...OUTLINE DIMENSIONS Revision 0 4 1 4 OUTLINE DIMENSIONS 4 1 K XLN 24 30...
Страница 13: ...OUTLINE DIMENSIONS 4 2 Revision 0 4 2 Outdoor Unit OU724 4 3 Outdoor Unit OU830...
Страница 29: ...WIRING DIAGRAMS Revision 0 7 3 7 5 Outdoor Unit OU724 OU830 3PH...
Страница 31: ...ELECTRICAL CONNECTIONS 8 2 Revision 0 8 3 K XLN 24 30 3PH...
Страница 32: ...REFRIGERATION DIAGRAMS Revision 0 9 1 9 REFRIGERATION DIAGRAMS 9 1 Heat Pump Models 9 1 1 K XLN 24 R410A...
Страница 33: ...REFRIGERATION DIAGRAMS 9 2 Revision 0 9 1 2 K XLN 30 R410A...
Страница 34: ...REFRIGERATION DIAGRAMS Revision 0 9 3 9 2 Cooling Only Models 9 2 1 K XLN 24 30...
Страница 37: ...CONTROL SYSTEM 11 2 Revision 0 11 1 3 Main PCB Controller...
Страница 75: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 2 Revision 0 17 18 19 20 25 26 21 22 23 24 27 28 32 29 31 33 34 30 35...
Страница 78: ...EXPLODED VIEWS AND SPARE PARTS LIST Revision 0 13 5 13 3 Exploded view of outdoor unit ONG...
Страница 79: ...EXPLODED VIEWS AND SPARE PARTS LIST 13 6 Revision 0...