INSTALLATION OF THE INDOOR UNIT

- Mark the position of each supporting rod, cooling pipes,

drainpipe of condensates, wires of power supply and cable of
remote control .
The supporting rods can be fixed, depending on the type of
ceiling.

Various models to fix

- Fix the angle brackets provided with the unit, on the threaded

rods , we recommend Ø 6, max.Ø 8,

and keep them away from the ceiling at a distance of 270mm or
107mm .

GENERAL POINTS
BEFORE INSTALLATION

- It is recommended to place the indoor unit as close as possible

to its final location before unpacking.

- Avoid to lay heavy tools  or weights on the packed unit.

Check as soon as the packing is opened, that no accessories
required for the installation, are missing. The grilled panel is
provided separately for better protection.

DO NOT LIFT THE UNIT BY GRASPING THE
DRAINPIPE OF CONDENSATES OR THE
COOLING CONNECTIONS, BUT ONLY THE
FOUR CORNERS.

CHOICE OF LOCATION

- Do not install the un it in rooms where inflammable gas or acid

or alkaline substances are present. Aluminium  and copper
evaporators and/or plastic components inside could be
damaged.

- Do no install the unit in workshops or kitchens; oil vapours

attracted by treated air could settle on the evaporators of the
unit and change its performance or damage plastic parts inside.

- The indoor unit is flush mounted into a false ceiling, size of the

tiles 600x600 and multiple.

-  Installation of the unit is made easier when using a fork-lift truck

and the base of the packing by placing the base between the
unit and the forks of the truck .

- It is recommended during installation to choose the location of

the unit as much as possible in the middle of the room, so as to
obtain the best distribution of treated air.

- Check that you can remove the discharge grilles and that the

clearance is large enough to allow maintenace and repairs.

- The cassettes must not be positioned above electrical

The cassettes must not be positioned above electrical

The cassettes must not be positioned above electrical

The cassettes must not be positioned above electrical

The cassettes must not be positioned above electrical
equipment in order to avoid exposure to running water

equipment in order to avoid exposure to running water

equipment in order to avoid exposure to running water

equipment in order to avoid exposure to running water

equipment in order to avoid exposure to running water
which could appear that may occur under extreme

which could appear that may occur under extreme

which could appear that may occur under extreme

which could appear that may occur under extreme

which could appear that may occur under extreme
conditions.

conditions.

conditions.

conditions.

conditions.

HOLDER TO FIX THE REMOTE
CONTROL ON THE WALL

- Use the holder when the remote control is not in operation. The

control can be easily removed and placed back on the holder.

2

1

Nut

Rubber mount

Large washer

Counter-nut

Angle bracket

to hang

9

K INST. MENU

Содержание K 30 RCF

Страница 1: ...nnections Servicing 4 5 6 7 8 8 9 10 10 11 12 14 15 16 CONTENTS SPLIT DUCTED UNITS For information on control options and P C Board refer to Electronic Controls and Control Options for KRS Controllers Manual Part No TH 3451 A 3990038A Uncontrolled Document for Information Purposes August 2003 A fresh approach to air conditioning INDOOR MODEL OUTDOOR MODEL HEATPUMP K 30 RCF GC30RCFA GC30RCC K 45 RC...

Страница 2: ...onal legislation transposing them Machines Directive 98 37 ECC Low tension Directive DBT 73 23 EEC Electromagnetic compatibility Directive 89 336 EEC Pressurised Equipment Directive DESP 97 23 CEE sub module A category I and that the following paragraphs of the harmonized standards have been applied NF EN 60 204 1 1998 NF EN 60 335 1 1995 NF EN 60 335 2 40 1994 NF EN 55 022 1998 NF EN 61 000 3 2 1...

Страница 3: ...rent required for any other appliance connected with the same circuit WARNING Cutoff power supply before starting to work on the appliance The manufacturer declines any responsibility and the warranty becomes void if these instructions are not respected If you meet a problem please call the Technical Department of your area If possible assemble the mandatory or optional accessories before placing ...

Страница 4: ...tpump heating 17 4 10 5 Cooling ventilation A Maximum current Fuse rating aM Fuse rating ASE VDE Cable section minimum MAINS Linking pipes Maximum current INTERCONECT Cable section minimum INTERCONECT A A A mm2 A mm2 24 8 25 25 3Core 4 2 6Core 1 5 12 4 25 25 5Core 1 5 2 6Core 1 5 A 11 2 17 4 POWER SUPPLY V PH Hz 13 45 18 75 25 25 3Core 4 2 6Core 1 5 13 94 GC30RCFA GC45RCFX GC30RCC OUTDOOR K30RCF K...

Страница 5: ...rs 29 m 5 m 17 grs 290 grs 30 m 6 m 34 grs 348 grs 31 m 7 m 51 grs 406 grs 32 m 8 m 68 grs 464 grs 33 m 9 m 85 grs 522 grs 34 m 10 m 102 grs 580 grs 35 m 11 m 119 grs 638 grs 36 m 12 m 136 grs 696 grs 37 m 13 m 153 grs 754 grs 38 m 14 m 170 grs 812 grs 39 m 15 m 187 grs 870 grs 40 m 16 m 204 grs 928 grs 41 m 17 m 221 grs 986 grs 42 m 18 m 238 grs 1044 grs 43 m 19 m 255 grs 1102 grs 44 m 20 m 272 g...

Страница 6: ...0 625 1 2 5 6 7 8 9 Ø 1 2 3 3 4 4 Ø 200 Ø 100 10 10 11 585 5 150 120 140 369 430 118 5 1 False ceiling 2 T shaped rod false ceiling 3 Evaporator 4 Fan 5 Return air grille 6 Electrical box removable 7 Draining of condensates 8 GAS pipe 9 LIQUID pipe 10 Supply air pop prepunched 11 fresh air pop prepunched 510 30 5 30 5 K INST MENU ...

Страница 7: ...337 362 380 WIRING CONNECTIONS LIQUID TUBE FLARED SUCTION TUBE FLARED AIR INTAKE AIR OUTLET 357 50 695 340 97 900 706 55 225 293 DIMENSIONS OF OUTDOOR UNIT GC30RCFA 7 K INST MENU ...

Страница 8: ... VIEW WIRING CONNECTIONS SUCTION PIPE FLARED LIQUID PIPE FLARED RIGHT VIEW 25 100 DIMENSIONS OF OUTDOOR UNIT GC45RCFX 340 380 WIRING CONNECTIONS 90 50 130 230 290 AIR INTAKE AIR OUTLET 356 5 50 705 100 1255 900 WALL 200 MIN 300 MIN WALL 600 MIN WALL MINIMUM CLEARANCE 800 MIN WALL 500 MIN FROM TOP 15 DIMENSIONS OF OUTDOOR UNIT GC30RCC 8 K INST MENU ...

Страница 9: ...0 and multiple Installation of the unit is made easier when using a fork lift truck and the base of the packing by placing the base between the unit and the forks of the truck It is recommended during installation to choose the location of the unit as much as possible in the middle of the room so as to obtain the best distribution of treated air Check that you can remove the discharge grilles and ...

Страница 10: ...then the nuts and counter nuts of the threaded rods Finally place the rubber mount Check once more that the unit is in a horizontal position after connection of the condensate drain and the refrigeration pipework DRAINING CONDENSATES To obtain correct condensate drainage the slope downwards should be 1 cm per meter without any bottleneck nor passage upwards Furthermore a trap of at least 50 mm hig...

Страница 11: ...their fittings can then be attachedtothecondensatedrainandpowercableswithaclamp INSTALLATION OF REFRIGERANT LINES Drill an 80 mm diameter hole through the wall for the crossing of the lines between the outdoor unit and indoor unit INSTALLATION OF THE OUTDOOR UNIT Minimum clearance to respect in mm Avoid recycling the air even partially between the air inlet and discharge INSTALLATION ON THE FLOOR ...

Страница 12: ...the vacuum pump and check that the dial pointer drops to 0 1 MPa 76 cm Hg The pump should remain in operation for at least 15 minutes 4 Before removing the vacuum pump check that the vacuum dial remains stable for five minutes 5 Disconnect the vacuum pump and reclose the service valve 6 Remove the caps from the GAS and LIQUID valves and open them with a socket wrench to release the R22 contained i...

Страница 13: ...ld especially ensure an airtight separation between return air and supply air The figure indicates the airtight packings avoiding A the by pass of air B discharge of treated air inside the false ceiling Check after installation that the space between frame and false ceiling is less than 5 mm Latch of the grille Packings AIR INLET AND OUTLET Return Supply air grille Unpack the assembly with care Fi...

Страница 14: ...side wall Check that there is no direct contact between the pipework and the wall FIXING Check that the indoor and outdoor units are firmly fixed Install the elements previouly removed MAINTENANCE Before servicing switch the power supply OFF RENEWAL OF AIR Lateral openings allow to install separate ducts for fresh air from outside and supply air towards an adjoining room Remove the anti condensati...

Страница 15: ...control unit cable Pull the polystyrene tray out as straight as possible toward the bottom Unscrew the central fan attaching screw Remove the fan Disconnect the motor wires marking on the wires and the connector Remove the four motor support screws Replace the motor Reconnect the new motor carefully checking the marking on each wire Install the motor support Install the fan Install the polystyrene...

Страница 16: ... POWER SUPPLY K30RCF POWER SUPPLY 240 V 50 Hz GC30RCFA GC30RCC K45RCF GC45RCFX POWER SUPPLY 3N 415 V 1 6 K INST MENU ...

Страница 17: ...oolant to increase Checkthatthesurfaceofthealuminiumfinsoftheheatexchanger is not damaged by impacts or scratches and clean with an appropriate tool if necessary ELECTRICAL SECTION ELECTRICAL SECTION ELECTRICAL SECTION ELECTRICAL SECTION ELECTRICAL SECTION Check that the main power supply cable is not damaged or altered in such a way as to affect the insulation Check that the interconnecting cable...

Страница 18: ...NECTION TO THE INDOOR LIQUID VALVE DURING INSTALLATION AS THE ABOVE ILLUSTRATION WARNING WITHOUT THIS KIT THE UNIT WILL NOT OPERATE PROPERLY IN THE HEATING MODE FOR CONNECTION TO INDOOR UNIT RESTRICTOR KIT INSTALLATION RESTRICTOR KIT INSTALLATION SUCTION VALVE RESTRICTOR LIQUID VALVE 1 8 K INST MENU ...

Страница 19: ...ffices on the parkSuite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE Suite 3 19 Darby Street Newcastle NSW 2300 TEL 02 4940 4652 FAX 02 4940 4653 NEW ZEALAND 517A Rosebank Road Avondale Auckland NZ TEL 09 820 0333 FAX 09 820 0332 www airwell com au NZ Tech Support Freecall TEL 0800...

Отзывы: