600 mm
MAXI
1cm/m
50 mini
Ø 16max
OK
NO
Nut
- In case the brackets are assembled at the lower part, remove
the insulating foam around the fixing nuts .
The possibility to adjust the bracket at different heights leaves
the brackets free to fix them at the upper or lower part of the
cassette.
- Fixing the brackets at the lower part offers an easier assembly.
Do not tighten the nuts, nor the counter-nuts, this should only be
done after having made all connections and placed the unit in its
final horizontal position.
- Lift the unit (without the frame) carefully by picking it up at the
four corners.
- Place the unit in the false ceiling.
- To make the assembly easier the electrical box can be
disassembled by removing 2 screws, and disconnect the
multipoints connector (15 pts connector for the main connection)
and small connector for the infra-red.
- Fix the cassette, connect the multipoints connectors, place the
cassette into is final position and reset the electrical box with 2
screws
- Fix the screws to fix the corner irons .
- In case the false ceiling is 300 mm distant from the ceiling (mini-
mum height admitted) it may be necessary to remove
temporarily a few T-shaped rods from the false ceiling.
- Position the unit with a level and keep 10mm between the sheet
metal body and the false ceiling .
Angle bracket
to hang
Electrical box
T-shaped rod
- Position the unit on the supporting rods of the false ceiling by
first tightening the bolts on the side , then the nuts and counter-
nuts of the threaded rods . Finally place the rubber mount.
- Check once more that the unit is in a horizontal position after
connection of the condensate drain and the refrigeration
pipework.
DRAINING CONDENSATES
- To obtain correct condensate drainage , the slope downwards
should be 1 cm per meter without any bottleneck nor passage
upwards . Furthermore a trap of at least 50 mm high should be
mounted to avoid bad smells in the room.
- Install an auxiliary pump to drain condensates and a levelcontroller
if the condensates are to be drained at a higher level than the
unit. It is recommended to install an appliance equipped with a
safety floater to stop the compressor in case the auxiliary pump
is damaged.
- The drainpipe of condensates should be heat insulated with
insulating material 5 to 10 mm thick, such as polyurethane,
propylane or neoprene, avoiding condensation.
- If several units are placed in the room , the draining system can
be made as indicated above.
Connection on the top of the pipe
Heat insulated drainpipe
Slope of 1cm/m
Trap
THE CAS
THE CAS
THE CAS
THE CAS
THE CASSET
SET
SET
SET
SETTE MUST AL
TE MUST AL
TE MUST AL
TE MUST AL
TE MUST ALW
W
W
W
WA
AA
A
AYS REMAIN CONNECTED
YS REMAIN CONNECTED
YS REMAIN CONNECTED
YS REMAIN CONNECTED
YS REMAIN CONNECTED
WITH ELECTRICAL SUPPL
WITH ELECTRICAL SUPPL
WITH ELECTRICAL SUPPL
WITH ELECTRICAL SUPPL
WITH ELECTRICAL SUPPLY TO ALL
Y TO ALL
Y TO ALL
Y TO ALL
Y TO ALLOW THE DRAI-
OW THE DRAI-
OW THE DRAI-
OW THE DRAI-
OW THE DRAI-
NAGE OF WATER CONDENSATS.
NAGE OF WATER CONDENSATS.
NAGE OF WATER CONDENSATS.
NAGE OF WATER CONDENSATS.
NAGE OF WATER CONDENSATS.
1 0
K INST. MENU