CLH LN
402
502
552
602
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
50.6
58.3
65.4
72.5
Rated current
A
56.9
67.0
82.0
91.9
Max. current (FLA)
A
85.5
98.5
109.5
120.5
Max. start-up current (LRA)
A
269
323
371
382
External fuses
(A)
100
125
125
160
Max. cable section (1)
mm
2
35
50
70
70
CLH LN with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
52.4
60.1
67.2
74.3
Rated current
A
61.8
71.9
86.9
96.8
Max. current (FLA)
A
90.4
103.4
114.4
125.4
Max. start-up current (LRA)
A
274
328
376
387
External fuses
(A)
100
125
125
160
Max. cable section (2)
mm
2
35
50
70
70
Technical data
CLH LN
182
202
242
302
352
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
19.3
25.9
31.4
36.7
42.8
Rated current
A
22.6
31.0
42.3
52.1
52.0
Max. current (FLA)
A
32.5
43.7
50.3
61.5
72.3
Max. start-up current (LRA)
A
116
150
176
207
256
External fuses
(A)
50
63
63
80
100
Max. cable section (1)
mm
2
16
25
25
35
35
CLH LN with pump
Rated voltage
V(%)/ph/Hz
400 ±10% / 3 / 50
Max. absorbed power
kW
20.1
26.7
32.9
38.2
44.6
Rated current
A
24.7
33.1
46.1
55.9
56.9
Max. current (FLA)
A
34.6
45.8
54.1
65.3
77.2
Max. start-up current (LRA)
A
119
152
180
211
261
External fuses
(A)
50
63
63
80
100
Max. cable section (2)
mm
2
16
25
25
35
35
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
(2) Data which refer to a single pump.