7
INSTALLATION
ÉLECTRIC SPÉCIFICATIONS
ELECTRICAL POWER SUPPLY
A variance of ±10% is acceptable in relation to the operating voltage marked on the appliance’s Maker’s Plate.
Operating voltages:
²
230V / 1 ph / 50 Hz (207 Volts minimum; 253 Volts maximum.)
Comments: the stated voltages represent the accepted range. However, certain components may be subject to
premature wear on appliances operating continuously, for extensive periods, on abnormally low or high voltages.
UNIT LOCATION
1 - Install the unit in a location allowing easy removal of the filter and the access panels
to the electrical box/compressor and fan by leaving sufficient free space for servicing
personnel to perform maintenance
and repairs. Leave sufficient space
for the water, electricity and duct
connections.
2 - The installer must ensure that access
under the suspended ceiling is provided,
and that sufficient space is provided for
the suspension angle brackets, the duct
attachment collars and the water and
electrical connections.
3 - Provide space under the unit for a siphon
on the condensates drainage pipe. Do not
install the unit on top of pipe work.
4 - Each unit is suspended from the ceiling on
four threaded rods. The rods are attached through the shock mounts to the corners of the unit by
suspension angle brackets.
Warning!
Do not use rods of a diameter smaller than that stated below. The rods must be solidly
anchored to the ceiling and to the ceiling joists.
5 - Each unit is supplied with a set of pre-fitted suspension angle brackets and a fitting kit contained in
the pouch with the technical manual. The kit comprises 4 shock mounts, 4 washers, 4 nuts and 4
locknuts.
6 - Arrange the threaded rods in accordance with the dimensions stated below. The use of nuts and
locknuts is recommended for attaching the suspension rods to the unit as the unit’s vibrations may
loosen a single nut. The installer is liable for any damage in the event of this recommendation not
being followed.
7 - To facilitate drainage, the unit must be angled in both planes towards the condensates drainage pipe.
(Slope minimum: 2 %)
M8 THREADED ROD
(NOT SUPPLIED))
SHOCK MOUNT
WASHER
NUT
LOCKNUT
453
593
893
39
39
600 mm
600 mm
600 mm
600 mm
200 mm