FRESH AIR INTAKE

If required this must be fitted to the return air ducting as no special provision is made within the unit.
All fresh air intakes must be provided with air filters if they are connected to the ductwork between 
the return air filter and the unit.
Consideration should be made to the return air sensor.  The ducted units have a return air sensor 
mounted near the return air coil.  Fresh air influences  may affect the room temperature.  Relocating 
the position of the return air sensor may be required.

AIR FILTERS

Air filters are not provided and no provision is made for fitting them within the unit as standard.
Air filters should however be provided by the installing contractor and located in an accessible location 
between the return air grille and the unit.  These filters must be sized for a maximum face velocity of 
2.0 m/sec. 

7

Where the unit must be installed in an attic space or outside, the following conditions must be 

assured: 

a)  The unit must be protected from rain, heat and radiation by an additional layer of 1” 

thick  thermal insulation.

b)  The return-air duct should be as short as possible, with a minimum dimension of 

700x300 mm (or similar cross section) with full acoustical lining inside, and no more 
than two long-radius elbows. The cross section at the duct connection to the unit shall 
be equal to that of the unit. 

c)  The distance between the return air grille and the air intake on the unit must be as 

short as possible. A minimum free passage of 0.3 m is necessary along the entire 
return-air path. 

d)  The installation should be designed to withstand the weight of the unit and avoid 

resonance vibrations. Use serrated rubber mounting under the unit and flexible joints 
for the air duct. 

Design and prepare in advance easy access for servicing as follows: (See Figure 4)

e)  The minimum height clearance for the installation is 470 mm. 

f)  Allow the access to the electrical control box to facilitate its easy removal by opening 

the cover (fastened by 3 screws). Allow also the access to the 700 mm long cable 
which is tied inside the unit to enable relocation of the control box. 

g)  A distance of 200 mm must be kept between the rear side of the unit and any near-by 

wall, to allow free air passage. 

h)  A distance of 300 mm must be kept to allow free air intake and convenient access to 

air filters. Allow the access to service panels from opposite sides (right and left) for 
the maintenance of fan and motor. 

Содержание DSD 40 RCA Series

Страница 1: ...ENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES INSTALLATION INSTRUCTIONS DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX DSD CAT NO ENG 6 5 9...

Страница 2: ...g mounting 8 OUTDOOR UNIT INSTALLTION 9 INSTALLATION OF INTERCONNECTING TUBING BETWEEN INDOOR AND OUTDOOR UNIT 10 General 10 Recomendation for interconnecting tubing installation 11 Setting in operati...

Страница 3: ...le No 1 If longer tubing is required consult your dealer b Outdoor unit installation should provide for Easy service access Minimum disturbance to the owner and nearby neighbors A minimum distance of...

Страница 4: ...ntrol Unit Port 8 Main Power Port Figure 1 Indoor Unit Outline Dimensions Return Air Spigot Connection Size W H DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX D...

Страница 5: ...tion tube connector flared 3 Liquid tube connector flared 4 Service valves 5 Service taps 6 Air inlet 7 Air outlet Figure 2 General dimensions of GCD 40 RC GCD 40 RCX GCD 50 RCX outdoor units WALL 300...

Страница 6: ...3 General dimensions of GCD 60 RCX outdoor unit Figure 3A Example of Installation OUTDOOR UNIT Condenser GCD 60 RCX WALL 300 MIN 300 MIN WALL 600 MIN WALL 1000 MIN WALL 500 MIN FROM TOP MINIMUM CLEAR...

Страница 7: ...to the unit without interference b The unit should not be installed close to rooms where noise should be avoided bedrooms children rooms etc The location should allow good air circulation 1 Frame inst...

Страница 8: ...le with a minimum dimension of 700x300 mm or similar cross section with full acoustical lining inside and no more than two long radius elbows The cross section at the duct connection to the unit shall...

Страница 9: ...ion 4 3 Ceiling Mounting The indoor unit can be mounted using spring or serrated rubber isolators a Spring isolators mounting Insert four 3 8 stu in the ceiling according to the dimensions of the spri...

Страница 10: ...this type of installation 1 Concrete Ceiling 2 Bolt for Ceiling Insert 3 Leveling Nut 4 Fastening Nut Figure 7 Indoor Unit Installation Ceiling Mounting using Rubber Isolators 5 OUTDOOR UNIT INSTALLA...

Страница 11: ...inimum If bends are necessary perform them only by using professional tube benders and not manually Make sure that tubing is insulated on its entire length including tube ends and quick connectors or...

Страница 12: ...ith Armaflex or equivalent insulation after installation has been completed 1 Air 2 Air 3 Suction Line 4 Oil trap every 3 m 5 Liquid Line 6 Indoor unit 7 See Table 8 Outdoor Unit Figure 10 Interconnec...

Страница 13: ...1 9 2 1 3 8 1 2 5 8 3 4 1 Copper Tube 2 Flaring Tool Figure 15 Tube flaring 6 3 3 Evacuation and setting in operation a Connect two charging hoses equipped with a push pin on one side as shown in Fig...

Страница 14: ...ce Connection 1 Charging Set 2 Vacuum Pump 3 Outdoor Unit 4 Service Port 5 Valve Cap 6 3 Way Suction Valve 7 Service Port Optional 8 3 Way Liquid Valve 9 Indoor unit 10 Suction Flare Connection 11 Liq...

Страница 15: ...with water and verify its free flow through the drain line Verify also absence of any water leakage underneath the unit 8 ELECTRICAL CONNECTIONS 8 1 Power Supply WARNING Electrical connection shall be...

Страница 16: ...d control optional 2 Terminal board 8 Power supply 3 Interconnecting cable 9 Semi automatic breaker by installer 4 Indoor unit 10 Indoor safety breaker 10A 5 Display control unit 11 Terminal board 6 W...

Страница 17: ...the unit is connected to the power supply the outdoor unit controller will start a self test for correct phase order and after a few seconds GREEN LED 1 will light on If the RED LED 2 and GREEN LED 3...

Страница 18: ...holes in the wall to match the holes in the Display Control Unit install the inserts and fasten the unit to the wall with 3 screws The Display Control Unit 4 is provided of a special communication ca...

Страница 19: ...Gold Green Black Brown Purple Yellow Orange Red Figure 21 Connection to a single Display Control Unit 1 Main Control Board on Indoor Unit 2 Distribution Board Cat N 402729 3 Communication cable Cat N...

Страница 20: ...ore be determined as follows a Avoid installation at location exposed to direct sunlight or near heat sources b Select a location free of any obstructions such as curtains etc c Select a neutral zone...

Страница 21: ...mote control commands 4 2 Outdoor unit Check for any abnormal noise or vibrations during operation of the air conditioner Check that the noise condensate drainage or air flow does not disturb the neig...

Страница 22: ...5 ADELAIDE Offices on the Park Suite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE...

Отзывы: