6.  INSTALLATION OF INTERCONNECTING TUBING BETWEEN INDOOR AND 
     OUTDOOR UNITS

  6.1 General

(See Figure 9)

The tubing between the indoor and 
outdoor units consist of two copper 
tubes and an electric cable routed 
through a 60-mm wall opening. In 
addition, a drainage hose is installed 
between the indoor unit and the 
closest drainage point. Connect both 
sections, taking the shortest, most 
direct route.

1.  To Outdoor Unit  
2. Interconnecting 

Tubing 

3. Electric 

Cable 

4. Inclination 

Angle

5.  To Indoor Unit 

Figure 9. Interconnecting tubing and 

cable

WARNING!

When laying the tubing for the installation, make sure that the ends are sealed to prevent penetration of
dirt, moisture etc. To prevent dust or moisture from entering the tubes, seal them with caps or masking tape.
It is recommended to clean the inside space of the tubes with nitrogen before connecting them to the unit.

Whenever possible, avoid passing tubes through hot zones, such as walls next to ovens, chimneys, etc.  
In such cases, additional insulation or other means of protection should be employed. 

Tubing route shall be kept in straight lines as much as possible. When installing, keep the number of tube 
bends to a minimum. If bends are necessary, perform them only by using professional tube benders and not 
manually. 

Make sure that tubing is insulated on its entire length, including tube ends and quick-connectors, or
flare-nuts, to avoid tube “sweating” and water dripping from it.

Tubing shall be of the “L” type, without any damage. Tube inside walls must be kept absolutely clean prior to 
and during installation operations. 

Each tube shall be individually insulated as follow: until 5/8” O. D. with 6 mm wall thick sleeve - above 3/4” O. 
D. with 9 mm wall thick sleeve. 

For diameters, length of liquid and suction lines, and height difference, see the Table No. 1 for each model. If 
the liquid or suction tube diameters  differs from the corresponding flare connector diameter (mounted on the 
unit), use a suitable reducing union (it is forbidden to insert a tube into another tube) between the flare 
connector and the requested size. 

Table No. 1: Unit Interconnecting tubing (indoor and outdoor units) 

10

15

20

25

30

50

Suction

3/4"

3/4"

3/4"

7/8"

7/8"

7/8"

Liquid 3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

Suction

3/4"

3/4"

3/4"

7/8"

7/8"

7/8"

Liquid 3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

Suction

7/8"

7/8"

7/8"

7/8"

7/8"

7/8"

Liquid 1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

DSD 50 RCA

50

25

DSD 60 RCA

50

25

Max HEIGHT 

DIFFERENCE

50

25

CONNECTING LINE

DSD 40 RCA

TUBING  LENGTH, up to - (in metrers, one way)

Max TUBING 

LENGT H

UNIT  MODEL

INTERCONNECTION TUBING SIZE TABLE

Содержание DSD 40 RCA Series

Страница 1: ...ENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES INSTALLATION INSTRUCTIONS DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX DSD CAT NO ENG 6 5 9...

Страница 2: ...g mounting 8 OUTDOOR UNIT INSTALLTION 9 INSTALLATION OF INTERCONNECTING TUBING BETWEEN INDOOR AND OUTDOOR UNIT 10 General 10 Recomendation for interconnecting tubing installation 11 Setting in operati...

Страница 3: ...le No 1 If longer tubing is required consult your dealer b Outdoor unit installation should provide for Easy service access Minimum disturbance to the owner and nearby neighbors A minimum distance of...

Страница 4: ...ntrol Unit Port 8 Main Power Port Figure 1 Indoor Unit Outline Dimensions Return Air Spigot Connection Size W H DSD 40 RCA GCD 40 RC DSD 40 RCA GCD 40 RCX DSD 50 RCA GCD 50 RCX DSD 60 RCA GCD 60 RCX D...

Страница 5: ...tion tube connector flared 3 Liquid tube connector flared 4 Service valves 5 Service taps 6 Air inlet 7 Air outlet Figure 2 General dimensions of GCD 40 RC GCD 40 RCX GCD 50 RCX outdoor units WALL 300...

Страница 6: ...3 General dimensions of GCD 60 RCX outdoor unit Figure 3A Example of Installation OUTDOOR UNIT Condenser GCD 60 RCX WALL 300 MIN 300 MIN WALL 600 MIN WALL 1000 MIN WALL 500 MIN FROM TOP MINIMUM CLEAR...

Страница 7: ...to the unit without interference b The unit should not be installed close to rooms where noise should be avoided bedrooms children rooms etc The location should allow good air circulation 1 Frame inst...

Страница 8: ...le with a minimum dimension of 700x300 mm or similar cross section with full acoustical lining inside and no more than two long radius elbows The cross section at the duct connection to the unit shall...

Страница 9: ...ion 4 3 Ceiling Mounting The indoor unit can be mounted using spring or serrated rubber isolators a Spring isolators mounting Insert four 3 8 stu in the ceiling according to the dimensions of the spri...

Страница 10: ...this type of installation 1 Concrete Ceiling 2 Bolt for Ceiling Insert 3 Leveling Nut 4 Fastening Nut Figure 7 Indoor Unit Installation Ceiling Mounting using Rubber Isolators 5 OUTDOOR UNIT INSTALLA...

Страница 11: ...inimum If bends are necessary perform them only by using professional tube benders and not manually Make sure that tubing is insulated on its entire length including tube ends and quick connectors or...

Страница 12: ...ith Armaflex or equivalent insulation after installation has been completed 1 Air 2 Air 3 Suction Line 4 Oil trap every 3 m 5 Liquid Line 6 Indoor unit 7 See Table 8 Outdoor Unit Figure 10 Interconnec...

Страница 13: ...1 9 2 1 3 8 1 2 5 8 3 4 1 Copper Tube 2 Flaring Tool Figure 15 Tube flaring 6 3 3 Evacuation and setting in operation a Connect two charging hoses equipped with a push pin on one side as shown in Fig...

Страница 14: ...ce Connection 1 Charging Set 2 Vacuum Pump 3 Outdoor Unit 4 Service Port 5 Valve Cap 6 3 Way Suction Valve 7 Service Port Optional 8 3 Way Liquid Valve 9 Indoor unit 10 Suction Flare Connection 11 Liq...

Страница 15: ...with water and verify its free flow through the drain line Verify also absence of any water leakage underneath the unit 8 ELECTRICAL CONNECTIONS 8 1 Power Supply WARNING Electrical connection shall be...

Страница 16: ...d control optional 2 Terminal board 8 Power supply 3 Interconnecting cable 9 Semi automatic breaker by installer 4 Indoor unit 10 Indoor safety breaker 10A 5 Display control unit 11 Terminal board 6 W...

Страница 17: ...the unit is connected to the power supply the outdoor unit controller will start a self test for correct phase order and after a few seconds GREEN LED 1 will light on If the RED LED 2 and GREEN LED 3...

Страница 18: ...holes in the wall to match the holes in the Display Control Unit install the inserts and fasten the unit to the wall with 3 screws The Display Control Unit 4 is provided of a special communication ca...

Страница 19: ...Gold Green Black Brown Purple Yellow Orange Red Figure 21 Connection to a single Display Control Unit 1 Main Control Board on Indoor Unit 2 Distribution Board Cat N 402729 3 Communication cable Cat N...

Страница 20: ...ore be determined as follows a Avoid installation at location exposed to direct sunlight or near heat sources b Select a location free of any obstructions such as curtains etc c Select a neutral zone...

Страница 21: ...mote control commands 4 2 Outdoor unit Check for any abnormal noise or vibrations during operation of the air conditioner Check that the noise condensate drainage or air flow does not disturb the neig...

Страница 22: ...5 ADELAIDE Offices on the Park Suite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE...

Отзывы: