5.SPECIFICATIONS FOR FIELD SUPPLIED ELB AND WIRE
Model
Power supply wiring
Remote controller wiring Transmission
wiring
Field ELB
Wire and Size
wires
Size
DLV007
16A
Must comply
with maximum
currentandlocal
codes (
≥
0.75mm
2
)
Twisted-pair Wire
≥
1.0mm
2
DLV009
DLV012
DLV015
DLV018
DLV021
DLV024
6.HEIGHT COMPENSATION SETTING
The Compensation setting according to installation height can be done by using the dip switch 11 and 12 on controller PCB.
Installation Height
Height Code
DS11
DS12
2.3-2.7(m)
H0
OFF
OFF
2.7-3.1(m)
H1
OFF
ON
3.1-3.5(m)
H2
ON
OFF
3.5(m)
H3
ON
ON
Note: Please disconnect the power supply when change this setting.
If you feel too noisy, please set DS11 and DS12 to lower height code level.
CHECK ITEMS
BEFORE POWER ON
Is there any gas leakage at flare nut connections?
⿌
Has the heat insulation been carried out at flare nut connection?
⿌
Is the connecting cable being fixed to terminal board firmly? Is the connecting cable being clamped firmly?
⿌
Is the drainage OK? (Refer to "Check the drainage" section)
⿌
Is the earth wire connection properly done?
⿌
Is the indoor unit properly hooked to the installation plate? Is the power supply voltage complied with rated value?
⿌
AFTER POWER ON
Is there any abnormal sound?
⿌
Is the cooling operation normal?
⿌
Is the thermostat operation normal?
⿌
Is the remote control's LCD operation normal?
⿌