2

UNIT INSTALLATION

STEP 1:

 

Deciding ceiling opening size

1.Gird ceiling installation situation (600mmx600mm standard ceiling):

   ● Because this unit is a mini-cassette, there is no need to make an 

      opening cut on the ceiling, just remove one piece of ceiling panel.

   ● Under this installation condition, decoration paner 625mmx625mm

      is recommended.

2.Hard ceiling installation situation:

   ● Create the ceiling opening required for installation, below shows

      the relationship of the ceiling opening to unit and the panel. (Fig 3)

   ● Under this installation situation, decoration panel 725mmX725mm

      is recommended.

   ● The maximum ceiling opening size is 680mm. Pay attention that 

      there must be an overlapping between panel and ceiling. (Fig 3-2)

STEP 2: 

Installing the indoor unit

 

A Installing the unit body

1.   Use installation template (supplied with the panel) when deciding the 

suspension bolt position (Fig 4). Fig 5 and table 1 show the dimensions 

relationship.

Refrigerant 

piping

Suspension 

hook (x4)

725

 (Decoration

 Panel)

585-680

 (Ceiling

 opening)

578

 (Indoor

 unit)

531

 (Suspension

 bolt)anel)

725 (Decoration Panel)

585-680 (Ceiling opening)

578 (Indoor unit)

531 (Suspension bolt)anel)

Ceiling opening dimension

585-680

Ceiling 

(Ceiling-panel overlapping dimension)

585-680(Ceiling

 opening

 dimension)

531(Suspension bolt pitch)

531

 (Suspension

 bolt

 pitch)

585-680 (Ceiling opening dimension) 

Ф Liquid Pipe

Ф Gas Pipe

CKV007

1/4”

1/2”

CKV009

1/4”

1/2”

CKV012

1/4”

1/2”

CKV015

1/4”

1/2”

CKV018

1/4”

1/2”

Table 2

            

Length 

  Type

A

B

C

D

E

007/009/012 230

160

115

169

91

015/018

281

160

115

169

91

Table 1

Fig 3-1

Fig 3-2

Installation 

hook

Fig 4

Wide tube

Narrow tube

Drain port

mm

Fig 5

Suspension hook

  2.Piping and wiring must be prepared before hand inside the ceiling when suspending 

the unit.

  3.The length of suspension bolts must be appropriate for a distance between the 

bottom of the bolt and the bottom of the unit of more than 15mm as shown in Fig 6.

  4.In order to prevent a possible looseness, it is recommended to use 3 hexagonal 

nuts (Prepared on site) and 2 washers (accessory) for each suspension bolt. Pay 

attention that 2 nuts will be used in the lower side.(Fig 7)

  5.Adjust the distance between the unit and the ceiling bottom to 10~12mm. Tighten all 

the nuts on the suspending bolts.(Fig 7)

(Unit: mm)

Unit:mm

Unit:mm

Unit:mm

40