5-2
PERFORMANCE DATA & PRESSURE CURVES
SM BS DCI 1- A.1 GB
5.1.3
Heating Capacity (kW) - Run Mode)
230[V] : Indoor Fan at High Speed
ID COIL ENTERING AIR DB TEMPERATURE [
o
C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
o
C]
DATA
15
20
25
-15/-16
TC
2.74
2.55
2.35
PI
0.80
0.89
0.97
-10/-12
TC
3.05
2.86
2.66
PI
0.97
1.05
1.13
-7/-8
TC
3.28
3.09
2.90
PI
1.09
1.17
1.26
-1/-2
TC
3.39
3.20
3.01
PI
1.16
1.24
1.32
2/1
TC
3.47
3.28
3.09
PI
1.20
1.28
1.36
7/6
TC
4.49
4.30
4.11
PI
1.26
1.34
1.42
10/9
TC
4.74
4.55
4.36
PI
1.33
1.42
1.50
15/12
TC
4.99
4.80
4.60
PI
1.41
1.49
1.57
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TH –
Total Heating Capacity, kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.1.4
Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Ca
p
a
c
it
y
R
a
ti
o
n
CONTENTS