GENERAL POINTS
LOCATION
- Do not install the indoor unit in rooms where inflammable
gas or acid or alkaline substances are stocked. The
aluminum and copper evaporator and/or the internal
plastic components could be damaged.
- Do not install the indoor unit in workshops or kitchens
where oil vapours attracted by treated air could set down
on the evaporator of the indoor unit and change the
performance or damage the internal plastic parts of the
unit.
- Installation of the unit will be easier when using a lift-
truck. Use the base of the packing by placing it between
the unit and the forks of the truck.
BEFORE INSTALLATON
- The appliance can be installed:
wall mounted
ceiling mounted
- It is recommended to place the unit as close as possible
to its final location before unpacking.
- Avid placing heavy tools or weights on the packed unit.
Check as soon as the packing has been opened that no
accessories required for the installation are missing.
DO NOT LIFT THE UNIT AT THE DRAIN PIPE OR
THE COOLING CONNECTIONS, BUT ONLY AT
THE 4 ANGLES.
INSTALLATION
- Mark the location of each support rod, the refrigerant
lines, the condensate discharge pipe, the power supply
cables and the remote control unit cable (see the
dimensions Fig.
1
a and
1
b).
CONFIGURATION :
ELECTRONIC CONFIGURATION FOR THE
COOLING MODEL
-The RC is configured for HEATPUMP MODEL.
-To configure it for COOLING MODEL, remove configuration
plug P/N ELD RC and replace it with configuration plug
P/N ELD ST (supplied with the appliance).
CAUTION be
careful to install
the plug in right
direction
(MANDATORILY
line up the arrows)
SELECTION OF PRESSURES
- Preselect the fanspeed according to the model, so as
to obtain the desired pressure by moving 3 wires on
the speed selection terminal box (see table Fig.
19
).
- Fasten the appliance on the wall with 4 screws (not
supplied) (Fig. 4).
CEILING MOUNTED
- The rods can be fixed depending on the type of ceiling,
as shown in (Fig.
2
).
- Connect the drain pipe and check once more that the
unit is in a horizontal position.
DRAINING OF CONDENSATES
- In order to drain the condensates, the downward slope
of the drain pipe should be 1 cm per meter without any
narrowing passage (Fig.
6
).
Furthermore a siphon at least
50
mm high should be
installed to avoid bad odours in the room.
- Install an auxiliary pump to drain the condensates and
a level controller, if needed, to drain the condensates
at a higher level than the unit.
WALL MOUNTED
- Position the unit with a airbulb level on the rods by
tightening first the bolds on the side (Fig. 3), then place
the rubber shock absorbers (Fig. 5) and finally tighten
the nuts and lock nuts of the threaded rods.