7.2.4 Electronic function.
7.2.4.1 Cooling mode
The speed of indoor fan can be optionally chosen as High/ Mid /Low
Compressor running rules:
T1>TS+2
F, compressor on
T1
≤
TS-2
F, compressor off
7.2.4.2 Auto mode
The machine will choose cooling, fan-
only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
2
℃
Cooling
-1
≤ΔT≤2
℃
Fan-only
The machine will choose actual running mode in auto mode in the below cases:
Power on or change mode to auto mode or adjust temperature in auto mode, the machine will
choose actual running mode again.
A: In auto mode, if the compressor keeps not running for 15 minutes. judge condition B
B: If 1
<ΔT or ΔT <-4
℃
, the machine will choose actual running mode again according to T1-Ts till
the compressor stops..
7.2.4.3 Fan mode
(1) Compressor stops.
(2) Temperature setting function is disabled.
(T1-Ts)
℉
2
-2
Operation conditon
compressor off
compressor on