28 | S e r v i c e M a n u a l
TRUBLESHOOTING
11.1.2 Unit failure code for unit power supply is 380-415V
Suitable for units: capacity 36000~60000BTU, power supply 380-415V 3N
50Hz
ailure causing
Display mode1
(
indication lamp on display
lamp board
)
Display mode1
(
failure lamp
on control board
)
Display mode3
(
wired
controller
)
Display
priority
Phenomenon
Communication
failure
Flash 5 times
and go out 2S
Flash 2 times
and go out 2S
F1
1
shutdown
Wired controller communication
failure
-
-
E5
1
shutdown
Drainage system
failure
Flash 4 times
and go out 2S
-
E4
3
shutdown
Outdoor protection( Phase
failure )
Flash6 times and go out 2S
-
E6
2
shutdown
Outdoor protection
(discharging
over-temperature )
Flash 10 times and go out 2S
Flash 10 times and go out 2S
EA
7
shutdown
High pressure
protection
Flash 9 times
and go out 2S
Flash 1 times
and go out 2S
E9
6
shutdown
Low pressure
protection
Flash 9 times
and go out 2S
Flash 3 times
and go out 2S
E9
6
shutdown
Indoor temp. sensor
abnormal(TA)
Flash 1 times
and go out 2S
-
E1
4
shutdown
Indoor coil sensor
abnormal(TE)
Flash 3 times
and go out 2S
-
E3
5
shutdown
Outdoor coil sensor
abnormal(TW )
Flash 2 times
and go out 2S
Flash 2 times
and go out 2S
E2
8
non-stop
Outdoor condensate temp.
Sensor
abnormal(TL)
Flash 7 times and
go out 2S
Flash 7 times and go out 2S
E7
9
non-stop
Discharging temp. sensor
abnormal(TP)
Flash 8 times and
go out 2S
Flash 8 times and go out 2S
E8
10
non-stop
Refrigerant shortage
Flash 11 times
and go out 2S
Flash 11 times
and go out 2S
E0
11
shutdown
Note:
When correct signal has not been received by wired control or main control board in 2 consecutive min, then the unit turns off
and indicates relative failure code, once communication renew and failure code disappears automatically.
Содержание AWSI YIFA060-H13
Страница 7: ...6 S e r v i c e M a n u a l OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 FAF 060 N11 4 2 YIFA 060 H13 ...
Страница 17: ...16 S e r v i c e M a n u a l 9 TUBING CONNECTIONS TUBING CONNECTIONS ...
Страница 31: ...30 S e r v i c e M a n u a l TRUBLESHOOTING Communication failure between indoor and outdoor unit ...
Страница 32: ...31 S e r v i c e M a n u a l TRUBLESHOOTING Drainage system failure ...
Страница 33: ...32 S e r v i c e M a n u a l TRUBLESHOOTING Outdoor protection phase sequence ...
Страница 34: ...33 S e r v i c e M a n u a l TRUBLESHOOTING Cooling high pressure protection ...
Страница 35: ...34 S e r v i c e M a n u a l TRUBLESHOOTING Heating high pressure protection ...
Страница 36: ...35 S e r v i c e M a n u a l TRUBLESHOOTING Cooling low pressure protection ...
Страница 37: ...36 S e r v i c e M a n u a l TRUBLESHOOTING Heating low pressure protection ...
Страница 38: ...37 S e r v i c e M a n u a l TRUBLESHOOTING Cooling exhaust temperature protection ...
Страница 39: ...38 S e r v i c e M a n u a l TRUBLESHOOTING Heating exhaust temperature protection ...
Страница 40: ...39 S e r v i c e M a n u a l TRUBLESHOOTING Refrigerant shortage or four way valve failure protection ...
Страница 41: ...40 S e r v i c e M a n u a l TRUBLESHOOTING Sensor failure protection ...
Страница 43: ...42 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 2 Air conditioner operates but effect is terrible ...
Страница 44: ...43 S e r v i c e M a n u a l TRUBLESHOOTING ...
Страница 45: ...44 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 3 Abnormal sound or vibration ...
Страница 46: ...45 S e r v i c e M a n u a l TRUBLESHOOTING ...
Страница 47: ...46 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 4 Abnormal odor ...
Страница 48: ...47 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 5 Air switch action when air conditioner starting up ...
Страница 57: ......