24 | S e r v i c e M a n u a l
CONTROL SYSTEM
After the defrosting is finished, outdoor fan will start, 10 s later the compressor will stop, and 15 s later four ways valve will open, 5
more seconds later the compressor will start, the unit returns to normal heating operation, and indoor fan runs as anti-cold wind
mode
c)
Defrosting entering temperature and heating internal time will auto-adjusted by outdoor defrosting time
d)
Defrosting time sequence drawing
Intelligent defrosting function(only in the case of outdoor coil is damaged this function is carried out)
Entering conditions
On the condition of running intelligent defrosting operation, one of following 7 conditions is satisfied (As
for secondary condition
in upper condition, it is only valid that all secondary condition be satisfied at the same time)
a) Condition No.1
①
The outdoor fan enters into over-load protection and stops running.
②
Outdoor fan stops running then restarts and keeps running over 10 min
③
The compressor accumulating running time ≥45min
④
The compressor continuous running time ≥20min
⑤
TE ≤ 48
℃
。
b) Condition No.2
①
Enter into heating mode 5 min later or finish defrosting 5 min later, catch the max difference value between TE and TA
If
TE≥38
℃
,
when the difference between TE and TA decrease by 5
℃
or more and lasting time ≥3min
If the difference between TE and TA decrease by 3
℃
or more and lasting time ≥3min
②
The compressor continuous running time ≥5min
③
The compressor accumulating running
time ≥45min
④
TE ≤ 48
℃
;
Note:
If there is wind modification, and when indoor fan wind speed descends 1 grade, temperature modification
Содержание AWSI YIFA060-H13
Страница 7: ...6 S e r v i c e M a n u a l OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 FAF 060 N11 4 2 YIFA 060 H13 ...
Страница 17: ...16 S e r v i c e M a n u a l 9 TUBING CONNECTIONS TUBING CONNECTIONS ...
Страница 31: ...30 S e r v i c e M a n u a l TRUBLESHOOTING Communication failure between indoor and outdoor unit ...
Страница 32: ...31 S e r v i c e M a n u a l TRUBLESHOOTING Drainage system failure ...
Страница 33: ...32 S e r v i c e M a n u a l TRUBLESHOOTING Outdoor protection phase sequence ...
Страница 34: ...33 S e r v i c e M a n u a l TRUBLESHOOTING Cooling high pressure protection ...
Страница 35: ...34 S e r v i c e M a n u a l TRUBLESHOOTING Heating high pressure protection ...
Страница 36: ...35 S e r v i c e M a n u a l TRUBLESHOOTING Cooling low pressure protection ...
Страница 37: ...36 S e r v i c e M a n u a l TRUBLESHOOTING Heating low pressure protection ...
Страница 38: ...37 S e r v i c e M a n u a l TRUBLESHOOTING Cooling exhaust temperature protection ...
Страница 39: ...38 S e r v i c e M a n u a l TRUBLESHOOTING Heating exhaust temperature protection ...
Страница 40: ...39 S e r v i c e M a n u a l TRUBLESHOOTING Refrigerant shortage or four way valve failure protection ...
Страница 41: ...40 S e r v i c e M a n u a l TRUBLESHOOTING Sensor failure protection ...
Страница 43: ...42 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 2 Air conditioner operates but effect is terrible ...
Страница 44: ...43 S e r v i c e M a n u a l TRUBLESHOOTING ...
Страница 45: ...44 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 3 Abnormal sound or vibration ...
Страница 46: ...45 S e r v i c e M a n u a l TRUBLESHOOTING ...
Страница 47: ...46 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 4 Abnormal odor ...
Страница 48: ...47 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 5 Air switch action when air conditioner starting up ...
Страница 57: ......