15
Electrical Wiring
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set capabilities of master and slave indoor units as well as indoor unit; SW03
is used to set indoor unit address (combine original communication address and address of
centralized controller); SW08 is used set room card and 26°C lock.
(A) Definition and description of SW01
Note 1: A wired controller can connected to at most eight ultrathin air-duct indoor units.
SW01_1
Operatlon
mode
displayed
on wired
controller
1
[air supply] [refrigerating] [dehumidification]
0
[automatic] [air supply] [refrigerating] [dehumidification] [heating]
SW01_2
SW01_3
SW01_4
Address
of wire
controlled
indoor unit
(Note 1)
[2]
[3]
[4] Address of wire controlled indoor unit (group address)
0
0
0
0# (wire controlled master unit) (default)
0
0
1
1# (wire controlled slave unit)
0
1
0
2# (wire controlled slave unit)
0
1
1
3# (wire controlled slave unit)
1
0
0
4# (wire controlled slave unit)
1
0
1
5# (wire controlled slave unit)
1
1
0
6# (wire controlled slave unit)
1
1
1
7# (wire controlled slave unit)
SW01_5
SW01_6
SW01_7
SW01_8
Capability of
indoor unit
[5]
[6]
[7]
[8]
Capability of indoor unit
0
0
0
0
0.6HP
0
0
0
1
0.8HP
0
0
1
0
1.0HP
0
0
1
1
1.2HP
0
1
0
0
1.5HP
0
1
0
1
1.7HP
0
1
1
0
2.0HP
0
1
1
1
2.5HP
1
0
0
0
3.0HP
1
0
0
1
3.2HP
1
0
1
0
4.0HP
1
0
1
1
5.0HP
1
1
0
0
6.0HP
1
1
0
1
8.0HP
1
1
1
0
10.0HP
1
1
1
1
15.0HP
Dipswitch Setting
•The dipswitch is dialed to "ON" position with the overline at the state of strapping if the code
or overline status is “1” The dipswitch is dialed to "OFF"position with the overline at the state
of disconnection if the code or overline status is "0"
• In the table below, the choice in the box " " refers to the setting of the socket/overline before
delivery.