Ventilation Options
Blank Off Plate
The blank-off plate prevents outside air from entering the building.
All capacity and efficiency ratings are based on installation of the blank off
plate. This is recommended for maximum energy efficiency.
Commercial Room Ventilator (CRV)
The power open, spring close, type fresh air damper allows outside fresh air to enter the building. The
adjustable actuator allows varying amounts of outside air to enter the building.
There are (5) blade positions to adjust the airflow allowed into the building:
Table 3: CRV Air Flow Data
Energy Recovery Ventilator (ERV)
The energy recovery ventilator harvests energy contained in the exhaust air by mixing it with fresh air
across a stationary cubic heat exchanger. The filter medium is designed to be pulled out for easy
cleaning and replacement.
Table 4: ERV Characteristics
Fresh Air Flow (CFM)
Damper Position
CV36
CV60
1
550
600
.8
450
550
.6
300
400
.4
180
250
ERV characteristics
Dial Position
CFM
Efficiency
6
450
54%
5
400
58%
4
350
62%
3
250
66%
2
220
70%
Figure 3: Blank Off Plate
Figure 4: Fresh Air Damper
Figure 5: Energy Recovery Ventilator