Physical Installation
Select the Wall for Installing the Unit
Select the wall where the unit will be installed. Be certain that the wall can support the weight of the
unit and that sufficient space is available for easy operation and installation, both inside and outside
the mounting location. Refer to Table 11 below for unit dimensions and weights by model number.
Refer to Table 10 for weights of ventilation options.
Table 9: Unit Dimensions and Weight
Model
CV36H2A
CV60H3A
Width
in
45.67
45.67
Depth
in
27.56
27.56
Height
in
85.83
92.91
Weight
lbs
730
830
Table 10: Ventilation Option Weight
Accessory
Blank Off Plate
Fresh Air Damper
Economizer
ERV
Weight (lbs)
10
40
40
50
Clearances
•
48” (1200mm) free space in front of the unit
•
40” (1000mm) free space at the side of the unit
Important:
1.
The wall selected for the unit must be strong enough to support both the static weight of the
unit and the vibration of a unit under operation.
2.
For any unit equipped with electrical heat, the supply grille should be at least three inches
away from combustible material.
NOTE:
To assist in the installation process, the following figures provide the unit dimensions to a
tolerance of ± 1/16” (2 mm).