Airstream EXPERT 2V3SA Скачать руководство пользователя страница 58

Mounting instructions    7

N

Night settings

see Day / night

O

Outputs

Output status LEDs    8

Outside temperature

Current outside T°    51

Outside temperature compensation

Operation & settings    25

Outside T° history    51

Override

see Low T° Override

P

Parameter (adjustment)    8
Password  15
Probe

Connection  7

Extension  7

Probes

Activating temperature probes    11

Individual probe readings    51

Probe assignment

0-10V output probes    30,  36,  37

Assigning probes for the avg. room T°    11

Assigning probes for zoned heaters    13

Probe history

see History

Static pressure probe

see Static pressure

Program version    15

R

Ramping

see Curves

Relative humidity (RH)

Activating the relative humidity sensor    11

RH compensation

Activation  11

Operation & settings    33

Room temperature

see Temperature

S

Seasons

Outside T° compensation    25

Seasonal parameter settings    25

Seasonal T° references    12

Security

Security options in case of low temperature

Activation & settings    14

Principle of operation    21,  39

Set points

Mist shutoff set point    31

Night set point

Activating the night set point    14

Set point curve

see Curves

Static pressure set points    45

Temperature set point    18

Soaking

Activation  13

Operation & settings    32

Static pressure (SP)

Activating the SP sensor    12

Current SP level    52

SP compensation

Activating SP compensation    12

Operation & settings    44

SP History    45

SP set points    45

Summer

see Seasons

Symbols

Symbols of the manual    4

T

Technical specifications    53
Temperature

Critical temperature    48

Low temperature override

Activation & settings    14

Principle of operation    21,  39

Outside temperature

Activating outside T° sensor    12

Outside T° compensation    12

Outside temperature compensation

Operation & settings    25–26

58

EXPERT 2V3SA, rev.10

EXPERT 2V3SA

2. 

MOUNTING INSTRUC-

TIONS

2.1. 

Installing the Controller on 

the Wall

Open the latch and lift the cover. Remove 

the black caps located on each of the four 

mounting holes. Mount the enclosure on 

the wall using four screws. Be sure the 

electrical knockouts are at the bottom of 

the enclosure in order to prevent water from 

entering the controller. Insert the screws in 

the mounting holes and tighten. Fasten the 

four black caps provided with the controller 

onto the four mounting holes. The enclosure 

must be mounted in a location that will allow 

the cover to be completely opened right up 

against the wall.

2.2. 

Connections

Refer to the wiring diagram enclosed with this 

user’s manual to connect the controller.  Drill 

holes at the bottom of the enclosure to pass 

the wires and install watertight connectors to 

prevent water from entering in the enclosure. 

Do not make any holes at the side and top 

of the enclosure.

All wiring must be done by an au-

thorized electrician and must comply 

with applicable codes, laws and 

regulations. Make sure power is off 

before doing any wiring to avoid 

electrical shocks and equipment 

damage.

Note that the input terminal blocks 

can be removed from the electronic 

board. This makes it easier to make 

the connections.

2.2.1.  Sensor Inputs

Sensors operate at low voltage and are isolated 

from the supply. Make sure that sensor cables 

remain isolated from all high voltage sources.  

In particular, do not route the sensor cables 

through the same electrical knockout as other 

cables. Do not connect the shield from the 

sensor cable to a terminal or a ground.

Extending a sensor:

 Each sensor can be ex-

tended up to 500 feet (150 meters). 

To extend a sensor: Use a shielded cable 

of outside diameter between 0.245 and 

0.260 in (6.22 and 6.60 mm) (the cable 

dimensions should not be under 18 AWG) to 

ensure the cable entry is liquid tight. 

Do not 

ground the shielding.

It is preferable to solder the cable joint to 

ensure a proper contact between the two 

cables.

Do not run sensor cables next to other 

power cables. When crossing over 

other cables, cross at 90°.

Defective sensors:

 

An alarm is gener-

ated when a defective 

sensor is detected. 

To identify the defective probe, select the 

PROBE TEMPERATURE or OUTSIDE TEM-

PERATURE menu. Probe readings are then 

displayed. Dashes are displayed instead of a 

reading when the probe is defective. In the 

case of room temperature probes, the control-

ler will operate according to the temperature 

of the remaining probes.

2.2.2.  Alarm Connection

There are two types of alarms on the  market. 

One type activates when current is cut off at 

its input, whereas the other activates when 

current is supplied at its input. For an alarm of 

the first type, use the NC terminal as shown on 

the wiring diagram. For an alarm of the second 

type, use the NO terminal.

1: 74.2  2:-----
3: 72.3  4:73.0

7

EXPERT 2V3SA, rev. 10

EXPERT 2V3SA

Содержание EXPERT 2V3SA

Страница 1: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Страница 2: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 3: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 4: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 5: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 6: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 7: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 8: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 9: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 10: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 11: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 12: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 13: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 14: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 15: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 16: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 17: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 18: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 19: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 20: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 21: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 22: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 23: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 24: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 25: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 26: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 27: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 28: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 29: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 30: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 31: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 32: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 33: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 34: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 35: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 36: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 37: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 38: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 39: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 40: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 41: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 42: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 43: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 44: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 45: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 46: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 47: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 48: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 49: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 50: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 51: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 52: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 53: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 54: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 55: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 56: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 57: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 58: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 59: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 60: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 61: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 62: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 63: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 64: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Отзывы: