TECHNICAL SPECIFICATIONS

Supply:  ......................115/230 VAC (-18%, +8%), 50/ 60Hz, overload and overvoltage protec-

tion fuse F1-1A fast blow.

Alarm:  .......................ON-OFF output, 30VDC, 24VAC.
Temperature Probes ......Low voltage ( < 5V), isolated from the supply. Operating range:  -40.0° to 

120.0°F (-40.0° to 48.9°C). Accuracy: 1.8°F (1°C) between 41° and 
95°F (5° and 35°C).

Rel. Humidity Input:  ......4 to 20mA current loop
Static Pressure Input:  ....4 to 20mA current loop
Water Meter Input:  .......Input pulse width > 12ms.
0-10V Output: .............30mA max
Stage 1:   ....................Variable output, 50/60Hz, 115VAC 1/2HP (373W), 230VAC 1.5HP 

(1120W), 10 Amp Max. Fuse F2-15A slow blow.

Stage 2:  ....................Variable output, 50/60Hz, 115VAC 1/2HP (373W), 230VAC 1.5HP 

(1120W), 10 Amp Max. Fuse F3-15A slow blow.

Stage 3:   .....................ON/OFF output, 50/60Hz, 115VAC 1/4HP (187W), 230VAC 1/2HP (373W), 

10 A Res. Max, 30VDC 5A Ind. Heating or cooling. Fuse F6-15A slow blow.

Stage 4:  ......................ON/OFF output, 50/60Hz, 115VAC 1/4HP (187W), 230VAC 1/2HP (373W), 

10 A Res. Max, 30VDC 5A Ind. Heating or cooling. Fuse F5-15A slow blow.

Actuator (winch):  ......... Open/Close output, 50/60Hz, 115VAC (0.17HP 124W), 230VAC (0.5HP 

373W), 30 VDC 5A Ind. Fuse F4-5A slow blow.

Enclosure:   .................ABS, moisture and dust-tight.

The room temperature where the controller is located must always remain between 32° and 

104°F (0 and 40°C). For indoor use only !

52

EXPERT 2V3SA, rev.10

EXPERT 2V3SA

Output Mode (0-10V or 10-0V) —

 Select 

the type of signal used by the 0-10V out-
put (0-10V or 10-0V). *

This parameter is 

accessible if  the 0-10V output is enabled above.

0-10V Mode
           0-10V

Use Soaking —

 Select “Yes” to enable the 

soaking function.

Use Soaking ?
             Yes

Use Mist —

 Select "Yes" to enable the 

mist function. 

Use Inlet —

 Select “Yes” to enable the 

air inlet.

Use Overopening —

 A supplementary 

stage can be defined in order to continue 
opening air inlet beyond the activation 
temperature of the last ventilation stage. 
This over-opening stage is used to direct 
the airflow more efficiently during periods 
of warm weather. Select “Yes” to enable 
the inlet over-opening function or select 
“No” to disable it. *

This parameter is acces-

sible if an air inlet is enable above.

Use Overopening  
             Yes

Move in 1 Step —

 The air inlet can either 

reach its over-opening position instan-
taneously when the room temperature 
reaches a certain point or it can reach its 
over-opening position gradually as the 
room temperature departs from the start 
temperature of the last fan stage. Select 
“Yes” to use the instant opening mode 
or select “No” to use the progressive 
opening mode. Note that either case, the 
inlet reaches its full over-opening position 
at: On T° of the last fan stage + Over-
Opening bandwidth (see chapter 11). *

This 

parameter is accessible if the over-opening func-

tion is enabled above.

Move in 1 step?
             No

Use a timer on heating stages —

 Select 

"Yes" for heater to run in timer mode as 
a function of the room temperature. *

This 

parameter is accessible if at least one heating 

stage is enabled above.

Use heaters on 
timer ?       No

Zoned or standard heaters —

 Zoned 

heating allows heating stages to operate 
according to specific  temperature sen-
sors instead of using the average room 
temperature as a reference. *

This parameter 

is accessible if two heating stages are enabled 

above.

Use  Zoned  heater?                           
              No

Heater 1-2 probes —

 Select which probes 

are used to control each heating stage. 
Blinking digits represent probes that are 
assigned for this purpose. At least one 
temperature probe must be selected. Press 
MODIFY then set each probe's status with 
the arrow keys. *

This parameter is accessible 

if  zoned heaters are enabled above. 

Heater 1 probes
1234

Heater 2 probes
1234

Merge between stages 1 and 2 —

 Select 

"Yes" if  to enable the merge  between fan 
stages 1&2 (see “Merging Fan Stages” on 
page 26).

Use merge for
stages 1-2    No

Merge between stages 2 and 3 —

 Select 

"Yes" to enable the merge between fan 
stages 2 and 3 (see “Merging Fan Stages” 
on page 26). *

This parameter is accessible 

if stage 3 is used as a fan stage (refer to the stage 

combination table in section  4.4).

Use merge for
stages 2-3    No

13

EXPERT 2V3SA, rev. 10

EXPERT 2V3SA

Содержание EXPERT 2V3SA

Страница 1: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Страница 2: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 3: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 4: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 5: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 6: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 7: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 8: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 9: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 10: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 11: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 12: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 13: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 14: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 15: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 16: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 17: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 18: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 19: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 20: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 21: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 22: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 23: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 24: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 25: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 26: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 27: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 28: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 29: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 30: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 31: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 32: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 33: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 34: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 35: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 36: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 37: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 38: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 39: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 40: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 41: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 42: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 43: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 44: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 45: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 46: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 47: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 48: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 49: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 50: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 51: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 52: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 53: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 54: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 55: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 56: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 57: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 58: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 59: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 60: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 61: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 62: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 63: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 64: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Отзывы: