Airstream EXPERT 2V3SA Скачать руководство пользователя страница 1

M 890-00069   rev.10

REV.08

CLEAN MODE

HUMIDITY

OUTSIDE TEMPERATURE

STATIC PRESSURE

LOW TEMPERATURE OVERRIDE

DE-ICING - STAGE 2

TEMPERATURE CURVE

MINIMUM SPEED CURVE

0-10V CURVE

DEFECTIVE PROBE

TEMPERATURE ALARM

WATER ALARM

OPEN

CLOSE

MANUAL MODE

RESET

MIST / SOAK

5
4
3
2
1
1
2

HEAT MAT

ROOM TEMPERATURE
PROBE TEMPERATURE
OUTSIDE TEMPERATURE
RELATIVE HUMIDITY
STATIC PRESSURE
TIME / DATE

SET POINT / CURVE
MINIMUM SPEED / CURVE

STAGE 1
STAGE 2
STAGES 3-5
MIST / SOAK
HEATERS
INLET
0-10V OUTPUT / CURVE
ALARMS
ALARMS
WATER HISTORY
LAST 48-HOUR WATER
HEATER RUN TIME
CLEAN MODE
USER
TEST

CURRENT CONDITIONS

SETTINGS

MONITORING

SETUP

COMPENSATION

STATUS

ALARMS

0-10V OUTPUT
INLET

FAN STAGES

HEATERS

 

EXPERT 2V3SA 

Temperature Controller

User’s manual

Содержание EXPERT 2V3SA

Страница 1: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Страница 2: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 3: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 4: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 5: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 6: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 7: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 8: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 9: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 10: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 11: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 12: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 13: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 14: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 15: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 16: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 17: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 18: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 19: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 20: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 21: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 22: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 23: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 24: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 25: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 26: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 27: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 28: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 29: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 30: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 31: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 32: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 33: ...must be added to the regular minimum ventilation speed when the humidity level exceeds the set point by more than 10 32 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 HEATERS 10 1 Regular Heating Stages Stages a...

Страница 34: ...sity when the temperature falls below its start temperature It then increases in intensity as the temperature decreases and reaches its maximum intensity when the temperature gets lower than the Max...

Страница 35: ...idity sensor is enabled in the User Setup Menu 30 EXPERT 2V3SA rev 10 EXPERT 2V3SA Settings 1 From the main menu select the option 0 10V OUTPUT CURVE Make sure the function of the se lected 0 10V outp...

Страница 36: ...the animal age over which the 0 10V heating output must stop being used See Setting the Day Number on page 10 to view modify the current day number Probes The 0 10V heating output oper ates according...

Страница 37: ...he start temperature 28 EXPERT 2V3SA rev 10 EXPERT 2V3SA 10 7 0 10V Heating Curve The controller can automatically change the temperature at which the 0 10V heater or heat mat starts over time by usin...

Страница 38: ...ng opt 38 EXPERT 2V3SA rev 10 EXPERT 2V3SA 6 4 3 Nbr of Degrees to 100 of Stage 3 1 From the main menu select STAGES 3 2 Use the navigation keys to select this parameter Degrees to 100 2 0 F This para...

Страница 39: ...e of air inlet you want to adjust INLET 0 10V OUTPUT CURVE If you are selecting a 0 10V output make sure the function of this out put is set to Chimney in the User Setup Menu before adjusting the para...

Страница 40: ...he inlet totally closes Once the actuator s position is reset the inlet returns to its previous position 2 Reset toward the nearest position Open Close mode If the current inlet position is higher tha...

Страница 41: ...a summer bandwidth Normally the winter s bandwidth should be greater than the summer s bandwidth of Degrees to Full Speed as a Function of Outside Temperature Outside T Winter T Summer T Winter Setti...

Страница 42: ...parameters The parameter adjustment process is explained in section 3 2 on page 8 Start T Set the start temperature of the selected fan stage Stop T Set the stop temperature of the selected fan stage...

Страница 43: ...the Lo Pressure Set Point the controller waits for the Compensation to make sure this unusual pressure condition is not temporary If the pressure is still out of range after this delay has elapsed the...

Страница 44: ...s is explained in section 3 2 on page 8 Curve status Off 1 day 1 Min Spd 30 1 day 5 Min Spd 45 10 day 40 Min Spd 100 Curve status Select Yes to enable the curve or No to disable it Once the curve is o...

Страница 45: ...n an abnormal situation occurs Each triggered alarm is logged in a history menu and must be acknowledged by the user The alarm conditions are as follows Defective temperature probe Defective outdoor p...

Страница 46: ...how much more water has been consumed and will convert this value in percent If the surplus in is higher than the High Alarm limit the controller will set off an alarm Last 24h Previous 24h x 100 Hi...

Страница 47: ...above which a temperature alarm must be triggered The low limit can be adjusted from 40 F to 0 5 F 22 2 to 0 3 C below the set point and the high limit from 0 5 F to 40 F 0 3 to 22 2 C above the set p...

Страница 48: ...t Point Settings 1 From the main menu select SET POINT CURVE 2 Set the following parameters The parameter adjustment process is explained in section 3 2 on page 8 Setp 75 0 F ClnSetp 45 0 F Night Setp...

Страница 49: ...tivity 1 From the main menu select TEST 2 Use the navigation keys to select the fol lowing parameters Test Mode Off Room T bypass 78 0 F 3 Set the following parameters The parameter adjustment process...

Страница 50: ...SA rev 10 EXPERT 2V3SA Display T Inlet Change Password The user can define a password to restrict access to certain functions USER SETUP and TEST MODE The password must be entered each time one of the...

Страница 51: ...ure is enabled above Min spd 15 Inlet 0 Set point curve Select Yes to enable the set point curve function Set point curve Yes Min speed curve Select Yes to enable the minimum speed curve function Min...

Страница 52: ...t Yes to enable the inlet over opening function or select No to disable it This parameter is acces sible if an air inlet is enable above Use Overopening Yes Move in 1 Step The air inlet can either rea...

Страница 53: ...CARD The memory card is used to create a backup copy of your controller s configuration The card is also useful to transfer the configura tion of one controller to another controller of the same type...

Страница 54: ...time format AM PM or 24 hour Time format AM PM Temperature Units Select the tempera ture units Fahrenheit F or Celsius C degrees Temp units F of Temperature Sensors in the Room Set the number of temp...

Страница 55: ...er adjustment process is explained in section 3 2 on page 8 Motor Curve Set the motor curve of the selected fan stage to the desired value 10 EXPERT 2V3SA rev 10 EXPERT 2V3SA User Setup Menu Contrast...

Страница 56: ...3SA LED MEANING Clean Mode Solid LED Clean mode is active Humidity Compensation Solid LED A RH compensation function is ON Outside Temp Compensation Solid LED The outside temperature compensation is O...

Страница 57: ...SSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INLET 0 10V OUTPUT CURVE ALARMS ALARMS WATER HISTORY LAST 48 HOUR WATER HEATER RUN TIME CLEAN MODE USER...

Страница 58: ...ounting holes The enclosure must be mounted in a location that will allow the cover to be completely opened right up against the wall 2 2 Connections Refer to the wiring diagram enclosed with this use...

Страница 59: ...us making it possible to centralize the management of information and diversify control strategies Test Mode A test mode allows you to simulate temperature changes and verify controller s performance...

Страница 60: ...temperature curve and a minimum ventilation cycle curve with up to ten different points each Choice of Ten Motor Types The variation in motor speed resulting from a change in voltage will depend on th...

Страница 61: ...r on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to prevent power...

Страница 62: ...d of Stages 1 2 25 6 4 Merging Fan Stages 27 6 4 1 Merging Fan Stages 1 2 27 6 4 2 Merging Stages 2 and 3 27 6 4 3 Nbr of Degrees to 100 of Stage 3 28 6 5 De icing Stage 2 Fans 28 6 6 0 10V Fan Output...

Страница 63: ...er not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is however subject to change without not...

Страница 64: ...2 1 1 2 HEAT MAT ROOM TEMPERATURE PROBE TEMPERATURE OUTSIDE TEMPERATURE RELATIVE HUMIDITY STATIC PRESSURE TIME DATE SET POINT CURVE MINIMUM SPEED CURVE STAGE 1 STAGE 2 STAGES 3 5 MIST SOAK HEATERS INL...

Отзывы: