Airstream Cumberland EXPERT LA Скачать руководство пользователя страница 48

48

EXPERT LA   rev.00

EXPERT LA

6.4

Tunnel  Doors

The controller can control the opening of 2 tunnel

doors as a function of the static pressure level or

as a function of the average temperature in the

room. Refer to section 4.5 of this manual to choose

the proper operating mode.

6.4.1

Pressure-based Tunnel Doors

Beginning of tunnel ventilation

The activation of tunnel ventilation is linked with

the activation of a user-defined fan stage: when

the start temperature of that fan stage is reached,

the controller starts controlling tunnel doors accord-

ing to the static pressure level. It opens the doors

when the pressure level exceeds the high pressure

set point and closes them when the pressure level

is lower than the low pressure set point. Refer to

the chapter 5 to set  the static pressure set points.

Minimum outside temperature

A minimum outside temperature can be specified

to avoid entering in tunnel ventilation when it is

too cold outside. This feature is optional and can

only be used if an outside temperature probe is

enabled (sec. 4.7.1).

Minimum age

A minimum age can be specified to avoid entering

in tunnel ventilation when the animals are too

young. This feature is optional and can only be used

if age-based functions are enabled in the Installa-

tion Setup (section 4.5).

Pre-opening

The pre-opening delay is used to slightly open tun-

nel doors before the activation of tunnel fans. The

pre-opening is performed at the start-up of tunnel

ventilation (i.e., when the fan stage which activates

tunnel ventilation starts).

Wind effect delay

When the pressure level exceeds the high or low

static pressure set point, tunnel doors wait for the

end of the 

“Wind Effect Delay”  

before moving. Tun-

nel doors will only move if the high or low pressure

condition is still valid after the delay has elapsed.

This way, tunnel doors do not move if a wind draft

causes fleeting changes in the pressure level.

Closing vent doors (inlets) in tunnel ventilation

If vent doors (inlets) remain opened in natural ven-

tilation, you must define the tunnel stage at which

they must close.

LO PRESSURE

SET POINT *

Static 

Pressure

HI PRESSURE

SET POINT *

T

H

E

 T

U

N

N

E

L

 

D

O

O

R

 

O

P

E

N

S

T

H

E

 T

U

N

N

E

L

 

D

O

O

R

  

D

O

E

S

 

N

O

T

 M

O

V

E

WIND

EFFECT

DELAY

WIND

EFFECT

DELAY

T

H

E

 T

U

N

N

E

L

 

D

O

O

R

 

C

L

O

S

E

S

The tunnel door

starts closing after 

the Wind Effect 

Delay has elapsed.

The tunnel 

door stops 

closing

The tunnel 

door stops 

opening

The tunnel door

starts opening 

after the Wind 

Effect Delay 

has elapsed. 

Time

Opening of Tunnel Doors

as a Function of Static Pressure

45

EXPERT LA   rev.00

EXPERT LA

6.3.2

Natural Ventilation Settings

Select:

Main menu

Start/Stop*
Natural**
Curtain #X

*

A password may be required to access this menu (sec. 4.2).

** Accessible if at least 1 natural ventilation curtain is enabled

in the Installation Setup (section 4.5).

Set the following parameters:

(Refer to previous sections to get further informa-
tion on these parameters)

Initial Open at

Set the temperature at which the curtain

opens for the first time. The curtain opens

during its initial moving time at that moment.

Start Close at

Set the temperature below which the cur-

tain starts closing in timer mode when the

controller is in natural ventilation.

Start Open at

Set the temperature above which the cur-

tain opens according to a timer when the

controller is in natural ventilation.

Initial Time

The curtain opens during its initial opening

time when the controller enters in natural ven-

tilation. This opening time can be adjusted

from 0 to 900 seconds (15 minutes).

Open /  Close / Off Time

Set the opening and closing timers of the cur-

tain (the Off time is common to both cycles).

The open, close and off times can be adjusted

from 0 to 900 seconds (15 minutes).

Wind Delay

When the controller is in natu-

ral ventilation and temperature falls below

the "Start Close At" temperature or rises

above the "Start Open At" temperature, the

curtain only starts moving after the wind de-

lay has elapsed. This way, the curtain does

not move when wind drafts cause sudden

temperature changes. Set the wind delay to

the desired value. Adjustable from 0 to 900

seconds (15 minutes).

Tunnel Close Delay

 

(Factory Setting)

This delay is launched at the beginning of

the first tunnel stage. Once it has elapsed,

the controller closes the natural ventilation

curtain.

Continuous Delay

  

(Factory Setting)

The natural ventilation curtain opens during

this delay when the controller returns in natu-

ral ventilation (when tunnel ventilation ends).

Purge move time

This is the amount of time required to open

the curtain during a purge cycle (see sec.

6.3.5). Set this parameter separately for

each curtain.

Accessible if the purge option is enabled in the
Installation Setup (section 4.5).

Main menu

      Start/Stop

  Natural

  Curtain 1

Natural Curtain 1 Settings

Use   to navigate

Initial Open at

80.0 °F

Start Close at

78.0 °F

Start Open at

82.0 °F

Initial Time

20 sec

Open Time

15 sec

Close Time

15 sec

Off Time

15 sec

Wind Delay

10 sec

Tun.Close Dly

300 sec

Continuous Open

300 sec

Purge Move Time

30 sec

Содержание Cumberland EXPERT LA

Страница 1: ...m CleanMode Light Open Close Open Close Open Close Open Close Open Close Open Close 12 11 10 9 8 7 6 5 4 3 2 1 Min Vent 1 2 3 4 Misting Cool cell 0 10V Clock 1 Clock 2 Tunnel 2 Tunnel 1 Curtain 2 Curt...

Страница 2: ...00 EXPERT LA NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to furthe...

Страница 3: ...g 13 4 INSTALLATION SETUP 14 4 1 Setting the Time Date 14 4 2 Password 14 4 2 1 Entering Changing the Password 15 4 2 2 Retreiving a Lost Password 15 4 3 Controller Programs 16 4 3 1 Program Selection...

Страница 4: ...4 0 10V Ventilation Outputs 43 6 3 Natural Ventilation Curtains 44 6 3 1 Principle of Operation 44 6 3 2 Natural Ventilation Settings 45 6 3 3 Curtain Compensation 46 6 3 4 Stopping Fans in Natural Ve...

Страница 5: ...ctivation 19 20 Principle of operation 48 Probe set 2 50 Settings 50 Static pressure limits 33 Tunnel doors temperature based Activation 19 20 Principle of operation 48 49 Probe set 2 50 Settings 50 U...

Страница 6: ...story 73 Posting of marketed animals 74 Measuring units 18 Memory card Erasing the card 79 Transfer process 77 Menu selectors 11 Minimum ventilation Activation 37 Principle of operation 37 Relay assig...

Страница 7: ...display Location 11 Unit selection 22 E Electrical specifications 76 English software 12 Evaporative pads see Cool cells F Fahrenheit units 18 Fan stages Activation 19 Current fan stage in use 72 Min...

Страница 8: ...side temperature sensor 75 days Inside humidity sensor 75 days Outside humidity sensor 75 days Static pressure sensor 75 days Run time of each heater 75 days Run time of each feeder 75 days Daily wate...

Страница 9: ...i Fire Heater 4 Heater 3 Hi Fire Heater 3 Heater 2 Hi Fire Heater 2 Heater 1 Hi Fire Heater 1 Room T Probe set 2 0 10V 1 Natural curtain 1 Natural curtain 2 PROBES 9 EXPERT LA rev 00 EXPERT LA BACKUP...

Страница 10: ...es Do not connect the shield from the sensor cable to a terminal or a ground Extending a sensor Each sensor can be extended up to 500 feet 150 meters To extend a sensor use a shielded cable of outside...

Страница 11: ...ors Use these buttons to select a menu Main menu short cut key This short cut key provides access to the main menu and allows seeing the current sta tus of each input and output on the main screen The...

Страница 12: ...be displayed in multiple languages Follow these steps to change the language selection Select Main menu More Otros or Outros English Espa ol or Portugu s The controller automatically changes the lan g...

Страница 13: ...d LED tunnel door 2 is opening Close Solid LED tunnel door 2 is closing Open Solid LED tunnel door 1 is opening Close Solid LED tunnel door 1 is closing Open Solid LED natural ventilation curtain 2 is...

Страница 14: ...ersion is available you can install it in your controller by downloading a firmware file fir from the card Upgrading the firmware will not affect your parameter settings Access the transfer menu as ex...

Страница 15: ...guration files are a set of instructions that tells the controller what to do These files are di vided into two parts 1 Software screen menus 2 User data parameter settings You can save your controlle...

Страница 16: ...and 3 start if the switch is based on the outside temperature select the outside tem perature above which each program starts Note that program 1 is automatically used when the animal age or outside t...

Страница 17: ...s message is shown when the program selection is made manually i e it is not se lected as a function of the day and or out side temperature Select the running pro gram Only programs that are enabled i...

Страница 18: ...ency at which this servicing activity must be performed In all the controller can display 3 different warning messages When a warning message is active the word Warning is displayed on screen along wi...

Страница 19: ...ality 0 Total Mortality 0 New Culled 0 Today s Culled 0 Total Culled 0 New Marketed 0 Today s Marketed 0 Total Marketed 0 19 EXPERT LA rev 00 EXPERT LA 4 5 Installation Setup The following section sho...

Страница 20: ...led above This parameter is common to all programs Curtain compensation Select Yes to enable a compensation on the opening of natural ventilation curtains as a function of the outside temperature Acce...

Страница 21: ...r continuously Select Yes to enable this function Misting The controller can control one misting out put Select Yes to enable this output Misting output follows the set point Operating temperatures of...

Страница 22: ...4 7 1 Water spill limit Specify the maximum amount of water that can be consumed by each water meter per 15 min utes 0 10 000 gal or liters 15 min Accessible if a water meter is enabled sec 4 7 1 Stat...

Страница 23: ...per 15 minutes Thealarmisactivatedifagreater amount of water is consumed within the 15 minute delay Static Pressure Alarms The controller can sound an alarm when the static pressure SP level exceeds...

Страница 24: ...Use to navigate Logged at Jan 01 200X 12 00 A Temperature High F Probe 5 Defective Probe 4 Defective 11 ALARMS When an alarm occurs the controller lights up the alarm pilot light displays letters AL o...

Страница 25: ...above which the misting output and or the cool cell output stops or select Off to disable this function Accessible if the mist shutoff compensation and or cool cell shutoff option is enabled in sec 4...

Страница 26: ...4 Heaters 1 4 Hi fire opt 0 10V output Natural ventilation curtain 1 2 A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are dis played sec 4 5 Ass...

Страница 27: ...signment Select the desired output A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are avail able sec 4 5 Select a relay then set its status as f...

Страница 28: ...is required to per form a light peak cycle see previous graph The cycle time must be even or longer than the peak duration peak sunrise peak sunset Peak Duration Select during how much time the light...

Страница 29: ...to 60 minutes Number of Cycles Select how many cycles must be performed during the selected light program Adjust able from 1 to 6 cycles Main menu Start Stop Lights Light Settings Program X Use to nav...

Страница 30: ...er is in clean mode Refer to section 11 3 to set the clean mode alarm limit 63 EXPERT LA rev 00 EXPERT LA 8 LIGHTS The controller has one 0 10V output that can be used to control the light intensity A...

Страница 31: ...higher that its On Temperature If the Hi Lo fire option is used set this tem perature separately for both steps of the heating stage Main menu Start Stop Heaters Heaters Start Stop Use to navigate Hea...

Страница 32: ...ean mode Outside set point The controller can adjust the moving speed of natural ventilation curtains as a function of outside temperature When this function is used the controller refers to the outsi...

Страница 33: ...e Set Points The high low static pressure set points are the limits above and below which pressure based air inlets such as vent doors or tunnel doors open or close The controller allows using up to 3...

Страница 34: ...put s start temperature the output stops when tempera ture falls below a user defined value It can also stop when humidity levels are too high see RH Compensation in chapter 10 If the cool cell output...

Страница 35: ...essible if the temperature curve is enabled in the Instal lation setup sec 4 5 A password may also be required to access this menu The following parameters can only be modified while the curve is off...

Страница 36: ...in minimum ventilation The inlet is at its Closed position during the Off Time portion of minimum ventilation cycles it opens to the position associated with stage 1 during the On Time Over opening A...

Страница 37: ...Ventilation Cycles Definition Minimum ventilation cycles are activated when the average room temperature is below the start tem perature of fan stage 1 Running the fans even though ventilation is not...

Страница 38: ...when the static pressure level is lower than the low pressure set point The graph below illustrates this process Refer to chapter 5 to set the static pressure set points Wind Effect Delay When the pre...

Страница 39: ...now Select Yes to re set the actuator s position now Day time Set the time of day at which re sets are performed Period Set the frequency of inlet resets A reset can be performed once every 1 7 days...

Страница 40: ...5 A password may also be required to access this menu section 4 2 Make sure you have selected a timer based vent door inlet Refer to sec tion 4 5 to set vent door inlet func tions Vent door inlet ope...

Страница 41: ...g Vent Doors Inlets Vent doors inlets can either close when the con troller enters in natural ventilation or when the controller reaches a user defined tunnel ventilation stage Refer to the Installati...

Страница 42: ...enabled in the Installation Setup section 4 5 Timer If timer based relays are assigned to some fan stages sec 4 8 set the On Time and the Off Time of each timer based relay These On Off Times can be...

Страница 43: ...ening 45 sec Wind Effect Delay 0 30 m s 43 EXPERT LA rev 00 EXPERT LA 6 2 4 0 10V Ventilation Outputs The controller has a 0 10V output which can ei ther be used to control an air inlet or variable sp...

Страница 44: ...Relation between Fan Stages Natural Ventilation Curtains 49 EXPERT LA rev 00 EXPERT LA 6 4 2 Temperature Based Tunnel Doors Beginning of tunnel ventilation The activation of tunnel ventilation is link...

Страница 45: ...nel door starts opening after the Wind Effect Delay has elapsed Time Opening of Tunnel Doors as a Function of Static Pressure 45 EXPERT LA rev 00 EXPERT LA 6 3 2 Natural Ventilation Settings Select Ma...

Страница 46: ...os ing temperature When this situation occurs a de fective whisker switch alarm is posted to the alarm log Refer to section 4 8 to select what fan relays must turn off in natural ventilation Current o...

Страница 47: ...os ing temperature When this situation occurs a de fective whisker switch alarm is posted to the alarm log Refer to section 4 8 to select what fan relays must turn off in natural ventilation Current o...

Страница 48: ...nel door starts opening after the Wind Effect Delay has elapsed Time Opening of Tunnel Doors as a Function of Static Pressure 45 EXPERT LA rev 00 EXPERT LA 6 3 2 Natural Ventilation Settings Select Ma...

Страница 49: ...Relation between Fan Stages Natural Ventilation Curtains 49 EXPERT LA rev 00 EXPERT LA 6 4 2 Temperature Based Tunnel Doors Beginning of tunnel ventilation The activation of tunnel ventilation is link...

Страница 50: ...ening 45 sec Wind Effect Delay 0 30 m s 43 EXPERT LA rev 00 EXPERT LA 6 2 4 0 10V Ventilation Outputs The controller has a 0 10V output which can ei ther be used to control an air inlet or variable sp...

Страница 51: ...enabled in the Installation Setup section 4 5 Timer If timer based relays are assigned to some fan stages sec 4 8 set the On Time and the Off Time of each timer based relay These On Off Times can be...

Страница 52: ...g Vent Doors Inlets Vent doors inlets can either close when the con troller enters in natural ventilation or when the controller reaches a user defined tunnel ventilation stage Refer to the Installati...

Страница 53: ...5 A password may also be required to access this menu section 4 2 Make sure you have selected a timer based vent door inlet Refer to sec tion 4 5 to set vent door inlet func tions Vent door inlet ope...

Страница 54: ...now Select Yes to re set the actuator s position now Day time Set the time of day at which re sets are performed Period Set the frequency of inlet resets A reset can be performed once every 1 7 days...

Страница 55: ...when the static pressure level is lower than the low pressure set point The graph below illustrates this process Refer to chapter 5 to set the static pressure set points Wind Effect Delay When the pre...

Страница 56: ...Ventilation Cycles Definition Minimum ventilation cycles are activated when the average room temperature is below the start tem perature of fan stage 1 Running the fans even though ventilation is not...

Страница 57: ...in minimum ventilation The inlet is at its Closed position during the Off Time portion of minimum ventilation cycles it opens to the position associated with stage 1 during the On Time Over opening A...

Страница 58: ...essible if the temperature curve is enabled in the Instal lation setup sec 4 5 A password may also be required to access this menu The following parameters can only be modified while the curve is off...

Страница 59: ...put s start temperature the output stops when tempera ture falls below a user defined value It can also stop when humidity levels are too high see RH Compensation in chapter 10 If the cool cell output...

Страница 60: ...e Set Points The high low static pressure set points are the limits above and below which pressure based air inlets such as vent doors or tunnel doors open or close The controller allows using up to 3...

Страница 61: ...ean mode Outside set point The controller can adjust the moving speed of natural ventilation curtains as a function of outside temperature When this function is used the controller refers to the outsi...

Страница 62: ...higher that its On Temperature If the Hi Lo fire option is used set this tem perature separately for both steps of the heating stage Main menu Start Stop Heaters Heaters Start Stop Use to navigate Hea...

Страница 63: ...er is in clean mode Refer to section 11 3 to set the clean mode alarm limit 63 EXPERT LA rev 00 EXPERT LA 8 LIGHTS The controller has one 0 10V output that can be used to control the light intensity A...

Страница 64: ...to 60 minutes Number of Cycles Select how many cycles must be performed during the selected light program Adjust able from 1 to 6 cycles Main menu Start Stop Lights Light Settings Program X Use to nav...

Страница 65: ...is required to per form a light peak cycle see previous graph The cycle time must be even or longer than the peak duration peak sunrise peak sunset Peak Duration Select during how much time the light...

Страница 66: ...signment Select the desired output A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are avail able sec 4 5 Select a relay then set its status as f...

Страница 67: ...4 Heaters 1 4 Hi fire opt 0 10V output Natural ventilation curtain 1 2 A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are dis played sec 4 5 Ass...

Страница 68: ...above which the misting output and or the cool cell output stops or select Off to disable this function Accessible if the mist shutoff compensation and or cool cell shutoff option is enabled in sec 4...

Страница 69: ...Use to navigate Logged at Jan 01 200X 12 00 A Temperature High F Probe 5 Defective Probe 4 Defective 11 ALARMS When an alarm occurs the controller lights up the alarm pilot light displays letters AL o...

Страница 70: ...per 15 minutes Thealarmisactivatedifagreater amount of water is consumed within the 15 minute delay Static Pressure Alarms The controller can sound an alarm when the static pressure SP level exceeds...

Страница 71: ...4 7 1 Water spill limit Specify the maximum amount of water that can be consumed by each water meter per 15 min utes 0 10 000 gal or liters 15 min Accessible if a water meter is enabled sec 4 7 1 Stat...

Страница 72: ...r continuously Select Yes to enable this function Misting The controller can control one misting out put Select Yes to enable this output Misting output follows the set point Operating temperatures of...

Страница 73: ...led above This parameter is common to all programs Curtain compensation Select Yes to enable a compensation on the opening of natural ventilation curtains as a function of the outside temperature Acce...

Страница 74: ...ality 0 Total Mortality 0 New Culled 0 Today s Culled 0 Total Culled 0 New Marketed 0 Today s Marketed 0 Total Marketed 0 19 EXPERT LA rev 00 EXPERT LA 4 5 Installation Setup The following section sho...

Страница 75: ...ency at which this servicing activity must be performed In all the controller can display 3 different warning messages When a warning message is active the word Warning is displayed on screen along wi...

Страница 76: ...s message is shown when the program selection is made manually i e it is not se lected as a function of the day and or out side temperature Select the running pro gram Only programs that are enabled i...

Страница 77: ...and 3 start if the switch is based on the outside temperature select the outside tem perature above which each program starts Note that program 1 is automatically used when the animal age or outside t...

Страница 78: ...guration files are a set of instructions that tells the controller what to do These files are di vided into two parts 1 Software screen menus 2 User data parameter settings You can save your controlle...

Страница 79: ...ersion is available you can install it in your controller by downloading a firmware file fir from the card Upgrading the firmware will not affect your parameter settings Access the transfer menu as ex...

Страница 80: ...d LED tunnel door 2 is opening Close Solid LED tunnel door 2 is closing Open Solid LED tunnel door 1 is opening Close Solid LED tunnel door 1 is closing Open Solid LED natural ventilation curtain 2 is...

Страница 81: ...be displayed in multiple languages Follow these steps to change the language selection Select Main menu More Otros or Outros English Espa ol or Portugu s The controller automatically changes the lan g...

Страница 82: ...ors Use these buttons to select a menu Main menu short cut key This short cut key provides access to the main menu and allows seeing the current sta tus of each input and output on the main screen The...

Страница 83: ...es Do not connect the shield from the sensor cable to a terminal or a ground Extending a sensor Each sensor can be extended up to 500 feet 150 meters To extend a sensor use a shielded cable of outside...

Страница 84: ...i Fire Heater 4 Heater 3 Hi Fire Heater 3 Heater 2 Hi Fire Heater 2 Heater 1 Hi Fire Heater 1 Room T Probe set 2 0 10V 1 Natural curtain 1 Natural curtain 2 PROBES 9 EXPERT LA rev 00 EXPERT LA BACKUP...

Страница 85: ...side temperature sensor 75 days Inside humidity sensor 75 days Outside humidity sensor 75 days Static pressure sensor 75 days Run time of each heater 75 days Run time of each feeder 75 days Daily wate...

Страница 86: ...display Location 11 Unit selection 22 E Electrical specifications 76 English software 12 Evaporative pads see Cool cells F Fahrenheit units 18 Fan stages Activation 19 Current fan stage in use 72 Min...

Страница 87: ...story 73 Posting of marketed animals 74 Measuring units 18 Memory card Erasing the card 79 Transfer process 77 Menu selectors 11 Minimum ventilation Activation 37 Principle of operation 37 Relay assig...

Страница 88: ...ctivation 19 20 Principle of operation 48 Probe set 2 50 Settings 50 Static pressure limits 33 Tunnel doors temperature based Activation 19 20 Principle of operation 48 49 Probe set 2 50 Settings 50 U...

Страница 89: ...4 0 10V Ventilation Outputs 43 6 3 Natural Ventilation Curtains 44 6 3 1 Principle of Operation 44 6 3 2 Natural Ventilation Settings 45 6 3 3 Curtain Compensation 46 6 3 4 Stopping Fans in Natural Ve...

Страница 90: ...g 13 4 INSTALLATION SETUP 14 4 1 Setting the Time Date 14 4 2 Password 14 4 2 1 Entering Changing the Password 15 4 2 2 Retreiving a Lost Password 15 4 3 Controller Programs 16 4 3 1 Program Selection...

Страница 91: ...00 EXPERT LA NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to furthe...

Страница 92: ...m CleanMode Light Open Close Open Close Open Close Open Close Open Close Open Close 12 11 10 9 8 7 6 5 4 3 2 1 Min Vent 1 2 3 4 Misting Cool cell 0 10V Clock 1 Clock 2 Tunnel 2 Tunnel 1 Curtain 2 Curt...

Отзывы: