56

EXPERT LA   rev.00

EXPERT LA

6.5.2.2 Static-Pressure-Based Vent Door (Inlet)

Settings

Select:

Main menu

Vent/Inlet*
Vent door / Inlet 1 is already displayed; press
Vent door / Inlet 2 to display parameter set-

tings of the second inlet.

*

Accessible if at least one vent door (inlet) output enabled in

the Installation Setup (section 4.5). A password may also

be required to access this menu (section 4.2).

Make sure you have selected a static-

pressure-based vent door (inlet). Refer

to section 4.5 to set vent door (inlet)

functions.

Set the following parameters:

(Refer to the previous section to get further infor-
mation on these parameters).

Wind Effect Delay

Select what delay must elapse before mov-

ing the vent door (inlet) when the pressure

level exceeds a pressure set point.

Pre-opening Delay

Set the time that is required to pre-open the

vent door (inlet) before activating minimum

ventilation fans. Adjustable from 0 to 30 sec-

onds.

Main menu

Vent/Inlet

Vent Door/
Inlet 2

Auto Reset

Vent Door /Inlet 1 Settings

Use   to navigate

Wind Effect Delay

0:30 m:s

PreOpening

15 sec

37

EXPERT LA   rev.00

EXPERT LA

Main menu

     Min. Vent.

MinV Relay

Vent Curve

Minimum Ventilation

Use   to navigate

    

Min Vent. Status

   On

Minimum Ventilation Timer

On time

15 sec

Cycle time

120 sec

6.

VENTILATION & COOLING

6.1

Minimum Ventilation

6.1.1

Minimum Ventilation Cycles

Definition

Minimum ventilation cycles are activated when the

average room temperature is below the start tem-

perature of fan stage 1. Running the fans even

though ventilation is not required for reducing the

room temperature is useful to reduce humidity lev-

els and supply oxygen to the room. It also prevents

the fans from freezing in winter.

Minimum ventilation timer

The minimum ventilation timer is composed of an

“On Time” and of a “Cycle Time”. The fans stay on

during the “On Time” then stop until the end of the

cycle. This timer is common to all programs of the

controller.

Minimum ventilation fans

Minimum ventilation is ensured by a user-defined

selection of On/Off fans.  Refer to section 4.8.2 to

select these fans.

Automatic adjustment of the min. ventilation rate

The controller can automatically increase minimum

ventilation rates over time by increasing the “On

Time” portion of minimum ventilation cycles. Re-

fer to section 6.1.3.

Minimum Ventilation Timer

ON

ON TIME

OFF

CYCLE

TIME

6.1.2

Minimum Ventilation Settings

Select:

Main menu

Min. Vent.

Set the following parameters:

Minimum ventilation status

Select “On” to use minimum ventilation

cycles; select “Off” to disable this function.

Minimum ventilation timer

Set the “On Time” and the “Cycle Time” of

the minimum ventilation timer. The “Cycle

Time” must last longer than the “On Time”.

This timer is common to all programs of the

controller.

This parameter can only be modified while the
minimum ventilation curve is inactive (sec. 6.1.4).

Содержание Cumberland EXPERT LA

Страница 1: ...m CleanMode Light Open Close Open Close Open Close Open Close Open Close Open Close 12 11 10 9 8 7 6 5 4 3 2 1 Min Vent 1 2 3 4 Misting Cool cell 0 10V Clock 1 Clock 2 Tunnel 2 Tunnel 1 Curtain 2 Curt...

Страница 2: ...00 EXPERT LA NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to furthe...

Страница 3: ...g 13 4 INSTALLATION SETUP 14 4 1 Setting the Time Date 14 4 2 Password 14 4 2 1 Entering Changing the Password 15 4 2 2 Retreiving a Lost Password 15 4 3 Controller Programs 16 4 3 1 Program Selection...

Страница 4: ...4 0 10V Ventilation Outputs 43 6 3 Natural Ventilation Curtains 44 6 3 1 Principle of Operation 44 6 3 2 Natural Ventilation Settings 45 6 3 3 Curtain Compensation 46 6 3 4 Stopping Fans in Natural Ve...

Страница 5: ...ctivation 19 20 Principle of operation 48 Probe set 2 50 Settings 50 Static pressure limits 33 Tunnel doors temperature based Activation 19 20 Principle of operation 48 49 Probe set 2 50 Settings 50 U...

Страница 6: ...story 73 Posting of marketed animals 74 Measuring units 18 Memory card Erasing the card 79 Transfer process 77 Menu selectors 11 Minimum ventilation Activation 37 Principle of operation 37 Relay assig...

Страница 7: ...display Location 11 Unit selection 22 E Electrical specifications 76 English software 12 Evaporative pads see Cool cells F Fahrenheit units 18 Fan stages Activation 19 Current fan stage in use 72 Min...

Страница 8: ...side temperature sensor 75 days Inside humidity sensor 75 days Outside humidity sensor 75 days Static pressure sensor 75 days Run time of each heater 75 days Run time of each feeder 75 days Daily wate...

Страница 9: ...i Fire Heater 4 Heater 3 Hi Fire Heater 3 Heater 2 Hi Fire Heater 2 Heater 1 Hi Fire Heater 1 Room T Probe set 2 0 10V 1 Natural curtain 1 Natural curtain 2 PROBES 9 EXPERT LA rev 00 EXPERT LA BACKUP...

Страница 10: ...es Do not connect the shield from the sensor cable to a terminal or a ground Extending a sensor Each sensor can be extended up to 500 feet 150 meters To extend a sensor use a shielded cable of outside...

Страница 11: ...ors Use these buttons to select a menu Main menu short cut key This short cut key provides access to the main menu and allows seeing the current sta tus of each input and output on the main screen The...

Страница 12: ...be displayed in multiple languages Follow these steps to change the language selection Select Main menu More Otros or Outros English Espa ol or Portugu s The controller automatically changes the lan g...

Страница 13: ...d LED tunnel door 2 is opening Close Solid LED tunnel door 2 is closing Open Solid LED tunnel door 1 is opening Close Solid LED tunnel door 1 is closing Open Solid LED natural ventilation curtain 2 is...

Страница 14: ...ersion is available you can install it in your controller by downloading a firmware file fir from the card Upgrading the firmware will not affect your parameter settings Access the transfer menu as ex...

Страница 15: ...guration files are a set of instructions that tells the controller what to do These files are di vided into two parts 1 Software screen menus 2 User data parameter settings You can save your controlle...

Страница 16: ...and 3 start if the switch is based on the outside temperature select the outside tem perature above which each program starts Note that program 1 is automatically used when the animal age or outside t...

Страница 17: ...s message is shown when the program selection is made manually i e it is not se lected as a function of the day and or out side temperature Select the running pro gram Only programs that are enabled i...

Страница 18: ...ency at which this servicing activity must be performed In all the controller can display 3 different warning messages When a warning message is active the word Warning is displayed on screen along wi...

Страница 19: ...ality 0 Total Mortality 0 New Culled 0 Today s Culled 0 Total Culled 0 New Marketed 0 Today s Marketed 0 Total Marketed 0 19 EXPERT LA rev 00 EXPERT LA 4 5 Installation Setup The following section sho...

Страница 20: ...led above This parameter is common to all programs Curtain compensation Select Yes to enable a compensation on the opening of natural ventilation curtains as a function of the outside temperature Acce...

Страница 21: ...r continuously Select Yes to enable this function Misting The controller can control one misting out put Select Yes to enable this output Misting output follows the set point Operating temperatures of...

Страница 22: ...4 7 1 Water spill limit Specify the maximum amount of water that can be consumed by each water meter per 15 min utes 0 10 000 gal or liters 15 min Accessible if a water meter is enabled sec 4 7 1 Stat...

Страница 23: ...per 15 minutes Thealarmisactivatedifagreater amount of water is consumed within the 15 minute delay Static Pressure Alarms The controller can sound an alarm when the static pressure SP level exceeds...

Страница 24: ...Use to navigate Logged at Jan 01 200X 12 00 A Temperature High F Probe 5 Defective Probe 4 Defective 11 ALARMS When an alarm occurs the controller lights up the alarm pilot light displays letters AL o...

Страница 25: ...above which the misting output and or the cool cell output stops or select Off to disable this function Accessible if the mist shutoff compensation and or cool cell shutoff option is enabled in sec 4...

Страница 26: ...4 Heaters 1 4 Hi fire opt 0 10V output Natural ventilation curtain 1 2 A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are dis played sec 4 5 Ass...

Страница 27: ...signment Select the desired output A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are avail able sec 4 5 Select a relay then set its status as f...

Страница 28: ...is required to per form a light peak cycle see previous graph The cycle time must be even or longer than the peak duration peak sunrise peak sunset Peak Duration Select during how much time the light...

Страница 29: ...to 60 minutes Number of Cycles Select how many cycles must be performed during the selected light program Adjust able from 1 to 6 cycles Main menu Start Stop Lights Light Settings Program X Use to nav...

Страница 30: ...er is in clean mode Refer to section 11 3 to set the clean mode alarm limit 63 EXPERT LA rev 00 EXPERT LA 8 LIGHTS The controller has one 0 10V output that can be used to control the light intensity A...

Страница 31: ...higher that its On Temperature If the Hi Lo fire option is used set this tem perature separately for both steps of the heating stage Main menu Start Stop Heaters Heaters Start Stop Use to navigate Hea...

Страница 32: ...ean mode Outside set point The controller can adjust the moving speed of natural ventilation curtains as a function of outside temperature When this function is used the controller refers to the outsi...

Страница 33: ...e Set Points The high low static pressure set points are the limits above and below which pressure based air inlets such as vent doors or tunnel doors open or close The controller allows using up to 3...

Страница 34: ...put s start temperature the output stops when tempera ture falls below a user defined value It can also stop when humidity levels are too high see RH Compensation in chapter 10 If the cool cell output...

Страница 35: ...essible if the temperature curve is enabled in the Instal lation setup sec 4 5 A password may also be required to access this menu The following parameters can only be modified while the curve is off...

Страница 36: ...in minimum ventilation The inlet is at its Closed position during the Off Time portion of minimum ventilation cycles it opens to the position associated with stage 1 during the On Time Over opening A...

Страница 37: ...Ventilation Cycles Definition Minimum ventilation cycles are activated when the average room temperature is below the start tem perature of fan stage 1 Running the fans even though ventilation is not...

Страница 38: ...when the static pressure level is lower than the low pressure set point The graph below illustrates this process Refer to chapter 5 to set the static pressure set points Wind Effect Delay When the pre...

Страница 39: ...now Select Yes to re set the actuator s position now Day time Set the time of day at which re sets are performed Period Set the frequency of inlet resets A reset can be performed once every 1 7 days...

Страница 40: ...5 A password may also be required to access this menu section 4 2 Make sure you have selected a timer based vent door inlet Refer to sec tion 4 5 to set vent door inlet func tions Vent door inlet ope...

Страница 41: ...g Vent Doors Inlets Vent doors inlets can either close when the con troller enters in natural ventilation or when the controller reaches a user defined tunnel ventilation stage Refer to the Installati...

Страница 42: ...enabled in the Installation Setup section 4 5 Timer If timer based relays are assigned to some fan stages sec 4 8 set the On Time and the Off Time of each timer based relay These On Off Times can be...

Страница 43: ...ening 45 sec Wind Effect Delay 0 30 m s 43 EXPERT LA rev 00 EXPERT LA 6 2 4 0 10V Ventilation Outputs The controller has a 0 10V output which can ei ther be used to control an air inlet or variable sp...

Страница 44: ...Relation between Fan Stages Natural Ventilation Curtains 49 EXPERT LA rev 00 EXPERT LA 6 4 2 Temperature Based Tunnel Doors Beginning of tunnel ventilation The activation of tunnel ventilation is link...

Страница 45: ...nel door starts opening after the Wind Effect Delay has elapsed Time Opening of Tunnel Doors as a Function of Static Pressure 45 EXPERT LA rev 00 EXPERT LA 6 3 2 Natural Ventilation Settings Select Ma...

Страница 46: ...os ing temperature When this situation occurs a de fective whisker switch alarm is posted to the alarm log Refer to section 4 8 to select what fan relays must turn off in natural ventilation Current o...

Страница 47: ...os ing temperature When this situation occurs a de fective whisker switch alarm is posted to the alarm log Refer to section 4 8 to select what fan relays must turn off in natural ventilation Current o...

Страница 48: ...nel door starts opening after the Wind Effect Delay has elapsed Time Opening of Tunnel Doors as a Function of Static Pressure 45 EXPERT LA rev 00 EXPERT LA 6 3 2 Natural Ventilation Settings Select Ma...

Страница 49: ...Relation between Fan Stages Natural Ventilation Curtains 49 EXPERT LA rev 00 EXPERT LA 6 4 2 Temperature Based Tunnel Doors Beginning of tunnel ventilation The activation of tunnel ventilation is link...

Страница 50: ...ening 45 sec Wind Effect Delay 0 30 m s 43 EXPERT LA rev 00 EXPERT LA 6 2 4 0 10V Ventilation Outputs The controller has a 0 10V output which can ei ther be used to control an air inlet or variable sp...

Страница 51: ...enabled in the Installation Setup section 4 5 Timer If timer based relays are assigned to some fan stages sec 4 8 set the On Time and the Off Time of each timer based relay These On Off Times can be...

Страница 52: ...g Vent Doors Inlets Vent doors inlets can either close when the con troller enters in natural ventilation or when the controller reaches a user defined tunnel ventilation stage Refer to the Installati...

Страница 53: ...5 A password may also be required to access this menu section 4 2 Make sure you have selected a timer based vent door inlet Refer to sec tion 4 5 to set vent door inlet func tions Vent door inlet ope...

Страница 54: ...now Select Yes to re set the actuator s position now Day time Set the time of day at which re sets are performed Period Set the frequency of inlet resets A reset can be performed once every 1 7 days...

Страница 55: ...when the static pressure level is lower than the low pressure set point The graph below illustrates this process Refer to chapter 5 to set the static pressure set points Wind Effect Delay When the pre...

Страница 56: ...Ventilation Cycles Definition Minimum ventilation cycles are activated when the average room temperature is below the start tem perature of fan stage 1 Running the fans even though ventilation is not...

Страница 57: ...in minimum ventilation The inlet is at its Closed position during the Off Time portion of minimum ventilation cycles it opens to the position associated with stage 1 during the On Time Over opening A...

Страница 58: ...essible if the temperature curve is enabled in the Instal lation setup sec 4 5 A password may also be required to access this menu The following parameters can only be modified while the curve is off...

Страница 59: ...put s start temperature the output stops when tempera ture falls below a user defined value It can also stop when humidity levels are too high see RH Compensation in chapter 10 If the cool cell output...

Страница 60: ...e Set Points The high low static pressure set points are the limits above and below which pressure based air inlets such as vent doors or tunnel doors open or close The controller allows using up to 3...

Страница 61: ...ean mode Outside set point The controller can adjust the moving speed of natural ventilation curtains as a function of outside temperature When this function is used the controller refers to the outsi...

Страница 62: ...higher that its On Temperature If the Hi Lo fire option is used set this tem perature separately for both steps of the heating stage Main menu Start Stop Heaters Heaters Start Stop Use to navigate Hea...

Страница 63: ...er is in clean mode Refer to section 11 3 to set the clean mode alarm limit 63 EXPERT LA rev 00 EXPERT LA 8 LIGHTS The controller has one 0 10V output that can be used to control the light intensity A...

Страница 64: ...to 60 minutes Number of Cycles Select how many cycles must be performed during the selected light program Adjust able from 1 to 6 cycles Main menu Start Stop Lights Light Settings Program X Use to nav...

Страница 65: ...is required to per form a light peak cycle see previous graph The cycle time must be even or longer than the peak duration peak sunrise peak sunset Peak Duration Select during how much time the light...

Страница 66: ...signment Select the desired output A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are avail able sec 4 5 Select a relay then set its status as f...

Страница 67: ...4 Heaters 1 4 Hi fire opt 0 10V output Natural ventilation curtain 1 2 A password may be required to access this menu sec 4 2 Only outputs that are enabled in the Setup menu are dis played sec 4 5 Ass...

Страница 68: ...above which the misting output and or the cool cell output stops or select Off to disable this function Accessible if the mist shutoff compensation and or cool cell shutoff option is enabled in sec 4...

Страница 69: ...Use to navigate Logged at Jan 01 200X 12 00 A Temperature High F Probe 5 Defective Probe 4 Defective 11 ALARMS When an alarm occurs the controller lights up the alarm pilot light displays letters AL o...

Страница 70: ...per 15 minutes Thealarmisactivatedifagreater amount of water is consumed within the 15 minute delay Static Pressure Alarms The controller can sound an alarm when the static pressure SP level exceeds...

Страница 71: ...4 7 1 Water spill limit Specify the maximum amount of water that can be consumed by each water meter per 15 min utes 0 10 000 gal or liters 15 min Accessible if a water meter is enabled sec 4 7 1 Stat...

Страница 72: ...r continuously Select Yes to enable this function Misting The controller can control one misting out put Select Yes to enable this output Misting output follows the set point Operating temperatures of...

Страница 73: ...led above This parameter is common to all programs Curtain compensation Select Yes to enable a compensation on the opening of natural ventilation curtains as a function of the outside temperature Acce...

Страница 74: ...ality 0 Total Mortality 0 New Culled 0 Today s Culled 0 Total Culled 0 New Marketed 0 Today s Marketed 0 Total Marketed 0 19 EXPERT LA rev 00 EXPERT LA 4 5 Installation Setup The following section sho...

Страница 75: ...ency at which this servicing activity must be performed In all the controller can display 3 different warning messages When a warning message is active the word Warning is displayed on screen along wi...

Страница 76: ...s message is shown when the program selection is made manually i e it is not se lected as a function of the day and or out side temperature Select the running pro gram Only programs that are enabled i...

Страница 77: ...and 3 start if the switch is based on the outside temperature select the outside tem perature above which each program starts Note that program 1 is automatically used when the animal age or outside t...

Страница 78: ...guration files are a set of instructions that tells the controller what to do These files are di vided into two parts 1 Software screen menus 2 User data parameter settings You can save your controlle...

Страница 79: ...ersion is available you can install it in your controller by downloading a firmware file fir from the card Upgrading the firmware will not affect your parameter settings Access the transfer menu as ex...

Страница 80: ...d LED tunnel door 2 is opening Close Solid LED tunnel door 2 is closing Open Solid LED tunnel door 1 is opening Close Solid LED tunnel door 1 is closing Open Solid LED natural ventilation curtain 2 is...

Страница 81: ...be displayed in multiple languages Follow these steps to change the language selection Select Main menu More Otros or Outros English Espa ol or Portugu s The controller automatically changes the lan g...

Страница 82: ...ors Use these buttons to select a menu Main menu short cut key This short cut key provides access to the main menu and allows seeing the current sta tus of each input and output on the main screen The...

Страница 83: ...es Do not connect the shield from the sensor cable to a terminal or a ground Extending a sensor Each sensor can be extended up to 500 feet 150 meters To extend a sensor use a shielded cable of outside...

Страница 84: ...i Fire Heater 4 Heater 3 Hi Fire Heater 3 Heater 2 Hi Fire Heater 2 Heater 1 Hi Fire Heater 1 Room T Probe set 2 0 10V 1 Natural curtain 1 Natural curtain 2 PROBES 9 EXPERT LA rev 00 EXPERT LA BACKUP...

Страница 85: ...side temperature sensor 75 days Inside humidity sensor 75 days Outside humidity sensor 75 days Static pressure sensor 75 days Run time of each heater 75 days Run time of each feeder 75 days Daily wate...

Страница 86: ...display Location 11 Unit selection 22 E Electrical specifications 76 English software 12 Evaporative pads see Cool cells F Fahrenheit units 18 Fan stages Activation 19 Current fan stage in use 72 Min...

Страница 87: ...story 73 Posting of marketed animals 74 Measuring units 18 Memory card Erasing the card 79 Transfer process 77 Menu selectors 11 Minimum ventilation Activation 37 Principle of operation 37 Relay assig...

Страница 88: ...ctivation 19 20 Principle of operation 48 Probe set 2 50 Settings 50 Static pressure limits 33 Tunnel doors temperature based Activation 19 20 Principle of operation 48 49 Probe set 2 50 Settings 50 U...

Страница 89: ...4 0 10V Ventilation Outputs 43 6 3 Natural Ventilation Curtains 44 6 3 1 Principle of Operation 44 6 3 2 Natural Ventilation Settings 45 6 3 3 Curtain Compensation 46 6 3 4 Stopping Fans in Natural Ve...

Страница 90: ...g 13 4 INSTALLATION SETUP 14 4 1 Setting the Time Date 14 4 2 Password 14 4 2 1 Entering Changing the Password 15 4 2 2 Retreiving a Lost Password 15 4 3 Controller Programs 16 4 3 1 Program Selection...

Страница 91: ...00 EXPERT LA NOTICE Every effort has been made to ensure that this manual is complete accurate and up to date The information contained in it is however subject to change without notice due to furthe...

Страница 92: ...m CleanMode Light Open Close Open Close Open Close Open Close Open Close Open Close 12 11 10 9 8 7 6 5 4 3 2 1 Min Vent 1 2 3 4 Misting Cool cell 0 10V Clock 1 Clock 2 Tunnel 2 Tunnel 1 Curtain 2 Curt...

Отзывы: