4/8/2008R series service manual
PAGE 13 OF 20
7.3.2 Indoor room temp. sensor or evaporator temp. sensor is open circuit or short circuit
7.2.3 EEPROM error
7.2.4 Cross zero signal error
7.2.5 High temp. Protect of condenser
When outdoor pipe temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe
temp. less than 52°C.
Is the indoor fan motor
connector and connection
good?
Repair the connector and
reconnect
Is voltage being applied to
the fan motor?
(rang 90v-160v between mid
pin and N on CN1
NO
YES
Indoor PCB is defective.
Replace the indoor PCB.
YES
Replace the indoor fan motor
NO
Is the indoor fan motor
connector and connection
good?
Repair the connector and
reconnect
Is voltage being applied to
the fan motor?
(rang 90v-160v between mid
pin and N on CN1
NO
YES
Indoor PCB is defective.
Replace the indoor PCB.
YES
Replace the indoor fan motor
NO
Is
power
supply
and
connection
of
connectors
good?
Indoor PCB is defective. Replace
the indoor PCB.
Be sure the power supply is good
and correct the connection
NO
YES
Circuit or software error on indoor
Replace indoor PCB
Содержание MSM-09HRN1
Страница 1: ...SERVICE MANUAL AirQ AIRCONDITIONER MULTI SPLIT TYPE MSM 09HRN1 MSM 12HRN1 MSM 30HRN1 V1 0 Dec 2007...
Страница 10: ...4 8 2008R series service manual PAGE 9 OF 20 6 Wiring diagram 6 1 Indoor unit...
Страница 11: ...4 8 2008R series service manual PAGE 10 OF 20 6 2 Outdoor unit For 1 drive 2 outdoor unit...
Страница 12: ...4 8 2008R series service manual PAGE 11 OF 20 For 1 drive 3 outdoor unit...