   5.02  If the inverter fails to operate, use the
following troubleshooting procedure.

5.02.1  Connect a 100 watt light bulb to

the inverter output.

5.02.2  Make sure the inverter is turned

"On", the output circuit breaker is reset and
that the voltage is at least 64 VDC at the DC
input terminals. If not, check DC wiring con-
nections and the line fuse.

5.02.3 Observe the fault indicating lights

on the front of the inverter.

a) The Low battery light indicates a low

DC condition. Switch the inverter “Off” for 5
seconds, then “On” again.  The light coming
on again indicates a fault in the DC wiring, DC
voltage, or the line fuse.

b) The Overload light indicates an output

wiring short circuit or a load that is too large
for the power rating of the inverter.  Switch the
inverter “Off”, remove the short circuit or
excessive load from the output, then switch
the inverter back “On”.

c) The High temperature light indicates

the inverter has overheated.  The unit will
automatically turn back on when it has cooled
to 40

0

C. Verify that the inverter is not in a

closed compartment and that the fan is not
blocked.
        5.02.4                 If the above steps are
completed and the inverter still will not oper-
ate satisfactorily, call Airpax Dimensions, Inc.
for a return authorization number.

Page 4

other source of AC power directly to the
output of the inverter. This will result in
damage to the inverter that is not covered
under warranty!
      3.06.2             The 120 VAC output of the
inverter is provided at the receptacle outlet on
the inverter.
    3.06.3 The 120 VAC output is also pre-
sented behind the wiring compartment panel
for direct hardwire wire leads. The black is hot,
the white wire is neutral and the green wire is
ground. The cable clamp strain relief should
be used to secure the field wires.
       3.06.4  Remote AC outlets should be
mounted at a convenient location in a listed
outlet box with approved strain relief. 

The

GFCI outlets should be Hubbell, Model GFR5352XX
(20A) or GFR5252XX (15A).

4. START UP/OPERATION
   4.01 
To operate the inverter turn the switch
to “On”.  Make sure that the output breaker is
reset.  Turn the switch to “Off” when the
inverter is not in use.

5. TROUBLESHOOTING
  5.01
   Dimensions offers free phone consul-
tation concerning installation or troubleshoot-
ing.
Call the Customer Service Department at:
1-651-653-7000 or 1-800-553-6418
fax: 1-651-653-7600
e-mail: [email protected]

NOTE:  Because the inverter has a quasi-sine
waveform, a TRUE RMS voltmeter (such as a
Fluke 87) is required for an accurate reading.
Other voltmeters that use averaging circuitry
will give incorrect readings.

Содержание ADI-64/500

Страница 1: ...L JANUARY 2007 Airpax Dimensions Inc DC to AC Power Inverters OWNERS MANUAL for Model 121335B ADI 64 500 Form 121335 Airpax Dimensions Inc 4467 White Bear Parkway 651 653 7000 St Paul MN 55110 7626 Fax 651 653 7600 ...

Страница 2: ... breaker and capacitor that may produce a spark Do not mount in a confined battery or gas compartment CAUTION Working in the vicinity of lead acid batteries is dangerous Batteries gener ate explosive gases during operation There is a risk of acid exposure There is also a risk of high current discharge from shorting the battery that can cause fire and explosion CAUTION Be sure both the inverter and...

Страница 3: ...n gas does not accumulate near the battery by keeping the area well ventilated A spark may result when connecting the battery wiring due to an initial charging of the internal input capacitor 3 05 2 Use stranded copper wire be tween the battery and inverter as indicated Aline fuse must be installed between the battery and the inverter within 18 inches of the battery DC Input Wire Lengths maximum a...

Страница 4: ...ctorily call Airpax Dimensions Inc for a return authorization number Page 4 other source of AC power directly to the output of the inverter This will result in damage to the inverter that is not covered under warranty 3 06 2 The 120 VAC output of the inverter is provided at the receptacle outlet on the inverter 3 06 3 The 120 VAC output is also pre sented behind the wiring compartment panel for di...

Страница 5: ...w battery High Temperature Charge voltage adjustment External power Output breaker POS NEG BondingLug Fuse Fuseholder and Fuse AC Hardwire Output On Off Inverter power Inverter Overload FRONT VIEW 64 VDC Source ...

Страница 6: ...RANTY Dimensions warrants to the original purchaser for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship for a period of 1 year from the date of purchase provided suchgoodsareinstalled maintainedandusedinaccordancewithDimensionsandtheoriginalmanufacturer swritteninstructions ComponentsnotmanufacturedbyDimensions butusedwithintheassembl...

Отзывы: