In-duct air purifier system V10P-ID
Status display / control / troubleshooting
Regularly inspect the air duct for external objects that might obstruct or damage
the module. Check the device and ensure that the LEDs are properly working.
LED
indicator light Status
Troubleshooting
green
on
ready for operation operating voltage
is present
–
off
not ready for
operation
no operating voltage
check electrical
connection
blue
on
photocatalysis in
operation
system running
–
off
photocatalysis off
ventilation system off -
no air flow
check ventilation
system
air flow too low -
unit switched off
check air flow
operating voltage missing /
indicator light green?
check electrical
connection
device error / internal defect exchange / repair
Green LED (A):
the unit is properly connected
to a valid power source (Standby
mode).
Blue LED (B):
the device is actively purifying
the air (photocatalytic process in
progress).
Function
control
Display
Operating voltage /
load current photocatalysis
Max. deviation
Press and
hold the check
button (C)
top
voltage
12 V
- + 1.0 V
down
current
2.2 A
- + 0.6 A
current (two units)
4.5 A
- + 1.0 A
Checking the photocatalytic unit
Checking is only possible when the unit is switched on.
If the values on the display are significantly different from those in the chart, one or more LEDs are possibly
faulty and need to be replaced.