Page 22
b.1.) INPUTS SPECIFICATIONS
Input Impedance:
Y1 and Y2
~1K Ohm between: each terminal to
C
(24VAC Return).
Minimum acceptable cooling anticipator resistance: 3.3K Ohms between 24Vac(R) to
Y1 or Y2
All other inputs:
>10K Ohm between each terminal and
C
(24VAC return).
Load Current FORM FACTOR — All Inputs:
Positive Half-Wave (with respect to C
(24VAC RTN)
MIN AND MAX INPUT VOLTAGE – All 24VAC Inputs:
Signals ACTIVE
: 20VAC minimum. 30VAC Maximum; Current: <15ma @30VAC.
Signals INACTIVE
: <4VAC (Current from any signal source, switch, and/or external
snubbers must hold inputs to <4VAC or DC)
NOTE: DO NOT CONNECT THE SWITCHED 24VAC INPUTS FROM A 2
nd
, SEPARATE
TRANSFOMER THAN THE 24VAC SOURCE SUPPLYING POWER TO THIS CONTROL
UNLESS
THE
TRANSFORMER
SUPPLYING
THIS
CONTROL
AND
THE
2
ND
TRANSFORMER ARE PHASED PROPERLY WITH THEIR COMMONS CONNECTED.
4.
OUTPUTS
A. CONNECTIONS TO EC MOTOR (ECM): J3 PIN-OUTS (SEE FIG 3):
J5–pin-1:
START/STOP
: When the Blower motor is commanded to operate this signal
enables motor operation. (Use is optional. Use if the system requires a separate
enable.)
0VDC = not enabled, 22VDC (nom) = enabled
10ma maximum sourced current.
J5–pin-2:
COMMON
– J5 Outputs Common (to
isolated
common input(s) on
motor/drive).
DO NOT CONNECT COMMON TO 24VAC RET
J5–pin-3
: PWM Motor Command
: 0% to 100% duty-cycle.
OFF: 0VDC (min). ON: 22VDC (peak). 10ma max sourced current.
When measured on a DC voltmeter, the signal level varies from 0VDC to
~22VDC max as the percent PWM duty cycle increases from 0 to 100%.
The
Green LED
“
BLWR CMND
” illuminates when the PWM command is active.
Brightness increases with PWM duty cycle.
J5–pin-4: NO CONNECTION
B. HIGH VOLTAGE RELAY OUTPUTS:
a.
A1, A2, A3 (PUMP) Relay (Formerly “WV RELAY”)
Contacts A1 (NO), A2 (NC) to A3 (Pole): A3 is “Dry” and can be connected to an
external voltage source for switching to A1, A2.
The WV Relay is energized under the following conditions:
1) SWITCH “PUMP TMR ON” POSITION,
AND
2) Upon detecting a call for W1 or W2 (no delay)
OR
3) If W1 or W2 was not active for 6 (or 24) consecutive powered hours.
The
green “W_TIMER” LED
illuminates when the PUMP relay is activated.
b.
ACCESSORY Relay (ACC, ACCp):
Contact ACC (NO) connects to pole ACCp. These are DRY Contacts and can be
connected to an external voltage source.
The Accessory relay is energized with
"G"
. i.e. Any call from the thermostat
that
includes
an active "G" signal energizes this relay.
c.
MAXIMUM CONTACT
RATINGS:
Содержание MaxAir 100e P2
Страница 43: ...Page 43 WIRING DIAGRAM P2 UNITS...
Страница 44: ...Page 44 WIRING DIAGRAM P3 UNITS...
Страница 45: ...Page 45 WIRING DIAGRAM P2 UNITS ALTERATIONS HEAT PUMP OPTION...
Страница 46: ...Page 46 WIRING DIAGRAM P3 UNITS ALTERATIONS HEAT PUMP OPTION...
Страница 51: ...Page 51 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Страница 52: ...Page 52...
Страница 53: ...Page 53...
Страница 54: ...Page 54...
Страница 55: ...Page 55...
Страница 56: ...Page 56...
Страница 61: ...Page 61 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Страница 62: ...Page 62 SAMPLE PIPING SCHEMATICS...
Страница 63: ...Page 63...
Страница 64: ...Page 64...
Страница 65: ...Page 65...