background image

2

IO-123114 Effective 12-04-2014

4. Installation Preparation

4A. Clearances

4B. Installation Options

4C. Condensate Drain

4D. Ductwork

Read all the instructions in this guideline carefully while paying spe

-

cial attention to the WARNING and CAUTION alerts. If any of the 

instructions are unclear; clarify with certified technicians. Gather all 

the tools needed for successful installation of the unit prior to begin-

ning the installation.

If the unit is to be installed in garages, warehouses or other areas 

where they may be subjected to physical damage, adequate protec-

tive barriers must be installed. Unit 

MUST

 be installed 18” away from 

source of ignition. 

If  the  unit  is  located  in  high  humidity  areas  like  attics  or  uncondi

-

tioned  garage;  the  air  handler  casing  might  experience  nuisance 

sweating. In such installation scenarios, wrapping the casing with a 

2” fiberglass insulation with vapor barrier 

SHOULD

 be used.

The drain lines must be installed with ¼” per foot pitch to provide free 

drainage. A condensate trap MUST be installed on the primary drain 

line to ensure proper drainage of the condensate. The trap must be 

installed in the drain line below the bottom of the drain pan (Fig. 

4D-1)

Since coil is upstream of the blower, all drains MUST be 

trapped or sealed. Failure to do so will re-

sult in condensate overflow from the drain 

pan. Aspen will NOT be responsible for any 

damages resulting from failure to follow these instructions.

CAUTION

!

Ductwork for air conditioning systems should be installed in accor-

dance with standards of the National Fire Protection Association 

Pamphlet No. 90A or 90B, and also be sized in accordance with 

National Environmental System Contractors Association Manual K, 

whichever is applicable.

On any job, non-flammable flexible collars should be used for the 

return air and discharge connections to prevent transmission of vi-

bration. Although these units have been specially designed for quiet 

vibration-free operation, air ducts can act as soundboards, and if 

poorly installed, amplify the slightest vibration to the annoyance level.

All main supply and return air drops should be properly size as deter-

mined by the designer of the duct system and should not necessarily 

be the size of the duct flange openings of the unit.

The drain pan has primary (white) and secondary (red) drain connec-

tions. If a secondary drain line is required, it should be run separately 

from the primary and should terminate in a highly visible location. 

Condensate disposal through the secondary drain line indicates that 

the primary drain line is plugged and needs cleaning. If a secondary 

drain line will not be provided, plug the secondary drain. Drain plugs 

are NOT to be reused without plumbers tape or putty. The drain line 

connectors should be hand tightened to a torque of approximately 

35-40 lb (4-5 turns).

Fig 4A-1. Air Handler Dimensions

Fig 4D-1. Condensate Drain Trap

3. Inspection

ü

 On receiving the product, visually inspect it for any major shipping 

related damages. Shipping damages are the carrier’s responsibility. 

Inspect the product labels to verify the model number and options 

are in accordance with your order. Manufacturer will not accept dam-

age claims for incorrectly shipped product.

Drain lines from the auxiliary drain pan 

should NOT be connected to the primary 

drain line of the coil.

CAUTION

!

If the drain pan is constructed of nylon 

or plastic; use Teflon tape to connect the 

drain lines to the threads in the drain pan. 

DO NOT USE SOLVENT BASED PIPE DOPE. THIS WILL RE-

DUCE THE LIFE OF THE PAN.

CAUTION

!

When installing a central air return grille in or near the living space, 

it is advisable to design the ductwork so that the grille is not in direct 

line with the opening in the unit. The use of one or two elbows and 

acoustical duct liner will also ensure quieter system operation. 

It is recommended that wherever supply and return air sheet metal 

duct pass through unconditioned areas, they be insulated to pre-

vent excessive heat loss during heating operation. When applied in 

conjunction with summer air conditioning, sheet metal duct routed 

through unconditioned areas should be insulated and have an out-

side vapor barrier to prevent formation of condensation.

The GAT & GAS series of horizontal ceiling mount air handlers are 

designed for zero clearance installation on the sides and back.

Содержание GAS Series

Страница 1: ...r service personnel CAUTION CAUTION WARNING WARNING WARNING WARNING WARNING WARNING GAT GAS Series Horizontal Ceiling Mount Electric Heat Dx Cool Air Handler 2 Introduction The GAT GAS Series air hand...

Страница 2: ...vel All main supply and return air drops should be properly size as deter mined by the designer of the duct system and should not necessarily be the size of the duct flange openings of the unit The dr...

Страница 3: ...burr free and clean Failure to do so may increase chances of a leak It is recommended to use a pipe cutter to remove the spun closed end of the suction line To reduce air leakage rubber gommets may b...

Страница 4: ...nstructions are separated into sec tions by metering device 2 A ducted return requires a non louvered panel 1 A bottom return installation requires a louvered panel 3 Both louvered and non louvered pa...

Страница 5: ...eflon O ring is located between the two halves of the flowrator CAUTION I 2 Replace the Teflon O ring located between the halves Discard Schrader if present During some installations a piston change m...

Страница 6: ...to install the right valve can lead to poor per formance and possible compressor damage CAUTION Ensure that the TXV bulb is in direct con tact with the suction vapor line Gap be tween the bulb and tub...

Страница 7: ...to the liquid line stub out See 8A I 3 Do not attempt to touch brazed joints while hot Severe burns may result WARNING III 3 After ensuring that the Teflon O ring seal is still in place inside the flo...

Страница 8: ...connections using proper brazing pro cedures 9 When all line connections are brazed perform a proper system evacuation procedure per the outdoor unit manufacturer instructions 10 Seal the penetration...

Страница 9: ...t 42 61 S Small Cabinet 18 36 Heat Strip 00 NO Heat BLOWER DATA UNIT MODEL RPM AMP VOLT HP CFM VS STATIC PRESSURE 0 00 0 10 0 20 0 30 0 40 GAT 18 1625 1 4 240 1 4 850 775 700 675 600 GAT 24 1000 900 8...

Страница 10: ...ssure measuring device 0 1 0 in slope gauge and a tempera ture measuring device 0 200 F thermometer 3 Release system charge from outdoor unit and call for cooling 4 Use outdoor unit equipment manufact...

Страница 11: ...are so that you may cut off the flow of energy in the event of overheating WARNING optimum equipment efficiency and performance Inspect and clean or replace filters every month This routine maintenanc...

Страница 12: ...MER 24 VOLTS HTR 3 BK CB CB LC LC HS LO SPEED CAPPED MED SPEED CAPPED HS HS BLOWER MOTOR SPEED SETTING FOR MAX KW RATING UNIT MODEL MAX KW SPEED TAP ELECTRIC HEAT ONLY ELECTRIC HEAT HEAT PUMP MAX KW S...

Страница 13: ...IO 123114 Effective 12 04 2014 13...

Страница 14: ...Atascocita Rd Humble TX 77396 Phone 281 441 6500 Toll Free 800 423 9007 Fax 281 441 6510 www airmark ac com Copyright 2014 AirMark All Rights Reserved Revised 12 04 2014 Subject to change without not...

Отзывы: