AirJet 2100 ALL-FUEL CHIMNEY Скачать руководство пользователя страница 5

APPLICATION (B) Two or More Story Installation of 6S and 8S Chimney

  After the frame opening is completed for the ceiling base support (6SCCB or 8SCCB) and the base support
is installed in the first floor level, use a plumb-bob to align and locate the next framed opening in the next floor
levels. Frame an opening 12 1/2” square for 6S or for the 8S, 14 1/2” square. See Figure 2A, and 5. Framed
openings must line up precisely. 

Be sure to maintain the required minimum clearance to combustibles.

  Install a radiation joist shield (6SJS or 8SJS) from below, at all floors (except roof), above base support with 6d nails
(2 each side, 2” from the ends). This provides firestop at the frame opening and establishes and maintains required
minimum clearance between chimney section and combustible materials in this area.

  The final framed openings (to attic) requires the installation of an insulation shield (6SIS or 8SIS). (Remove insulation
from around this area.) Place the female end of the starter pipe section down over the centering flange on the base
support (6SCCB or 8SCCB) (see Figure 3).

  Then assemble enough pipe sections to pass from base support (6SCCB or 8SCCB) through the joist shield (6SIS or
8SIS). Assemble pipe by aligning seams and pressing straight down until the click is heard. Remove any insulation or
other foreign materials from inside joist shield that might have fallen in.

  Lower the insulation shield (6SIS or 8SIS) down from above, over the pipe until it sets on the framed opening. Using
6d nails, nail down with 2 nails on each side, 2” from the ends. See Figure 4. Next place insulation shield collar over
pipe and push down until it rests on top of insulation shield. Make sure there is no gap between collar and shield.
Tighten the stove bolt and nut which draws the collar tight around the pipe.

Continue installation as required (see Step 2).

STEP  2. Locate the center point where the chimney will pass through the roof by using a plumb-bob. Cut an opening

large enough to provide a 

minimum of 2” clearance all around the chimney section

. See figure 5

showing frame opening size required.

            3. Install the boot flashing (6 or 8SBF) making sure the flashing cone is centered over the roof opening so the

chimney pipe is plumb and the 

2” air space clearances are maintained

. Before attaching the flashing to

the roof, place a bead of caulk under the edges. Slip flashing under overlapping roof shingles as far as
possible before nailing flashing to roof. Trim, cut or replace shingles to fit cone as necessary. Thoroughly
caulk around edges of flashing. Add chimney sections until the pipe extends through the flashing (see Figure
8.)

            4. Install storm collar (6 or 8 SSC) on the top pipe section and slide down until it contacts the high side of the

flashing cone. Put a bead of roofing cement between the storm collar and pipe section to insure a leak free
installation.

            5. Chimneys shall extend at least 3 feet above the highest point where they pass through a roof of a building

and at least 2 feet higher than any portion of a building within a horizontal distance of 10  feet (see Figure 1).
If the chimney extends more than 6’, external bracing will be required. Plumbers tape may be wrapped
around chimney and secured with a minimum of three (3) guy wires anchored to roof, 120° apart (see Figure
8A).

            6. Install the termination cap (6 or 8SU) tightening the screws on collar until the cap is fastened securely to

section.

Figure 8

Figure 8A

GUY WIRES

Содержание 2100 ALL-FUEL CHIMNEY

Страница 1: ...meet new criteria for wood burning applications exclusive snap lock design for fast easy installation heavy duty interior liner Tools You Will Need Power Saber Saw Hammer and Nails Screwdriver Plumb Bob Caulking Gun Tin Snips SUPPLIES 10d nails 8d nails 6d nails silicone caulk or roof tar 10 screws plumbers tape Please read Instruction Notes inside before starting AirJet Inc 3020 Mine Road Frederi...

Страница 2: ...ng of 50 A minimum clearance of 2 inches of air space to combustible materials building insulation enclosure walls and roof must be maintained Do not place any insulation material in clearance spaces around pipe Clearances at floor joists and ceilings are established by the installation of the factory furnished base supports and firestop shields and may be less than 2 The flue gas exits must be a ...

Страница 3: ... is located is to be provided with an enclosure having a fire resistance rating equal to or greater than that of the floor or roof assemblies through which it passes The following installation applications take into account the various building constructions single floor two floor and multi floor INSTALLATION OF 6S OR 8S CHIMNEY 1 Through the Ceiling Installation Cut and frame a square opening in ...

Страница 4: ...r pipe and push down until it contacts top of the insulation shield Make sure there is no gap between collar and shield Tighten the stove bolt and nut which draws the collar tight around the pipe Continue installation as required see Step 2 Figure 5 Figure 5A Figure 5C Figure 5B Multi Story Installation Single Story Installation Chimney Housing Top Assembly Telescoping Connector Chimney Housing Co...

Страница 5: ...push down until it rests on top of insulation shield Make sure there is no gap between collar and shield Tighten the stove bolt and nut which draws the collar tight around the pipe Continue installation as required see Step 2 STEP 2 Locate the center point where the chimney will pass through the roof by using a plumb bob Cut an opening large enough to provide a minimum of 2 clearance all around th...

Страница 6: ...h against the wall and mark through the screw holes onto the wall see Figure 10 Remove the tee from the support and screw the support to the wall at the marked location with nine 9 10 screws Place the tee female end down while sliding the snout through the thimble making sure to maintain required clearance to combustibles Tee snout must protrude through the wall a minimum of 1 Snout is adjustable ...

Страница 7: ...oof peak or building projection then it must terminate at least 2 above such peak or projection height see Figure 1 8 Place termination cap 6SU 8SU down until it is firmly in place Tighten the screws on collar until cap is fastened securely on the top pipe section 9 Install weather shield 6SWSH 8SWSH Using screws provided place two halves of weather shield around the tee to cover the outside wall ...

Страница 8: ...below the first elbow a second wall band should be installed around the vertical return elbow Second wall band will require framing out from wall for attachment Remember to maintain the 2 clearance to combustible requirement Terminate as described in Step 8 If the overhang is too wide for offsetting finish the chimney as you would with a ceiling installation Remember to maintain the 2 clearance to...

Страница 9: ... see Figure 14 3 Place starter pipe section into roof support 6SRS 8SRS with female end down over centering flange Install section of pipe onto starter section by aligning the seams and pressing straight down until a click is heard Slide boot flashing 6SBF 8SBF over pipe into place over roof opening Lay bead of caulk under edge of flashing Check to see that chimney is vertical and attach flashing ...

Страница 10: ... Seal the plastic bag around the opening with tape so no debris will escape Clean tee snout in the same manner as the top cap and smoke pipe sections were cleaned Shove debris toward tee support outside so it will be collected in the plastic bag Then attach a plastic bag around the tee snout in the same manner as on the tee support NOTE If deposits are very heavy or you are unable to clean the chi...

Отзывы: