8
-
For the ceiling position use the condensate outlet in section i2 (EHA)
●
Connect a pipe or hose (not included; a standard washing machine hose is recommended) to the condensate outlet and shape it
into a siphon trap with dimensions as shown in the picture. Appropriately secure the siphon trap shape and connect it to the
sewer line.
●
Check the entire length of the pipe including the parts inside the unit for free passage and its sloping.
●
Prime the condensate drain siphon trap.
5.7
Classification of air filters
●
IF the unit is fitted with filters of various filtration grades (F7 and F5), then the F7 grade filter is an outdoor air filter (ODA) and the
F5 grade filter is an extract air filter (ETA).
●
The outdoor air filter is installed in chamber e1 (ODA), the extract air filter in chamber i1 (ETA).
5.8
Installing air filters
●
The unit is supplied with separately packaged filter cassettes. Remove and unpack the cassettes and check their condition.
Then install the cassettes in their proper locations on the unit as shown in 5.7.
Unpack and install air filters last, immediately before putting the unit into service to avoid their contamination.
●
Should any damage or contamination be detected, replace them with new ones. Spare filter cassettes are to be ordered from the
s
upplier. The
suppliers
address and the spare cassette part number are shown on the identification plate of the unit.
●
Insert undamaged clean filters into the guide rails and secure following the instructions in the pictures: