14
up).
Installation Instructions
SECOND FIX – Installing Horizontal Mounted Unit
Connect 22mm PVC drain fitting
Floor mounting
5.
6. Mount
the remote control near the unit.
Fix securely to a flat surface. For
maintenance please ensure the remote
control is disconnected before removing
the unit from the wall.
The unit can be floor mounted by using
the horizontal mounting kit,
Part Number 90000558
Use the long and short S brackets
provided along with short fitting screws
to ensure correct drainage. The unit must
be higher at the duct end.
Bracket fixing position. See Page 13
Drain connections should be solvent
welded as here. The center Tee section is
reversed to make either LH or RH
drain. Push in the drain fitting and seal
as appropriate to create a watertight
assembly
.
When fixing the remote control please
ensure the ribbon cable is in place
(contacts down, red side up)
RH
LH
Important note: The floor mounted drain
must be fitted on the same side as the factory
fitted drain. This unit is for wall or floor mount
only. Ceiling mounting units are configured
differently and should be ordered separately.