16
For the appliance to work properly and safely it is necessary to correctly connect a condensate
drain line!
Connect a tube or a hose to the condensate drain outlet (not supplied; we recommend using a
conventional washing machine hose) and shape it into a trap. Install the trap in the mounting
position (see the pictures below), with the trap size according to chapter 5.8. Secure the trap
shape suitably and run the condensate drain line into a drain outlet.
The following rules must be adhered to during the installation of the water chiller:
The water chiller in all versions must be filled with an antifreeze solution with sufficient thermal
resistance, or it must be drained as long as the outdoor temperature might drop below 0°C.
Maximum permitted operating positive pressure is 1.0 MPa!
The inlet of the chilled water system into the unit must be equipped with a sludge filter.
5.17.
Installing mixing valve of the water chiller
During the mechanical installation and connection of the control manifold of the hot water heater follow
the instructions supplied with this optional accessory.
5.18.
Installing direct chiller
During the mechanical installation of the direct chiller follow the manual supplied with this optional
accessory.
During the connection of the direct chiller follow the instructions of the supplier of condensation
units and connecting pipes.
5.19.
Installing electric heater / pre-heater EPO-V
During mechanical installation and electrical connection follow the manual supplied with this
optional accessory.
Electrical connections may only be made by a qualified electrician authorized to service power
supply networks.
Attention - extra care should be taken regarding the installation conditions of EOP-V heater as
they cannot be installed at randomly selected locations! For specific conditions see the manual
included with this optional accessory.
5.20.
Installing manostats to control constant flow and constant
pressure
During mechanical installation and electrical connection follow the manual supplied with this optional
accessory.
Ceiling-suspended position
Floor-standing position