Installation Data
Chilled water pipework and ancillary components must be installed in accordance with:
•
National and Local Water supply company standards
•
The manufacturer's instructions are followed when fitting ancillary components
•
The system liquid is treated to prevent corrosion and algae forming
•
In ambients of 0°C and below, where static water can be expected, or when water
supply temperatures of +5°C or below is required, the necessary concentration of
Glycol or use of an electrical trace heater must be included
WATER SYSTEM
•
The schematic is referred to as a guide to ancillary recommendations
CAUTION
The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.
1
Place Grooved Ends Together
2
Locate Rubber Gasket
•
Note that an expansion gap of 5mm is
shown here
•
The gasket should be checked for
compatability and damage prior
to installation
•
A thin coat of sealing lubricant should
be applied to both the inside and
outside mating surfaces
•
Slip the gasket fully onto one of the
pipe ends, align the second pipe and
slide the gasket into place
3
Place Clamp over Gasket
4
Secure Clamp
•
Wrap the 2-halves of the clamp over
the gasket
•
Ensure the gasket fits snugly within the
grooved recess within the inside of the
clamp and that the clamp
mates correctly
•
Tightend the bolts incrementally and
evenly at both sides until a leak free
seal is formed
•
The gasket should not be visible
beneath the clamp when the bolts are
properly tightened
GROOVED & CLAMPED
TYPE CONNECTION