Technical Data SD CLCL Units
Waterside Pressure Drop Data
Includes coil, 2 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
2
M
Q
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
36
Kv
Fluid 100% water.
Kv Cooling Kv Bypass
SD31D190-CLCL
63
63
SD35D225-CLCL
63
63
4
SD31D190-CLCL-0
5
SD35D225-CLCL-0
0.00
50.00
100.00
150.00
200.00
250.00
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
Pre
ss
ure
D
ro
p (
kP
a)
Flow Rate (l/s)
SD31D190-CLCL-0
SD35D225-CLCL-0
5
4
SmartCool™ 6 - 200kW