Chilled Water Components
System Configuration
Range
SN
SR
SD
Number of Circuits
Single
Single
Dual
Single
Dual
Chilled W
ater
Hydrophilic Epoxy Coated RTPF Chilled Water Coil
●
●
●
●
●
0-10 Volts Chilled Water Regulating Valve (2 Way)
●
●
●
●
●
0-10 Volts Chilled Water Regulating Valve (3 Way)
○
○
○
–
–
0-10 Volts Chilled Water Regulating Valve
(2 x 2-Way) Auto Commission
–
–
–
○
○
Pressure Independant Control Valve (PICV)
○
○
○
○
○
Brazed Connections
●
●
●
●
●
Threaded Connections
○
○
○
○
○
Grooved Connections
–
–
–
○
○
Flanged Connections
–
–
–
○
○
●
Standard Features
○
Optional Features
–
Feature Not Available
Chilled Water Coil
Chilled water coils shall be ideally positioned to optimise airflow and heat transfer, they shall be manufactured from plain
copper tubes with mechanically bonded aluminium fins. Fins shall be coated with a non-stick acrylic film (hydrophilic) to
provide additional corrosion protection and efficient surface water removal for improved performance. Plain aluminium
shall not be acceptable. The cooling coil shall be mounted over a full width stainless steel condensate tray. A 22mm
condensate drain hose connection shall be available. For control of water flow, various valve options shall be fitted.
The factory test pressure shall not be less than 20 Barg and the maximum operating pressure shall be less than 10.
Sweat copper pipe for brazed connection shall be standard. Optional threaded and Grooved connections shall be
available.
SmartCool™ 6 - 200kW
Precision Air Conditioning
14
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018